Lithonia Lighting ELM2 LED Скачать руководство пользователя страница 3

INSTALLATION INSTRUCTIONS

SAVE THESE INSTRUCTIONS 

and deliver to owner after installation

PAGE: 3 of 4

A. Normal Operation:

 When the unit is functioning properly, with power applied, the “TEST” switch will be illuminated red.

B. To Test:

 Press the “TEST” switch. The fi xture will remain illuminated. When switch is released, the lamps will go off.

      

NOTE:

 See important battery information before testing.

INSTALLATION & MAINTENANCE

To Open Housing:

Press both circular snaps at the bottom of the hous-
ing. Lift the housing upward and pull it fi rmly away 
from the mounting plate.

Lamp Replacement:

Disconnect the wire harness for the LED lamp board. 
Unscrew the screws holding the LED lamp board to 
the refl ector. Re-attach the new LED lamp board onto 
the refl ector and connect the connector.

Charger Board Replacement:

Flex the snap at each end of charger board and pull 
it straight out of the housing. Disconnect lamphead 
wires from board and reconnect them to new board. 
Slide charger board into place, make sure it is se-
cured by the snaps on both ends.

Lens Removal:

Using small straight blade tool, gently remove 
the lens from the lamp head as shown above.

Battery Replacement:

Disconnect battery connector. Cut cable tie 
and remove battery. Install new battery in 
orientation as shown above. Reconnect battery 
connector.

IMPORTANT BATTERY INFORMATION:
Allow battery to charge for 24 hours 
before testing and fi rst use. Batteries 
are perishable items. For best results, 
it is recommended that the battery 
receive an initial charge within the fi rst 
3 years of the manufacture date of the 
fi xture. The manufacture date can be 
found on the outside of the unit pack-
aging and on the UL label as part of 
the Date Code/Series.

Snaps

TEST 

switch

Содержание ELM2 LED

Страница 1: ...TANCES MAY DAMAGE FIXTURE WHICH MAY RESULT IN PERSONAL INJURY WARNING RISK OF PERSONAL INJURY This product may have sharp edges Wear gloves to prevent cuts or abrasions when removing from carton handling installing and maintaining this product WHERE APPLICABLE Before wiring to power supply turn off electricity at fuse or circuit breaker Disconnect AC power and unplug battery before servicing Consu...

Страница 2: ...ensure proper engagement of the snaps in the mounting plate to the housing DO NOT OVERTIGHTEN SCREWS With AC power turned off connect battery connector leads CAUTION Continuous AC power must be available at time of installation as damage to the battery will occur if the battery is connected to the charger board for more than 3 days Align the holes on the bottom of the housing with the circular sna...

Страница 3: ...ct the connector Charger Board Replacement Flex the snap at each end of charger board and pull it straight out of the housing Disconnect lamphead wires from board and reconnect them to new board Slide charger board into place make sure it is se cured by the snaps on both ends Lens Removal Using small straight blade tool gently remove the lens from the lamp head as shown above Battery Replacement D...

Страница 4: ...mergency lighting system must be tested monthly for a minimum of 30 seconds and annually for 90 minutes Refer to your local codes for any additional requirements that may apply NOTE Unused input lead must be properly insulated with wire nut or other approved method One Lithonia Way Conyers GA 30012 Phone 800 334 8694 www lithonia com OPTIONAL VOLTAGE ORANGE 220V 240V BLACK 120V WHITE Neutral OPTIO...

Отзывы: