8
H.
Setting
H-1 Parameter Setting
For optimum braking performance, the braking unit must be set to parameter P3-03
(stall prevention during deceleration) to zero.
H-2 Voltage Setting
According to different AC voltage input, users need to set on the braking unit switch
and this setting will affect the braking unit action level. Below shows more details :
[ Input voltage dip switch ]
400V class AC Power
Starting Voltage
380Vac
660Vdc
400Vac
690Vdc
420Vac
720Vdc
440Vac
750Vdc
460Vac
780Vdc
480Vac
780Vdc
200V class AC Power
Starting Voltage
190Vac
330Vdc
200Vac
345Vdc
210Vac
360Vdc
220Vac
375Vdc
230Vac
390Vdc
240Vac
390Vdc