background image

Troubleshooting Step By Step Procedure

The following is a step by step procedure to help in troubleshooting any problems with this
boiler.   These   steps   should   be   performed   only   by   qualified   personnel   with   experience   in
hydronic   heating   systems,   and   electrical   heating   equipment.   You   are   working   with   high
voltages and should be extremely careful.

Before energizing boiler, ensure system is full of water.

(1) Make   sure   that   there   is   power   to   the   boiler.   There   must   be   power   to   the   boiler   to

complete these troubleshooting steps.
 a) On 240 volt single phase models there should be power at the main terminal block.

You should read 120 volts between L1 and N, 120 volts between L2 and N, and 240
volts between L1 and L2.

 b) On three phase models there should be power at the main terminal block. You should

take three readings on the main terminal block, you should read the appropriate
voltage for your model between L1 and L2, between L2 and L3, and between L1 and
L3. You should also read 120 volts on the terminal block on the lower right side on
the terminals labeled SL and SN.

 c) Disconnect the thermostat wires from the terminals “STAT 1”. Measure the voltage at

the top of the boiler at each heating element. If you measure voltage at any of the
elements,   then   the   element   relay   for   that   element   is   stuck   on   and   needs   to   be
replaced.

(2) Check the fuse on models equipped with a fuse.

 a) Remove the fuse located inside the boiler. Check it for continuity. Replace with a new

fuse of the correct type if necessary.

 b) Otherwise replace the existing fuse.

(3) Check that there is 24 volt AC power on the secondary side of the transformer. These

are the two wires running from the transformer to the control board. There must be 24
volt AC power on the secondary side of the transformer for the boiler to operate. If there
is no power the transformer needs to be replaced.

(4) With  the thermostat  wires still  disconnected from  step  (1)c),  disconnect  the outdoor

sensor as well, then connect a jumper wire from one terminal of STAT 1 to the other
terminal of STAT 1.
 a) This should energize the relay to the right of the control board, you should hear a

click. If not check that there is 24 volt AC power on the two terminals with purple
wires.

 b) If there is no power at the relay, the control board needs to be replaced.
 c) If there is power, but the relay is not turning on, replace the relay.

(5) When the relay is energized, it will supply 120 volt power for running the pump, and

activate the control board.
 a) There should now be 120 volt AC power to the terminals labeled PL and PN.
 b) If there is no power, replace the relay.

(6) With the circuit board now activated, the power relays should turn on one at a time.

There is about a one to two minute delay before the first relay turns on, and about the
same for each additional relay. If they have not started to come on as yet, temporarily

20

Содержание CEBR Series

Страница 1: ...an appropriate antifreeze Do not use any other liquids especially methanol automotive antifreeze or any kind of oil Do not exceed 50 antifreeze LION BOILERS CEBR Series Boiler Installation Manual CEB...

Страница 2: ...2...

Страница 3: ...le phase power to terminals L1 and L2 and connection of a neutral conductor to the N terminal see Fig 4 Three phase models require connection of three phase power of the correct voltage to the L1 L2 a...

Страница 4: ...he aquastat By modulating the boilers heat output based on both the indoor and outdoor temperature your CEBR model provides you with the ultimate in indoor comfort The graph below is an example with t...

Страница 5: ...8 11 11 25 208 3 31 2 40 32 CEBR 208 15 14 7 208 3 40 8 60 48 CEBR 208 22 22 5 208 3 62 5 100 80 CEBR 208 30 29 4 208 3 81 6 125 100 CEBR 600 9 9 600 3 8 7 15 12 CEBR 600 15 14 7 600 3 14 1 20 16 CEBR...

Страница 6: ...g system Pressure will decrease at a rate of 0 433 psi per foot above the fill point An expansion tank must be included to allow for approximately 4 expansion of the water in the entire heating system...

Страница 7: ...r the boiler 3 Though the unit is suitable for floor or wall mount only faces indicated as Zero Clearance may be mounted against combustible surfaces 4 Units must be mounted straight as shown in Fig 2...

Страница 8: ...block lower right terminal block see Fig 4 and Fig 5 The pump starts when the thermostat terminals on the control board are closed and stops when these terminals are opened If desired the pump may be...

Страница 9: ...on pump and not the boiler the anticipator should be set to match the current draw of the zone valve being used Temperature Control Setting The boiler has a temperature control knob know as an aquasta...

Страница 10: ...and thoroughly purged of air The automatic air vent is to assist in removing air from the top of the tank to prevent elements from burning out It alone is not sufficient in removing air from the entir...

Страница 11: ...cipator setting Check pump circulation Boiler operates continuously Check anticipator setting Boiler noisy Oversized pump Flow rate too high Flow rate too low Pump location incorrect Boiler not heatin...

Страница 12: ...that Boiler The obligation of the Manufacturer to repair replace or refund the purchase price exists provided the defective part or complete unit is returned to the Manufacturer ANY AND ALL TRANSPORT...

Страница 13: ...ITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS LIMITED WARRANTY THE MANUFACTURER S LIABILITY ON ANY CLAIM OF ANY KIND INCLUDING NEGLIGENCE WITH RESPECT TO THE GOODS OR SE...

Страница 14: ...14...

Страница 15: ...15...

Страница 16: ...16...

Страница 17: ...17...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...Check the fuse on models equipped with a fuse a Remove the fuse located inside the boiler Check it for continuity Replace with a new fuse of the correct type if necessary b Otherwise replace the exist...

Страница 21: ...e sure the boiler and the heating system are completely full of water a Unplug the low water cut off from the control board Temporarily no more than one second place a jumper wire across the two pins...

Отзывы: