Dear Customer: 
 
Thank you for buying a Linear commercial boiler. 
 
The Linear is a cast iron, oil or gas fired hot water boiler, using the famous 3-pass design. The 
boiler is simple, rugged and engineered for maximum heating efficiency. 
 
We  realize  that  it  is  not possible  to  answer  all  questions  about  the  Linear  series  boiler  in  this 
manual.  Reading  this  installation  manual  does  not  make  the  reader  an  expert  in  all  aspects  of 
installation  and  operation,  and  does  not  replace  the  need  for  a  qualified,  licensed  heating 
contractor. We urge you to contact your installing contractor or distributor if you are in question 
about any aspect of your boiler's performance. Our main concern is that you are satisfied with 
your  boiler  and  its  performance.    We  require  that  your  contractor  complete  efficiency  tests 
using instruments. 
 

 

The controls and accessories listed in this manual are intended to serve as guidelines rather than 
specific  recommendations.  We  realize  that  other  makes  and  models  of  such  devices  are 
available and can be used as successfully  as those we specify. The installing contractor is the 
best judge of a system's specific requirements, as well as the local availability of certain makes 
and  models  of  controls  and  accessories.  The  preceding  does  not  apply,  however,  to  the 
equipment  that  comes  with  every  boiler,  such  as  the  overheat  control  (L4006E)  and  pressure 
relief valve. 

The installation of the specific devices supplied with every boiler is absolutely 

necessary to the safe operation of the boiler and protection of the heating system. 

 
This Linear boiler has a limited warranty, a copy of which is provided with the boiler.  Please 
be sure to return the warranty registration card as the warranty will be void without your boiler's 
serial numbers, date of installation and the name of your installer being on record in our files. 
 
Thank  you  for purchasing our  B-40  Linear series boiler.   If  you have questions or comments, 
please don't hesitate to contact us immediately. Our goal is 100% customer satisfaction. 
 

 

Содержание 6-12 SECTION

Страница 1: ...UTH NH 0380 PORTSMOUTH NH 0380 PORTSMOUTH NH 0380 PORTSMOUTH NH 03801 1 1 1 PHONE 603 PHONE 603 PHONE 603 PHONE 603 334 334 334 334 6400 6400 6400 6400 FAX 603 FAX 603 FAX 603 FAX 603 334 334 334 334...

Страница 2: ...lines rather than specific recommendations We realize that other makes and models of such devices are available and can be used as successfully as those we specify The installing contractor is the bes...

Страница 3: ...er Location 5 7 Boiler Block Assembly 6 8 Boiler Trim Kit Installation 7 8 Boiler Tapping Diagram 9 Burner Set up 8 10 Gas Piping 9 12 Breeching and Chimney 10 14 Piping 11 15 Boiler Jacket Assembly 1...

Страница 4: ...operating properly when the installation is completed Do not burn volatile garbage gasoline naphtha or other flammable liquids other than No 2 fuel oil All flammable liquids especially gasoline chemi...

Страница 5: ...g flu season A victim may not experience any symptoms only one symptom or a few symptoms Suspect the presence of carbon monoxide if symptoms tend to disappear when you leave your home The following si...

Страница 6: ...ontent Gals Length L inches Weight LBS B40 6 6 265 2 20 308 230 86 0 17 34 8 902 B40 7 7 352 2 90 406 305 86 7 20 39 5 1023 B40 8 8 437 3 60 504 380 86 8 23 44 4 1144 B40 9 9 524 4 30 602 456 87 0 26...

Страница 7: ...AL In general boiler rooms should incorporate two 2 permanent air supply openings one commencing within 12 inches of the ceiling and one commencing within 12 inches of the floor These openings should...

Страница 8: ...rter draw rods are installed on the bottom of the boiler The bottom draw rods should not extend past the front section Draw the sections together until sections make iron to iron contact at a point ar...

Страница 9: ...the location and function of the front and rear boiler tappings Boiler Model Length L B 40 6 34 8 B 40 7 39 5 B 40 8 44 5 B 40 9 49 2 B 4 10 53 9 B 4 11 58 8 B 4 12 63 9 2 5 MPT Return 2 5 MPT Supply...

Страница 10: ...L FULL Nozzle 2 00 X 45 2 25 X 60 2 75 X 60 3 25 X 60 3 75 X 60 4 5 X 45 5 50 X 45 Spray Pattern solid solid solid solid solid solid solid Pump Pressure 140 psi 170 psi 175 psi 175 psi 175 psi 160 psi...

Страница 11: ...1 Setting the electrode and flame rod settings against manufacturer s specs to insure proper operation 2 Installing properly sized gas piping according to BTU input required and length of gas line ru...

Страница 12: ...1 for proper sizing of gas piping for various lengths and diameters Locate a drop pipe adjacent to but not in front of the boiler Locate a tee in the drop pipe at the same elevation as the gas inlet c...

Страница 13: ...union 4 A drip pipe Caution The gas valve should not be subjected to more than PSIG Therefore the burner should be isolated during high pressure gas leak tests The appliance and its individual shut o...

Страница 14: ...and 400F gross stack temp so caution should be used when connecting to an outside built chimney Should you have concern that the flue gases could condense then you should consider using a listed powe...

Страница 15: ...hould be supported by suitable hangars and floor stands not by the boiler It is recommended that the make up water line have a backflow preventer and a pressure reducing valve to reduce line pressure...

Страница 16: ...BIASI B 40 PAGE 16...

Страница 17: ...nd screw on the threaded hex spacers 87 onto the studs Attach the lower mounting bracket 83 to the boiler by using two bolts 89 and screw ing them into the threaded hex spacers Then using sheet metal...

Страница 18: ...er shall come from a dedicated breaker in the electric service box A service switch should be mounted on the side of the boiler so the burner man can service the burner and controls The electrical wir...

Страница 19: ...the manual high limit 5 Circulator Switch Supplies power to boiler circulator or relay panel It is not suggested to use this switch and it is not utilized in any of the suggested wiring diagrams in th...

Страница 20: ...BIASI B 40 PAGE 20 B 40 Control Panel Wiring Diagram for Beckett Heat Wise Oil Burner 24V CIRCULATOR RELAY BURNER CONTROL...

Страница 21: ...PAGE 21 BIASI B 40 B 40 Control Panel Wiring Diagram for Beckett Heat Wise Oil Burner Line Voltage CIRCULATOR RELAY BURNER CONTROL...

Страница 22: ...BIASI B 40 PAGE 22 B 40 Control Panel Wiring Diagram for Riello Oil Burner...

Страница 23: ...PAGE 23 BIASI B 40 B 40 Control Panel Wiring Diagram for Heat Wise Gas Burners CIRCULATOR RELAY Burner Primary Control...

Страница 24: ...he flexible oil line Brush and vacuum combustion chamber and flue passages until all deposits are removed Reassemble components in reverse order making sure any damaged gaskets are repaired or replace...

Страница 25: ...________________ ______________________ _________________________ ______________________ Burner Manufacturer Type of Oil Burner Burner Model No Burner Serial No Nozzle Manufacturer Nozzle Spray Angle...

Страница 26: ...BIASI B 40 PAGE 26...

Страница 27: ...PAGE 27 BIASI B 40...

Страница 28: ...lled with approved burner and that installation conforms to all codes and ordinances 4 This warranty does not apply to boilers which are subject to misuse abuse neglect alteration accident excessive t...

Отзывы: