INSTALLATION
SITING
The installer must ensure that all regulations are met and that there is an unobstructed minimum
distance of 1000mm from the top of the flue to the ceiling, which must be of non-combustible
material.
The appliance should be installed on a level surface ensuring the unit is stable and firmly located.
Any partitions, walls or kitchen furniture in close proximity must be of non-combustible materials
and not be closer than 50mm from the sides and rear of the flue.
GAS SUPPLY AND CONNECTION
Connection is at the rear of the unit via a 1/2" G male thread.
Gas supply hose and connection shall comply with local regulations, and shall be periodically
examined and replaced as necessary.
When making the connection to the appliance an isolating cock should be fitted into the supply line
close to the unit, for emergency shutdown or servicing purposes.
SUPPLY PRESSURES
To gain access to the gas pressure test nipple remove the debris drawer. The nipple is situated
behind the fascia panel on the right of the appliance.
Remove the blanking screw and attach a pressure gauge to the boss of the test nipple.
Light both burners and set to maximum.
Adjust the operating pressure at the governor. See table.