Installation Guide Power Supply
DE
Page 6 / 12
Power range 480 W
NTI AG / LinMot
Safety / Standards
IEC60950 / UL60950 / UL508 / CSA22.2-60950 / CSA22.2-107.1 / IP20,
safety class 1 / pollution degree 2
EMC
Mains feedback / PFC
EN 61000-3-2 Class A only with ext. PFC 12mH/4, 5A/230VAC
Flicker
EN 61000-3-3
Interference immunity
EN 61000-6-2 Industrial generic standard
ESD
EN 61000-4-2 8/15KV
Electrical fields
EN 61000-4-3 noise level 10V/m (Krit. A)
Burst
EN 61000-4-4 4KV (Krit.A)
Surge
EN 61000-4-5 4/2KV (Krit.A)
HF Immunity
EN 61000-4-6 noise level 10V (Krit.A)
Voltage drop
EN 61000-4-11
Interference emission
EN 61000-6-4 Industrial generic standard
EN 55011 Class B, Radiation depends on assembly
Weight
1.0 kg
4 Operating data
Temperature range
-25°C...70°C (integral, temperature-regulated fan, sucking in air from below)
Derating
3% / K at +60°C (see diagram chapter 7)
Due to the integrated fan, the SPH500 can be installed in any position. The passage of air
must not be obstructed by installation.
The distance to the air vents must be at least 20 mm. Fire protection must be ensured
via the outer casing system.
Protect the products against moisture, humidity, condensation and dirt.
5 Mechanics
5.1 Connection
Mains input:
4-pol terminal
1.5 - 4/6 mm² strand / wire
tightening torque 0.6 - 0.7 Nm
Load output:
4-pol terminal
1.5 - 4/6 mm² strand / wire
tightening torque 0.6 - 0.7 Nm
Control signals: 4-pol terminal, pluggable
0.1 - 0.5 mm² strand / wire