APPENDIX 1
Inspection instructions:
Project:
Location:
Unit name:
1
CHECKING THE NORMAL FUNCTIONING:
Designation
Colour Remark
Expected
(1)
FIRE A
red
Fire alarm
Off
FIRE B
red
Fire alarm
Off
FAULT
yellow
Shows the fault status of the SCU
Off
OPERATION
green
Power is on
On
MEASUREMENT
yellow
Lights up every 10s for a few
seconds
Blinking
DATA TRANSMISSION
yellow
lights up sporadically in the SCU is
connected to a SCADA system
Yes
(2)
No
(2)
2
NUMBER OF ACTIVE MEASURING POINTS (SENSORS):
Procedure
Remark
Expected
(2)
(1)
1. open the SCU 800
1.
2. press TA1
Data transmission LED:
slow blinking
= tens
fast blinking
= units
(sum of both sensor cable connections)
3
CHECK FOR DAMAGE AND LOOSE MOUNTING DEVICES:
Check:
(1)
the correct mounting of the sensor cable
all mountings are closed
all boxes are dry and glands are tight
(1)
Should any of the above points
not be OK, report this to the responsible maintenance service immediately.
(2)
These values can be found in the commissioning protocol and can be pre-specified on the from according to the project
specifications.
Name:
Date:
Signature:
60T028
LISTEC GmbH
Page 1/1
60T023-01 / 24/01/08
LISTEC GmbH
Page 28/28