Lindab UltraLink FTCU Скачать руководство пользователя страница 13

13

Lindab reserves the right to make changes without prior notice

2020-08-05

UltraLink Controller  

FTCU

lindab  |  we simplify construction

Correcting flow measurement for installation  

close to disturbance

Later UltraLinks have a function to compensate for mount-
ing the product closer to a disturbance, and still have 5% 
measurement uncertainty, than what is specified in the 
chapter “Mounting”. If it is required to install an UltraL-
ink close to a disturbance, the correction is done via a 
function in the UltraLink app. Connect a mobile device to 
the UltraLink and tap the “Device” tab, there is a function 
which is activated by choosing “Type of disturbance” and 
then “Distance to dirsturbance”. After these two inputs 
have been made, the function is active and corrects the 
flow according to the inputs made.

Controller FTCU Ø125

Serial no. 132600052

Ultra

Link

Lindab

®

ID-numbers

The FTCU is given an 
ID-number between 1 to 
239 during production. 
The given ID-number can  
be seen on the label on the outside of the box the FTCU 
is delivered in, the ID-number is the same as the three last 
digits in the serial number.

If two or more Modbus devices have the same ID-number 
it is necessary to apply changes so that each of them get 
an unique ID-number to allow communication.

To change the Modbus ID register of an UltraLink

®

 all other 

devices with the same ID must be disconnected. It is more 
efficient to change the ID in the display under “Con.Set” 
(See page  14 for more info). The register for Modbus ID 
is a holding register with address 4x001.

PIN code

UltraLink with Bluetooth must be protected againt unau-
thorized access by PIN-code, which has to be stated 
before changes to the settings can be made. It is important 
to choose and change the code that the product is deliv-
ered with (1111), to ensure that no unauthorized changes 
are made. The Bluetooth radio can be disabled by setting 
register 4×007  
to 0.

The code can be changed in three ways:

•  using the configuration menu in the display, see page 13 

for instructions.

•  connecting a PC via Modbus and using the “Configura-

tion Tool” software.

•  connect a Bluetooth device and use the “UltraLink” 

application.

Maintenance

The FTCU does not normally require any maintenance. The 
visible parts of the device can be wiped with a damp cloth.

Settings for override

The FTCU has two different override functions that can 
be initiated either over the bus or with analog input (only 
in case of input voltage range of 2-10 V or 10-2 V). If 
controlled via bus (register 4x071 = 0),  then the damper 
can be forced (register 4x151) to fully open or fully closed 
position, or the flow rate setpoint can be set to minimum 
or maximum flow rate setpoint (according to registers 
4x315 and 4x316, respectively). If the unit is controlled with 
analog input (4x071 = 1), then the damper can be forced 
to fully closed position (regardless the settings in register 
4x501, which represents the minimum angle (fully closed) 
of the damper in normal mode).

Override function by bus:

1.  Normal mode, no override (register 4x151 = 0).

2.  Go to maximum flow rate setpoint (register 4x151 = 1).

3.  Go to minimum flow rate setpoint (register 4x151 = 2).

4.  Go to fully open damper position (register 4x151 = 3).

5.  Go to fully closed damper position (register 4x151 = 4).

If an override is initiated, it can be restored either manually 
by setting register 4x151 to 0, or automatically after the 
predefined override timeout in register 4x150.

Analog override function:

In analog mode (4x071 = 1), the override function can only 
be called if input voltage range is set to 2-10 V or 10-2 V 
(4x500 = 2 or 3, respectively) and the controlled variable is 
flow rate (4x070 = 2). If these settings are active, the over-
ride function is set as follows:

1.  Normal mode, no override (input voltage ≥ 2 V).

2.  Go to fully closed damper position (if input voltage is 

lower than the value defined in register 4x511).

Содержание UltraLink FTCU

Страница 1: ...of reproduction without written permission are forbidden is the registered trademark of Lindab AB Lindab s products systems product and product group designations are protected by intellectual proper...

Страница 2: ...us on energy saving has led to ventilation systems requiring low min imum flows The low flows are a problem since they are very difficult to measure and it is makes it difficult to control the ventila...

Страница 3: ...nected to a display unit The display unit is mounted on top of a shelf on the damper body The sensor and damper bodies can rotate relative to each other This means that the sensors can be optimally po...

Страница 4: ...ion Mount the FTCU into the air duct system according to the mounting instructions for Lindab Safe When the FTMU is positioned accurately it should be fixed with screws to the damper body in the same...

