A-6

INSTALLATION   

EAGLE™ 10,000 PLUS

A-6

120/240 VOLT DUAL VOLTAGE RECEPTACLE

The  120/240  volt  receptacle  can  supply  up  to  38
amps of 240 volt power to a two wire circuit, up to 38
amps  of  120  volts  power  from  each  side  of  a  three
wire circuit (up to 76 amps total).  Do not connect the
120  volt  circuits  in  parallel.  Current  sensing  for  the
automatic  idle  feature  is  only  in  one  leg  of  the  three
wire circuit as shown in the following column.

120 V DUPLEX RECEPTACLES

The 120V auxiliary power receptacles should only be
used with three wire grounded type plugs or approved
double insulated tools with two wire plugs.

The  current  rating  of  any  plug  used  with  the  system
must be at least equal to the current load through the
associated receptacle. 

MOTOR STARTING

Most 1.5 hp AC single phase motors can be started if
there is no load on the motor or other load connected
to  the  machine,  since  the  full  load  current  rating  of  a
1.5  hp  motor  is  approximately  20  amperes  (10
amperes  for  240  volt  motors).  The  motor  may  be  run
at  full  load  when  plugged  into  only  one  side  of  the
duplex receptacle. Larger motors through 2 hp can be
run provided the receptacle rating as previously stated
is not exceeded. This may necessitate 240V operation
only.

GND

120 V

120 V*

240 V

*Current Sensing for Automatic Idle.
(Receptacle viewed from front of Machine)

GND

120 V

120 V*

240 V

*Current Sensing for Automatic Idle.
(Receptacle viewed from front of Machine)

EAGLE™ 10,000 Plus Extension Cord Length Recommendations

(Use the shortest length extension cord possible sized per the following table.)

WELDER OPERATION

WELDER OUTPUT

•  Maximum Open Circuit Voltage at 3700 RPM is 80

Volts RMS.

•  Duty  Cycle  is  the  percentage  of  time  the  load  is

being applied in a 10 minute period. For example, a
60% duty cycle represents 6 minutes of load and 4
minutes  of  no  load  in  a  10  minute  period.  Duty
Cycle for the EAGLE™ 10,000 Plus is 100%.

AUXILIARY POWER

The  EAGLE™  10,000  Plus  can  provide  up  to  9,000
watts  of  120/240  volts  AC,  single  phase  60Hz  power
for continuous use, and up to 10,500 watts of 120/240
volts  AC,  single  phase  60Hz  power  surge  use.  The
front  of  the  machine  includes  three  receptacles  for
connecting the AC power plugs; one 50 amp 120/240
volt  NEMA  14-50R  receptacle  and  two  20  amp  120
volt NEMA 5-20R receptacles. Output voltage is within
+/-10% at all loads up to rated capacity.

All  auxiliary  power  is  protected  by  circuit  breakers.
The  120V  has  20  Amp  circuit  breakers  for  each
duplex receptacle. The 120/240V Single Phase has a
40  Amp  2-pole  Circuit  Breaker  that  disconnects  both
hot leads simultaneously.

Do  not  connect  any  plugs  that  connect  to  the
power receptacles in parallel.

------------------------------------------------------------------------
Start the engine and set the “IDLER” control switch to
the  desired  operating  mode.  Set  the  “CONTROL”  to
10. Voltage is now correct at the receptacles for auxil-
iary power.

CAUTION

Current

(Amps)

15
20
15
20
38

Voltage

Volts

120
120
240
240
240

Load

(Watts)

1800
2400
3600
4800
9000

14 AWG

30      (9)

60     (18)

12 AWG
40   (19)

30    (9)

75   (23)
60   (18)

10 AWG

75    (23)
50    (15)

150   (46)
100   (30)

50    (15)

8 AWG

125   (38)
88     (27)
225   (69)
175   (53)

90    (27)

6 AWG

175   (53)
138   (42)
350  (107)
275   (84)

150    (46)

4 AWG

300    (91)
225    (69)
600  (183)
450  (137)

225   (69)

Conductor size is based on maximum 2.0% voltage drop.

Maximum Allowable Cord Length in ft. (m) for Conductor Size

EAGLE™ 10,000 Plus

Constant Current

210 Amps DC @ 25 Volts

Содержание 000 PLUS IM10028-B

Страница 1: ...installation and thoughtful operation on your part DO NOT INSTALL OPERATE OR REPAIR THIS EQUIPMENT WITHOUT READ ING THIS MANUAL AND THE SAFETY PRECAUTIONS CON TAINED THROUGHOUT And most importantly th...

Страница 2: ...KER WEARERS SHOULD CONSULT WITH THEIR DOCTOR BEFORE OPERATING Read and understand the following safety highlights For additional safety information it is strongly recommended that you purchase a copy...

Страница 3: ...Never simultaneously touch electrically hot parts of electrode holders connected to two welders because voltage between the two can be the total of the open circuit voltage of both welders 3 i When w...

Страница 4: ...eas Avoid welding near hydraulic lines Have a fire extinguisher readily available 6 b Where compressed gases are to be used at the job site special precautions should be used to prevent hazardous situ...

Страница 5: ...opri s et non inflammables 4 Des gouttes de laitier en fusion sont mises de l arc de soudage Se prot ger avec des v tements de protection libres de l huile tels que les gants en cuir chemise paisse pa...

Страница 6: ...mportant when identifying the correct replacement parts On Line Product Registration Register your machine with Lincoln Electric either via fax or over the Internet For faxing Complete the form on the...

Страница 7: ...uel Consumption B 2 Start in Shutdown Instructions B 3 Starting the Engine B 3 Safety Precautions B 3 Stopping the Engine B 3 Break In Period B 3 Welding Process B 4 Stick Constant Current Welding B 4...

Страница 8: ...g in watts is equivalent to volt amperes at unity factor Output voltage is within 10 at all loads up to rated capacity When welding available auxiliary power will be reduced RECEPTACLES 2 120VAC Duple...

Страница 9: ...f the welder SPARK ARRESTER Some federal state or local laws may require that gasoline engines be equipped with exhaust spark arresters when they are operated in certain locations where unarrested spa...

Страница 10: ...ing operated or serviced 4 Typical conditions of use i e travel speed rough ness of surface on which the trailer will be operated environmental conditions 5 Conformance with federal state and local la...

Страница 11: ...ed when lifting the machine ADDITIONAL SAFETY PRECAUTION HIGH ALTITUDE OPERATION At higher altitudes Welder output de rating may be necessary For maximum rating de rate the welder output 3 5 for every...

Страница 12: ...y and shielding gas control for DC GTAW TIG welding See IM528 supplied with the TIG Module for installation instructions NOTE The TIG Module does not require the use of a high frequency bypass capacit...

Страница 13: ...following table WELDER OPERATION WELDER OUTPUT Maximum Open Circuit Voltage at 3700 RPM is 80 Volts RMS Duty Cycle is the percentage of time the load is being applied in a 10 minute period For example...

Страница 14: ...ITHOUT ADDI TIONAL RESISTIVE TYPE LOADS Inductive Single phase induction motors These devices require large Drills well pumps grinders small Current inrush for starting Refrigerators weed and hedge So...

Страница 15: ...ole circuit break er Maximum rated load for the 240V auxiliary is 38 amperes Loading above 38 amperes will reduce output voltage below the allowable 10 of rated voltage which may damage appliances or...

Страница 16: ...ction of EAGLE 10 000 Plus to premises wiring must be done by a licensed electrician and must comply with the National Electrical Code and all other applicable electrical codes Figure 1 CONNECTION OF...

Страница 17: ...high speed If no power is being drawn from the receptacles and not welding for 10 14 seconds the idler reduces the engine speed to low idle B 1 OPERATION EAGLE 10 000 PLUS B 1 SAFETY PRECAUTIONS Do no...

Страница 18: ...ge switch set in the wire feed mode Process Range Setting Current Range B 2 OPERATION B 2 EAGLE 10 000 PLUS CAUTION KOHLER 23 H P COMMAND CH23S 40 Gallons Hour 1 50 Liters Hour 7 Gallons Hour 2 8 Lite...

Страница 19: ...engine to run at low idle speed for a few minutes to cool the engine Stop the engine by placing the Engine switch in the OFF position A fuel shut off valve is not required on the EAGLE 10 000 Plus be...

Страница 20: ...are refer enced The EAGLE 10 000 Plus and any high frequency generating equipment must be properly grounded See the K930 2 TIG Module operating manuals for complete instructions on installa tion opera...

Страница 21: ...table SUMMARY OF WELDING PROCESSES CONTROL ELECTRODE CABLE IDLE WHEN NOT TO START PROCESS USED MODE WELDING WELDING ELECTRODE SETTING CURRENT RANGE DC electrode positive 1 8 30 60 Amps 5 32 90 150 Am...

Страница 22: ...he EAGLE 10 000 Plus when not in use Made from attractive red canvas material which is flame retardant mildew resistant and water repellent K802R Power Plug Kit provides four 120V plugs rated at 15 am...

Страница 23: ...plete with a handle High frequency bypass is built in Requires K938 1 Contactor Kit K936 4 Control Cable and K814 Arc Start Switch K938 1 Contactor Kit For use with TIG Module Provides a cold electrod...

Страница 24: ...emperature and other severe operating conditions Refer to the maintenance section of the Engine Owner s Manual for more information NOTE Engine life will be reduced if the oil and oil filter are not c...

Страница 25: ...cket tool to tighten the filter an additional 1 2 to 7 8 turn 5 Refill the crankcase with the specified amount of the recommended oil Reinstall the oil filler cap 6 Start the engine and check for oil...

Страница 26: ...d then the positive battery cable before attaching the charger leads Failure to do so can result in damage to the internal charger components When reconnecting the cables connect the positive cable fi...

Страница 27: ...IBLE CAUSE lists the obvious external possibilities that may contribute to the machine symptom Step 3 RECOMMENDED COURSE OF ACTION This column provides a course of action for the Possible Cause genera...

Страница 28: ...n miscellaneous leads 2 Open lead in flashing or field circuit 3 Faulty rotor 4 Faulty Potentiometer R1 5 Faulty stator Field winding 6 Faulty Field rectifier On PCB 7 Faulty P C Board 1 Idler switch...

Страница 29: ...ngine does not develop full power Engine is hard to start 1 No voltage signal from the current sensor 2 Auxiliary power load less than 100 to 150 watts 3 Faulty P C Board 1 Battery will not hold a cha...

Страница 30: ...It may not be accurate for all machines covered by this manual The specific diagram for a particular code is pasted inside the machine on one of the enclosure panels If the diagram is illegible write...

Страница 31: ...I L I N E N G I N E A N D E M P T Y F U E L T A N K 2 1 4 4 2 0 8 0 4 2 1 0 3 3 6 2 3 6 2 4 1 0 2 7 1 0 7 8 N O T E C A S E F R O N T G R A P H I C S M A Y N O T M A T C H A L L C O D E S M22195 A 01...

Страница 32: ...NOTES EAGLE 10 000 PLUS...

Страница 33: ...NOTES EAGLE 10 000 PLUS...

Страница 34: ...uch electrically live parts or electrode with skin or wet cloth ing l Insulate yourself from work and ground l No toque las partes o los electro dos bajo carga con la piel o ropa mojada l Aislese del...

Страница 35: ...Schweibrauch l Sorgen Sie f r gute Be und Entl ftung des Arbeitsplatzes l Mantenha seu rosto da fuma a l Use ventila o e exhaust o para l Turn power off before servicing l Desconectar el cable de ali...

Страница 36: ...and Service through Subsidiaries and Distributors Worldwide Cleveland Ohio 44117 1199 U S A TEL 216 481 8100 FAX 216 486 1751 WEB SITE www lincolnelectric com World s Leader in Welding and Cutting Pr...

Отзывы: