Service & maintenance Celo
Lindab reserves the right to make changes without prior notice
2021-04-15
Lindab reserves the right to make changes without prior notice
2021-04-15
4.0 Product and system specification
4.1 Material data
Celo
Weight, kg/m
6.5
Water content, cooling, l/m
0.25
Copper pipes, quality
SS/EN 12449
Pressure class
PN10
4.2 Environmental declaration
Please follow the links below
• Building product declaration
•
4.3 Pressure class
The waterborne products in Lindab, active chilled beams (battery products), passive
chilled beams (battery and strips products), facade units (battery) and radiant panels
(strips and panels) are produced according to pressure class PN10 according to EN
1333: 2006.
This means the maximal working pressure for the products at a water temperature of
20°C must not exceed 10 bar.
4.4 Water quality
Lindab recommend water treatment and quality to be according to VDI 2035-2.
– The water preparation and maintenance for the chilled beam water circuit should
be handled by a specialist
– To prevent corrosion, the water circuit must be airtight
– The water system must also be equipped with aerators to remove any build-up air
in the system.
– The water should be oxygen free, to prevent corrosion.
– The water system must be filled with potable water that complies with the “EC
directive 98/83/EC”.