Страница 5: ...the uncertainty of the measurement It is recommended to mount the FTCU so that the first flow sensor is placed on the inner radius of a fitting see table below For example in the case of the bend in t...

Страница 6: ...ment uncertainty or X l s depending wich is the greatest of percentage or the absolute value for the specific product size see table Technical data on page 19 a 2 4 d 4 5 d 5 d Reducer a d Duct diamet...

Страница 7: ...ation cables to the premounted cable Check the label on cable for reference to cable colours It is important that the cable is as short as possi ble for optimal Modbus communication For cable connecti...

Страница 8: ...ion Cable type 24 V Supply 2 wire thickness depending on length and load max 1 5 mm RS485 Modbus communication 2 wire shielded twisted pair min 0 1 mm LIYCY cable Using other cables for Modbus signals...

Страница 9: ...us the shield is broken at each transformer so SH on every product only has connection to ground at the transformer from which its power is supplied BA B A B A B A B A GND GND GND GND Signal ground Sh...

Страница 10: ...ds to approximately 150 VA for a 24 V AC transformer it is neces sary to use more transformers to prevent overheating Supply cable sizing The wire size of the supply cable can be determined by calcula...

Страница 11: ...the Lindab UltraLink app nearby UltraLinks will be identified Now you can connect to all the different UltraLink units to change settings and view information regarding each UltraLink You can find the...

Страница 12: ...ween the different parameters in the menu by short pressing the Mode button The arrows at the bottom of the menu indicates the air flow reading temperature and also what unit the current value has if...

Страница 13: ...anges are made The Bluetooth radio can be disabled by setting register 4 007 to 0 The code can be changed in three ways using the configuration menu in the display see page 13 for instructions connect...

Страница 14: ...ty none Id Modbus Id Id x Modbus id x value PLA PLA address for Pascal PLA x PLA address x value ELA ELA address for Pascal ELA x ELA address x value Pi Pin code Pi xxxx Default xxxx 1111 Cnt Control...

Страница 15: ...ee digits in the serial number also visible in the display if the product has power Baud rate 19200 Parity Odd Stop bits 1 After updating any of the communication parameters the product needs to be po...

Страница 16: ...501 502 are used if the device is controlled with angle 4 070 1 and registers 4 503 504 are used if the device is controlled using flow 4 070 2 If set points are controlled via bus this point can be i...

Страница 17: ...s 4x408 Angle Min 4x409 Angle Max 100 2 2 10V 0 Flow 0 50 0 55 0 100 125 0 50 0 86 0 100 160 0 50 0 141 0 100 200 0 50 0 220 0 100 250 0 50 0 344 0 100 315 0 50 0 546 0 100 400 0 50 0 880 0 100 500 0...

Страница 18: ...onnected between all the products without any mixups of A and B Bus layout is not allowed to be star connection The cables for power supply are connected identical on all products and transformers con...

Страница 19: ...0 C Maximum ambient moisture 95 RH Connection RS485 standard or analog Cable RS485 standard cable 2 wire shielded twisted pair min 0 1 mm LIYCY cable Protocol Modbus Output Flow Flow Velocity Temperat...

Страница 20: ...icates Input 4x indicates Holding UltraLink Type of UltraLink where the register is available Indicated by x Name Name of register Description Short description of register Data type Data type for reg...

Страница 21: ...RO HOLDING REGISTERS Communication settings 4x001 X X Communication id Modbus address 16bit 1 239 RW 4x002 X X RS485 Baud Rate Conf Baudrate 0 9600 1 19200 2 38400 3 76800 16bit 1 0 3 RW 4x003 X X RS...

Страница 22: ...02 X Angle Set Point Angle setpoint used in normal mode Only relevant when 4x070 is set to 1 16bit 0 0 100 RW 4x314 X Flow Set Point Flow setpoint used in normal mode Only relevant when 4x070 is set t...

Страница 23: ...alog Output 2 Open Min Min open shown Min output voltage Only relevant when 4x431 is set to 2 16bit 10 0 0 1000 RW 4x439 X Analog Output 2 Open Max Max open shown Max output voltage Only relevant when...

Страница 24: ...ffering efficient availability and logistics We are also working on ways to reduce our impact on our environment and climate We do that by de veloping methods to produce our solutions using a minimum...

Отзывы: