40
After the measuring of the ventilation loss has been com-
pleted, "ventilation loss" will be marked by a tick mark in the
"Heating check" screen.
How to print out a report:
• Select the 'PRINT' option from the main menu.
How TO save the results:
• Select the 'Save' option from the main menu.
Measuring the surface loss
The surface loss is the temperature that the burner emits via
the surface.
NOTE!
The Special Wall Temperature Probe is needed to measure
the surface loss (see accessories).
Before measuring the surface loss, it is necessary to enter
certain data. For that purpose all partial areas of the burner
must be considered that do not adjoin directly to other instal-
lations and/or walls and floors
Determining
Denomination
A partial area = measured
value/manufacturer
information
Partial area in m²
T
S
partial area = measured
value
Temperature of the partial
area in °C
T
R
Room = measured value
air temperature in ° in the
fireplace room
a
= value determined
according to EN 304
Heat transfer coefficient in
W/m²K
Q
burner
= value indicated in
the instruction plate of the
burner
Nominal power of the heat
generator in kW