UltraLink Controller
FTCU
lindab | we simplify construction
Please note:
•
Do not remove the transducers!
•
Do not use transducers as handles when you mount the FTCU since this
may cause damage!
Transducers
•
Make sure the airflow arrow is pointing in the direction of the airflow.
IP42
Status
Airflow
m³/h l/s m/s °C
Lindab
UltraLink
Monitor
FTMU
Airflow
direction arrow
•
Rotate the senor body to the correct position according to next page
.
•
On FTCU’s sizes 400 — 630 loosen the nut so the sensor body can be
turned into the desired position. The flange must then be fastened by tight-
ening the nut.
Flange
•
Position the display so it is visible from a suitable direction.
•
Mount the FTCU into the air duct system according to the
•
When the FTMU is positioned accurately it should be fixed with screws to
the damper body in the same way as when you connect ducts and fittings.
•
Never use a FTCU on the outlet side of a duct fan. Place it on the inlet side
or in worst case use a flow conditioner if it must be placed on the outlet
side.
•
The longer distance to disturbance, i.e. the longer straight duct before the
UltraLink®, the higher the measurement accuracy will be.
D
uc
t f
an
•
The motor direction switch must always be set to “1” as supplied.
•
You are not allowed to make any changes or adjustment to the motor or its
end-stops!
Motor direction switch
Airflow
direction arrow
•
If the damper needs to be turned manually, then press the manual override
button on the motor and turn the damper shaft with a 8 mm wrench or
similar.
Motor override
button
Damper shaft
Mounting