www.limotec.be
HG0300E02D
20
5
SIGNALLING
WARNING
–
EVACUATION
WARNING
Warning means “the information given to certain persons of the beginning of a fire or a danger”.
EVACUATION
Evacuation is understood to mean “the notification to all persons staying in a certain place to
evacuate this place”.
The switchover from warning to evacuation on the MD300 control panel is made:
-
Either after the set evacuation-reaction time has elapsed (see below) if the alarm message on
the MD300 control panel has not been accepted (accept = operate the “SILENCE” button).
-
Either after the set evacuation-intervention time has elapsed (see below) if the alarm message
has not yet been reset on the MD300 control panel. The alarm message is reset as follows:
Eliminate the cause of the alarm message and reset the MD300 control panel by
pressing the “RESET” button with the system in operating level 2.
Switch off the detector loop that signals the fire alarm (see below) and reset the
control panel by pressing the “RESET” button with the system in operating level 2.
-
Either after pressing the “EVACUATION” button on the MD300 control panel and/or after
operating any evacuation call point installed in the building.
If required, the evacuation can be activated immediately after the alarm message has been triggered.
In this case, there is no warning phase and the evacuation actions are carried out immediately.