background image

Premum

11

|

p

y

We reserve the right to make changes

3.0 Maintenance

The interval of cleaning depends on the indoor environment where the beam is placed. 

Under optimal conditions the Premum beams only need cleaning every 5 years. 

3.1 Cleaning 

instructions 

 

Remove the faceplate

 

Clean underneath the battery with a vacuum cleaner and a piece of wet cloth 

 

Demount the inspection hatch in the opposite end of the air connection, in a turn 

and pull motion.

 

Clean the inside of the beam with a vacuum cleaner and a piece of wet cloth   

 

Only use lukewarm water and a mild detergent.

3.2  Models with down fold battery

 

Remove the faceplate

 

Unscrew the four screws on the battery, as described in the mounting instruc-

tion. Note that the two screws closest to the battery connection pipes must not 

be completely unscrewed. Refer to the mounting instruction for details on this 

matter. 

 

It is now possible to fold the battery down.

Содержание Premum

Страница 1: ...Premum Service maintenance...

Страница 2: ...ple points Do not lift in pipes Do not lift in edges Each beam is equipped with protective lm to avoid any damage during transport and handling at building site The lm needs to be removed before commi...

Страница 3: ...er protection cover which should be removed before installation After removing the protection cover make sure that the pipe is intact and undam aged especially at the pipe end Crocked or in other ways...

Страница 4: ...ion tting the pipe will be exposed to a big amount of force creating a risk of crushing the pipe To ensure that the pipe won t be crushed when mounting the compression tting a copper insert should be...

Страница 5: ...lly soft welded why it s not allowed to solder the beam to the pipes 1 5 3 Flex hoses Our exible hoses can be used with both compression and Tectite tting We recom mend using Tectite ttings for easier...

Страница 6: ...a deburring tool before installation Mount a push on tting to the pipe Make sure to press the tting all the way onto the pipe After mounting the push on tting mount the exible hose Make sure that the...

Страница 7: ...er of plugged nozzles Product ID Product number Sign To be signed when checked and commissioned on site 2 2 Measure air pressure and calculating the air ow Before calculating the air ow the static noz...

Страница 8: ...the air ow After measuring the static nozzle pressure read the setting of the four pins in the corners to nd the mean value of the pins Locate the diagram on the faceplate or see diagram 1 2 and use...

Страница 9: ...3 Changing the air ow Measure the static nozzle pressure Locate the air pressure air ow diagram on the faceplate or see diagram 1 2 Find the mean value of the four pins to reach the desired air ow in...

Страница 10: ...dalla posizione corrente del deflettore Pousser et rel cher les clips de la position d flecteur Align deflector at desired position Tilpas deflektor til nsket position S tt luftriktaren i nskad posit...

Страница 11: ...t the inspection hatch in the opposite end of the air connection in a turn and pull motion Clean the inside of the beam with a vacuum cleaner and a piece of wet cloth Only use lukewarm water and a mil...

Страница 12: ...nd Engineering Practice Pressure table Pressure class PN10 Max working pressure 10 bar Max recommended dynamic pressure 0 2 bar Max test pressure 16 bar Even though the battery of the chilled beam can...

Страница 13: ...imize noise and optimize the energy yield There should be used in line strainers to remove dirt particles from the water If the water contains any additive inhibitor this must be appropriate to use wi...

Страница 14: ...jeet sek tuotetuen yhteystiedot www lindab fi Oikeus muutoksiin pid tet n DE Hier finden Sie aktuelle Produktinformationen Mon tageanleitungen und Telefonnummer E Mail Adressen der Ansprechpartner www...

Отзывы: