Temperature calibration of thermosensitive element for auto-

matic damper closing

72 °C±7 °C (Standard)

95 °C±9 °C (On request).

ELEC TRICAL CONNEC TIONS

 

„

Electrical wiring

Electrical connections must be done by qualified and trained people.

Switch off the power supply before starting any work on the electric 

elements. Never switch on the power supply during electrical con-

nections.

 

†

Manual and compact manual

S1-25 electric board (S2 optional) for blade position microswitches (manual)

S1-25-B electric board (S2 optional) for blade position microswitches (compact 

manual)

1  Microswitch contacts for blade position

FCU Closed blade contact

DCU Open blade contact

NO  Normally open

C Common

NF  Normally closed

 

†

Manual with magnet - MR/MI version (the magnet is powered 

using 24 V DC/48 V DC through S0-25 electric board)

S0-25 electronic board (S2 optional) for 24V DC / 48V DC power supply. Blade 

position microswitches included

1  Microswitch contacts for blade position

2  Magnet power supply contacts. 24V DC or 48V DC. Keep to the polarity for 

input magnet

MAG 

Magnet power supply

FCU Closed blade contact

DCU Open blade contact

NO  Normally open

C Common

NF  Normally closed

 

†

S2 microswitches position for manual control and magnetic 

control

1.  The fire damper's blade is open (the air flow is allowed)

2.  The fire damper's blade is closed (the air flow is not allowed)

FCU Closed blade contact

DCU Open blade contact

 

†

Motorized version

Belimo servomotor:

BFL24T, BFN24T, BF24T, BFL230T, BFN230T, BF230T.

Siemens servomotor:

GRA126, GNA126, GGA126.

Содержание EI 120 S

Страница 1: ...l data the equipment and acces sories indicated could be subject to variations Installation booklet RECTANGULAR SERIES WKS25 500 Pa Cert N 1812 CPR 1046 EN 15650 This is a 15 page installation booklet...

Страница 2: ...sity 995 kg m Plasterboard sealing ve i o D B x H min 100 x 200 max 800 x 600 B x H min 100 x 200 max 800 x 600 B x H min 100 x 200 max 800 x 600 EI 120 S Installation within vertical light wall gypsu...

Страница 3: ...l axis Fixing flaps 1 Bend for walls 100 mm thick or higher 2 Bend for walls 70 mm thick or higher Fire dampers pairing The patented WKS25 rectangular fire dampers can be paired side by side or vertic...

Страница 4: ...atically closes the blade when the temperature in the duct exceeds 70 C or 95 C for the fire damper with 95 C thermal fuse It is possible to close the damper by pressing the indicated button Blade ope...

Страница 5: ...perature sensor or cut off the power supply Blade opening mode The damper must be opened when the ventilation system if switched off To open the damper with the electric motor driven actuator provide...

Страница 6: ...Normally open C Common NF Normally closed Manual with magnet MR MI version the magnet is powered using 24 V DC 48 V DC through S0 25 electric board S0 25 electronic board S2 optional for 24V DC 48V DC...

Страница 7: ...4V AC DC WKS25VSS Siemens GRA126 Opening 3 5 W In stand by 2 W Motor 230V AC WKS25VSS Siemens GRA326 Opening 4 5 W In stand by 3 5 W Microswitches position contacts Manual control version 12VDC 2A 125...

Страница 8: ...itioning The fire damper can be installed both with the blade axis positioned vertically or horizontally Positioning brackets before fixing 1 Positioning brackets Installation of flexible connectors i...

Страница 9: ...L1 L2 200 50 50 250 50 100 300 50 100 350 50 150 400 50 150 450 50 200 500 50 200 550 50 250 600 100 250 H Nominal height of fire damper L1 End cap length mechanism side L2 End cap length mechanism o...

Страница 10: ...l floor used for the test and wall floor used for the actual installation The test results obtained on a type of wall floor are valid also for walls floor of the same type but with greater thickness a...

Страница 11: ...tach to the steel pro file underneath 1 Plasterboard thickness 12 5 mm 2 Rock wool density up to 100 kg m optional 3 Horizontal U shaped profile 4 Vertical C shaped profile 5 Self drilling screw 3 5 X...

Страница 12: ...located on the fire damper casing See section Fixing flaps for further details Position the damper in the opening so that the side of the closing mechanism extends from the wall by 185 mm Be careful n...

Страница 13: ...r both in relation to air flow and the side with the higher probability of exposure to fire as indicated in standard EN1366 2 paragraph 6 2 Filling It is not necessary to insert any material but simpl...

Страница 14: ...5 mm 2 Self drilling screw 3 5 X 45 mm EI 120 S Installation within vertical light wall gypsum blocks wall The WKS25 fire dampers classified EI 120 S within vertical light walls built with gypsum bloc...

Страница 15: ...al wall Installation within vertical light wall Shaft wall WKS25 fire dampers are tested and approved in Fire resistance classification Hole size D1 x D2 mm Damper protrusion from the wall E mm Wall m...