Door Operator / CDO/ LC-3158 Rev.B 

Stuart Road,       Manor Park,       Runcorn,       Cheshire,       WA7 1TS

T: +44 (0)1928 579050     F: +44 (0)1928 579259     www.linkcontrols.co.uk     [email protected]

Warning : Please read these instructions fully before installation

Link Controls

Instructions for Rolling Door Operator type :

Содержание CDO Series

Страница 1: ... Manor Park Runcorn Cheshire WA7 1TS T 44 0 1928 579050 F 44 0 1928 579259 www linkcontrols co uk enquiries linkcontrols co uk Warning Please read these instructions fully before installation Link Controls Instructions for Rolling Door Operator type ...

Страница 2: ...opriate safety equipment Capable of recognising the dangers associated with installation Only qualified and trained electricians may connect the operator and carry out electrical maintenance Qualified and trained electricians fulfil the following requirements knowledge of the general and specific safety and accident prevention regulations knowledge of the relevant electrical regulations trained in...

Страница 3: ...e fluctuations EN 61000 6 2 Electromagnetic compatibility EMC Part 6 2 Generic standards Immunity for industrial environments EN 61000 6 3 Electromagnetic compatibility EMC Part 6 3 Generic standards Emission standard for residential commercial and light industrial environments Machinery guidelines EN 60204 1 Safety of machinery electrical equipment of machines part 1 general requirements EN 12100...

Страница 4: ...er a lengthy storage period all connections have been carried out correctly the direction of rotation of the drive motor is correct all motor protective devices are active no other sources of danger exist the installation site has been cordoned off over a wide area Information The relevant instruction for the door must be observed when fitting the drive to the door a suitably rated mains protectio...

Страница 5: ...n failure CDO Operator Information Link Controls Ltd constantly strives to improve the quality of its goods and as such reserves the right to replace modify products without prior notification Any examples given are intended for guidance only Self Aligning Flange Bearing End Plate Shutter Barrel Drive End Shaft Weld into Position Plate Wheel Drive Chain Sprocket End Plate Self Aligning Flange Bear...

Страница 6: ...ypes of cable and their diameters must be selected according to current regulations The nominal currents and the type of connection must correspond to those on the motor type plate The drive details must agree with the connected loads Information When operated with electronic control units the corresponding start up instructions and circuit diagrams must be complied with 5 Installation 6 Initial O...

Страница 7: ...l operate should the motor be overloaded The Hand Chain Interlock provides a means of control circuit isolation to prevent electrical operation whilst the door is being operated manually Warning To ensure compliance with BS 7671 wiring regulations IET the Thermal Trip must be connected into the relevant controller safety circuit Stop circuit Note For operators with a disengage clutch the disengage...

Страница 8: ...he CLOSED direction The operator must close the door Drive the door in the OPEN direction The operator must open the door Information If the door s direction of travel does not correspond to the commands keyed in then the direction of rotation must be changed Instructions for changing the direction of rotation are given in the control unit operating manual After this the direction of travel must b...

Страница 9: ...l unit operating manual for instructions on setting the limit end positions A B Wiring allocation AVE absolute value encoder plug The numbers on the plug are also the wire numbers 4 Safety circuit input N C 5 RS 485 B 6 GND 7 RS485 A 8 Safety circuit output N C 9 7 18V DC AVE absolute value encoder plug terminal 7 12 C Thermal element in the drive D Manual emergency control emergency crank or emer...

Страница 10: ... site During maintenance works or in the case of an electrical failure the door can be moved towards the OPEN or CLOSED positions with the help of the emergency manual override equipment Information If the door is moved beyond the CLOSED or OPEN end positions the operator may no longer be activated electrically place the door back into a normal position before attempting powered operation Operatio...

Страница 11: ...ches Check for noises and oil leaks Check the mounting of the operator for corrosion Check the housing for damage Operation with emergency floor level hand chain KE Releasing Gently pull the cable with the red handle downwards as far as possible The control voltage will be interrupted and the door can no longer be operated electrically Release the emergency hand chain from its fixing Move the door...

Страница 12: ...000 6 2 Electromagnetic compatibility EMC Part 6 2 Generic standards Immunity standard for industrial environments EN 61000 6 3 Electromagnetic compatibility EMC Part 6 3 Generic standards Emission standard for residential commercial and light industrial environments EN 60335 2 103 Particular requirements for drives for gates doors and windows The relevant technical documentation is compiled in ac...