9140053441 Rev. 1 

                                                                                                                                                                                 1 

 

 

 
 

LZ SERIES 

EMERGENCY LED EXIT  

 

Service Questions Call: (800) 334-8694 

 

IMPORTANT SAFEGUARDS 

 
When  using  electrical  equipment,  basic  safety 
precautions  should  always  be  followed,  including 
the following: 

 

READ AND FOLLOW ALL 

SAFETY INSTRUCTIONS 

 

All  servicing  should  be  performed  by  qualified 
personnel only. 
 
Do not mount near any heat producing equipment. 
 
Equipment  should  be  mounted  in  locations  and  at 
heights  where  it  will  not  be  readily  subjected  to 
tampering by unauthorized personnel. 
 
The  use  of  accessory  equipment  not  recommended 
by the manufacturer may cause an unsafe condition. 
 
Do  not  use  this  equipment  for  other  than  intended 
use. 
 
In Class I Division 2 locations, do not replace any 
non-metallic hardware with metal hardware. 
Contact authorized agent for factory replacement 
parts. 
 
In Class I Division 2 areas, install equipment in 
accordance with appropriate NEC articles plus any 
other applicable codes. 
 
To avoid static discharge, do not attach any 
ungrounded metal hardware to the enclosure. 
 
Do not use this equipment outdoors

.

 

 

CLASS I DIV 2 

HAZARDOUS LOCATION 

GROUPS A, B, C, AND D 

ZONE 2 GROUPS IIC, IIB AND IIA 

CLASS II DIV 2 GROUPS F AND G 

AND CLASS III DIV 1 AND 2 

 

INSTALLATION AND OPERATING 

INSTRUCTIONS 

 

 

 
 
 

 

 

 
 
 
 

Install only grounded wiring systems to supply 
this equipment. 
 
Free installation area of hazardous atmospheres 
before wiring equipment or servicing, this reduces 
the risk of accidental explosion due to inadvertent 
battery shorting during installation. 

 

 

SAVE THESE INSTRUCTIONS

WARNING  –  Shut  off  AC  power  to  branch 
circuits  to  which  units  will  be  connected.  All 
wiring should be per N.E.C.  wiring methods  for 
Hazardous locations. 

 

To  maintain  warranty,  equipment  with  batteries 
must  be  installed  or  placed  on  charge  within 
prescribed period after shipment. 
 
 

Содержание LZ Series

Страница 1: ...lacement parts In Class I Division 2 areas install equipment in accordance with appropriate NEC articles plus any other applicable codes To avoid static discharge do not attach any ungrounded metal hardware to the enclosure Do not use this equipment outdoors CLASS I DIV 2 HAZARDOUS LOCATION GROUPS A B C AND D ZONE 2 GROUPS IIC IIB AND IIA CLASS II DIV 2 GROUPS F AND G AND CLASS III DIV 1 AND 2 INS...

Страница 2: ... See Figures 1 and 2 4 Connect conduit supply to hub on unit 5 Hookup AC service to the connector assembly as follows Enclosure Cover Screws 2 Lens Screws 4 Hub Vent Test Switch Figure 1 Figure 2 AC Charge IR Receiver Status Indicator 120 VAC OPERATION 277 VAC OPERATION Black Wire 120V Line Blue Wire 277V Line White Wire Common White Wire Common Green Wire Ground Green Wire Ground Unused primary w...

Страница 3: ... adhesive backing are supplied Apply label s to exit lens as necessary 7 Remount exit lens using lens screws Close cover and secure with cover screws INSTRUCTIONS OPERATION 1 Energize AC power to exit Unit will initiate normal power up sequence See page 4 ...

Страница 4: ...ll flash for up to 36 hours to indicate that the unit is in battery charging mode Allow 72 hours for the battery to fully charge User Interface Green LED Indicator Steady On AC power is present and battery is fully charged Slow Flash Battery charging Fast Flash Unit is performing an automatic or manually initiated self test Red LED Indicator Single Flash Battery fault Double Flash Lamp failure Tri...

Страница 5: ...9140053441 Rev 1 5 ...

Отзывы: