B.  Nominal base dimension (mm)

H.  Nominal height dimension (mm)

1.  Ceiling contact installation

2.  Corner room installation

3.  Plasterboard infill panel, thickness 12,5 mm

4.  Installation wall

5.  Ceiling or floor

6.  Side vertical wall

 

„

EI 90 S Installation within vertical light wall (gypsum blocks wall) 

The WKS25 fire dampers classified EI 90 S within vertical light walls 

built with gypsum blocks "carreaux de plâtre", guarantee fire and 

heat sealing for 90 minutes only if installed inside walls with a mini-

mum fire resistance class of EI 90, minimum thickness of 70 mm and 

minimum density of 995 kg/m³.

In accordance with standard EN 1366-2 (Article 13.7) the results of 

the tests are extended to thicker or higher density walls.

Comply with the minimum distances indicated on section Minimum 

distances 

 

†

Wall opening

A rectangular opening must be provided in the wall with a side 50 

mm greater than the nominal size of the fire damper.

It is advisable not to exceed by more than 10 mm from the indicated 

sizes so as not to compromise the correct thermal insulation.

 

†

Damper positioning

Lift the fixing flaps located on the fire damper casing. See section 

Fixing flaps  for further details.

Position the damper in the opening so that the side of the closing 

mechanism extends from the wall by 202 mm.

Be careful not to damage the intumescent gasket on the outside the 

casing.

Secure the fire damper to the wall using four screws on the four holes 

of the fixing flaps.

The double test (with the mechanism inside and outside the fire 

area) demonstrated that there is no preferred direction for the po-

sition of the damper, both in relation to air flow and the side with 

the higher probability of exposure to fire, as indicated in standard 

EN1366-2 (paragraph 6.2).

 

†

Filling

It is not necessary to insert any material, but simply cover the gap 

between the damper and the wall by applying on face of the wall 

mechanism side a layer of plasterboard, to a total minimum thickness 

of 12,5 mm, to make a frame 100 mm wide.

B.  Nominal base dimension (mm)

H.  Nominal height dimension (mm)

1.  Plasterboard infill panel, thickness 12,5 mm

2.  Self-drilling screw Ø 3,5 X 45 mm

 

„

EI 120 S Installation within vertical light wall (gypsum blocks wall)

The WKS25 fire dampers classified EI 120 S within vertical light walls 

built with gypsum blocks “carreaux de plâtre”, guarantee fire and heat 

sealing for 120 minutes only if installed inside walls with a minimum 

fire resistance class of EI 120, minimum thickness of 100 mm and 

minimum density of 995 kg/m³.

In accordance with standard EN 1366-2 (Article 13.7) the results of 

the tests are extended to thicker or higher density walls.

Comply with the minimum distances indicated on section Minimum 

distances 

 

†

Single fire damper wall opening

A rectangular opening must be provided in the wall with a side 50 

mm greater than the nominal size of the fire damper.

It is advisable not to exceed by more than 10 mm from the indicated 

sizes so as not to compromise the correct thermal insulation.

 

†

Paired fire dampers wall opening

A rectangular opening must be provided in the wall with a side 50 

mm greater than the nominal size of the paired fire dampers:

– Vertically paired fire dampers

base = damper base + 50 mm

height = h h 45 mm + 50 mm

– Side by side paired fire dampers

base = base1 + base2 + 45 mm + 50 mm

height = damper 50 mm.

It is advisable not to exceed by more than 10 mm from the indicated 

sizes so as not to compromise the correct thermal insulation.

 

†

Damper positioning

Lift the fixing flaps located on the fire damper casing. See section 

Fixing flaps  for further details.

Position the damper in the opening so that the side of the closing 

mechanism extends from the wall by 185 mm.

Be careful not to damage the intumescent gasket on the outside the 

casing.

Secure the fire damper to the wall using four screws on the four holes 

of the fixing flaps.

The double test (with the mechanism inside and outside the fire 

area) demonstrated that there is no preferred direction for the po-

sition of the damper, both in relation to air flow and the side with 

the higher probability of exposure to fire, as indicated in standard 

EN1366-2 (paragraph 6.2).

 

†

Filling

It is not necessary to insert any material, but simply cover the gap 

between the damper and the wall by applying on face of the wall 

mechanism side a layer of plasterboard, to a total minimum thickness 

of 12,5 mm, to make a frame 100 mm wide.

Содержание EI 120 S

Страница 1: ...l data the equipment and acces sories indicated could be subject to variations Installation booklet RECTANGULAR SERIES WKS25 500 Pa Cert N 1812 CPR 1046 EN 15650 This is a 15 page installation booklet...

Страница 2: ...sity 995 kg m Plasterboard sealing ve i o D B x H min 100 x 200 max 800 x 600 B x H min 100 x 200 max 800 x 600 B x H min 100 x 200 max 800 x 600 EI 120 S Installation within vertical light wall gypsu...

Страница 3: ...l axis Fixing flaps 1 Bend for walls 100 mm thick or higher 2 Bend for walls 70 mm thick or higher Fire dampers pairing The patented WKS25 rectangular fire dampers can be paired side by side or vertic...

Страница 4: ...atically closes the blade when the temperature in the duct exceeds 70 C or 95 C for the fire damper with 95 C thermal fuse It is possible to close the damper by pressing the indicated button Blade ope...

Страница 5: ...perature sensor or cut off the power supply Blade opening mode The damper must be opened when the ventilation system if switched off To open the damper with the electric motor driven actuator provide...

Страница 6: ...Normally open C Common NF Normally closed Manual with magnet MR MI version the magnet is powered using 24 V DC 48 V DC through S0 25 electric board S0 25 electronic board S2 optional for 24V DC 48V DC...

Страница 7: ...4V AC DC WKS25VSS Siemens GRA126 Opening 3 5 W In stand by 2 W Motor 230V AC WKS25VSS Siemens GRA326 Opening 4 5 W In stand by 3 5 W Microswitches position contacts Manual control version 12VDC 2A 125...

Страница 8: ...itioning The fire damper can be installed both with the blade axis positioned vertically or horizontally Positioning brackets before fixing 1 Positioning brackets Installation of flexible connectors i...

Страница 9: ...L1 L2 200 50 50 250 50 100 300 50 100 350 50 150 400 50 150 450 50 200 500 50 200 550 50 250 600 100 250 H Nominal height of fire damper L1 End cap length mechanism side L2 End cap length mechanism o...

Страница 10: ...l floor used for the test and wall floor used for the actual installation The test results obtained on a type of wall floor are valid also for walls floor of the same type but with greater thickness a...

Страница 11: ...tach to the steel pro file underneath 1 Plasterboard thickness 12 5 mm 2 Rock wool density up to 100 kg m optional 3 Horizontal U shaped profile 4 Vertical C shaped profile 5 Self drilling screw 3 5 X...

Страница 12: ...located on the fire damper casing See section Fixing flaps for further details Position the damper in the opening so that the side of the closing mechanism extends from the wall by 185 mm Be careful n...

Страница 13: ...r both in relation to air flow and the side with the higher probability of exposure to fire as indicated in standard EN1366 2 paragraph 6 2 Filling It is not necessary to insert any material but simpl...

Страница 14: ...5 mm 2 Self drilling screw 3 5 X 45 mm EI 120 S Installation within vertical light wall gypsum blocks wall The WKS25 fire dampers classified EI 120 S within vertical light walls built with gypsum bloc...

Страница 15: ...al wall Installation within vertical light wall Shaft wall WKS25 fire dampers are tested and approved in Fire resistance classification Hole size D1 x D2 mm Damper protrusion from the wall E mm Wall m...

Отзывы: