Wiring Diagram 

G-1 Main Circuit 

R/L 1

S/L 2

T/L 3

U/T 1

V/T 2

W/T 3

E

-

+

IM

Braking Unit

MCCB MC

Fast Acting Fuse

R

S

T

Braking Resistor

 

 

For safety consideration, install an overload relay between the braking unit and 

the braking resistor. In conjunction with the magnetic contactor(MC) prior to the 

drive, it can perform complete against abnormality. 

 

The  purpose  of  installing  the  thermal  overload  relay  is  to  protect  the  braking 

resistor  from  damage  due  to  frequent  braking,  or  due  to  braking  unit  keeping 

operating  resulted  from  unusual  high  input  voltage.  Under  such  circumstance, 

just turn off the power to prevent damaging the braking resistor. 

Note

 

 

Inflammable solids, gases or liquids must be avoided at the location where the 

braking  resistor  is  installed.  The  braking  resistor  has  better  be  installed  in 

individual metallic box with forced air-cooling.   

 

Connect  the  ground  terminal  to  the  Earth  Ground.  230V  followers  the  third 

grounding construction. 460V followers the special third grounding construction. 

 

Please  install  braking  resistor  with  forced  air-cooling  or  the  equivalent  when 

frequent deceleration braking is performed (over 10ED%). 

 

To  prevent  personal  injury,  do  not  connect/disconnect  wires  or  regulate  the 

setting of the braking unit while power on. Do not touch the terminals of related 

wiring and any component on PCB lest users be damaged by extreme dangerous 

DC high voltage.   

 

The ring terminals are suggested to be used for main circuit wiring. Make sure the 

terminals are fastened before power on. 

 

The cable distance between the inverter and the brake unit should be less than 2 
meters. The brake unit and brake resistor should be less than 1 meter, and the 

master-slave parallel control line (B1) and (B2) should be less than 30 cm. 

Содержание EVO6-DBU-43D7

Страница 1: ...ety because the input terminals of the braking unit and braking resistor are filled with high voltage Make sure to fully tighten screws when installing C Wiring Notice Do not proceed with wiring while...

Страница 2: ...2 D EVO 6 DBU Design D 1 440V Power Input Terminal Fault Lamp Power Lamp Brake Lamp Input Voltage Setting Switch Master Slave Terminal Relay Output Terminal Master Slave Switch Brake Resistor Terminal...

Страница 3: ...3 D 1 220V Power Input Terminal Fault Lamp Power Lamp Brake Lamp Input Voltage Setting Switch Master Slave Terminal Relay Output Terminal Brake Resistor Terminal Master Slave Switch...

Страница 4: ...4 E Dimensions Unit mm...

Страница 5: ...te 10 ED Overheat Protection Braking unit Overheat Alarm 95 Power Charge Display The Main circuit voltage is extinguished below PN 50VDC Overheat Alarm Output Relay Output 250VAC under 1A 30VDC under...

Страница 6: ...g resistor has better be installed in individual metallic box with forced air cooling Connect the ground terminal to the Earth Ground 230V followers the third grounding construction 460V followers the...

Страница 7: ...G 3 Multiple installation master slave parallel G 4 Terminal Wire Gauge Terminal AWG kcmil mm 2 Screw Suggestion Available Suggestion Available P N B1 B2 10 14 8 2 58 1 63 3 26 M3 M1 M2 S1 S2 RA RB RC...

Страница 8: ...ltage input users need to set on the braking unit switch and this setting will affect the braking unit action level Below shows more details Input voltage dip switch 400V class AC Power Starting Volta...

Страница 9: ...r Resistor Value Spec Resistor Quantity HP kW 460V 0 5 0 4 300W 400 1 1 0 75 300W 400 1 2 1 5 400W 300 1 3 2 2 600W 200 1 5 3 7 900W 120 1 230V 0 25 0 2 200W 250 1 0 5 0 4 200W 250 1 1 0 75 200W 150 1...

Отзывы: