INSTALLATION INSTRUCTIONS

PAGE: 2 of 4

NOTE:

 This unit should be mounted ONLY through a pair of the preformed keyholes onto a 4” “OCTAGON” junction box, or 

through a pair of the keyhole knockouts onto a 4” SQUARE junction box.

NOTE:

 The maximum mounting height for the standard model is 12.3 feet.

 

 The maximum mounting height for the HO model is 11.0 feet.

Feed the fi xture leads through the mounting plate and 
make connections to AC power supply.

Use only Flexible Conduit with this 
unit. Must be used with 4” j-box.

Dress the wires into the junction box. Secure the mounting 
plate onto the junction box with a minimum of two screws.

NOTE:

 To ensure proper engagement of the snaps in the 

mounting plate to the housing, DO NOT OVERTIGHTEN 
SCREWS.

With AC power turned off, connect battery connector 
leads. 

CAUTION:

 Continuous AC power must be available 

at time of installation as damage to the battery will occur 
if the battery is connected to the charger board for more 
than 3 days.

Align the holes on the bottom of the housing with the circular 
snaps at the bottom of the mounting plate and push the 
housing directly onto the mounting plate. 

(NOTE: Make 

sure red battery wires are securely inside bat-
tery compartment prior to mounting housing 
onto mounting plate.)

 

The two at the bottom, as well as the two hidden snaps at 
the top should make an audible snap when fully engaged. 
Apply continuous AC power and check that the test switch is 
illuminated red, indicating proper function.

Содержание ELM2 LED

Страница 1: ...TANCES MAY DAMAGE FIXTURE WHICH MAY RESULT IN PERSONAL INJURY WARNING RISK OF PERSONAL INJURY This product may have sharp edges Wear gloves to prevent cuts or abrasions when removing from carton handling installing and maintaining this product WHERE APPLICABLE Before wiring to power supply turn off electricity at fuse or circuit breaker Disconnect AC power and unplug battery before servicing Consu...

Страница 2: ...ensure proper engagement of the snaps in the mounting plate to the housing DO NOT OVERTIGHTEN SCREWS With AC power turned off connect battery connector leads CAUTION Continuous AC power must be available at time of installation as damage to the battery will occur if the battery is connected to the charger board for more than 3 days Align the holes on the bottom of the housing with the circular sna...

Страница 3: ...ct the connector Charger Board Replacement Flex the snap at each end of charger board and pull it straight out of the housing Disconnect lamphead wires from board and reconnect them to new board Slide charger board into place make sure it is se cured by the snaps on both ends Lens Removal Using small straight blade tool gently remove the lens from the lamp head as shown above Battery Replacement D...

Страница 4: ...mergency lighting system must be tested monthly for a minimum of 30 seconds and annually for 90 minutes Refer to your local codes for any additional requirements that may apply NOTE Unused input lead must be properly insulated with wire nut or other approved method One Lithonia Way Conyers GA 30012 Phone 800 334 8694 www lithonia com OPTIONAL VOLTAGE ORANGE 220V 240V BLACK 120V WHITE Neutral OPTIO...

Отзывы: