Control Function 

Temperature Control 

When T-water 

≤ SP – U01, start heating. 

When T-water 

≥ SP, stop heating. 

Heating start procedure:   

Pump is on; 30 seconds later, outdoor fan is on, valve takes action; 30 seconds later, compressor is on. 

Heating stop procedure: 

Compress is off; 30 seconds later, outdoor fan is off, valve takes action; 30 seconds later, pump is off. 

Note: the four-way valve works according to U34. 

Aux Electrical Heater Control 

When T-water 

≤ SP – U01 

If T-outdoor 

≤ 10

, electrical heater is on. 

If T-outdoor 

≥ 12

, electrical heater is off. 

When T-water 

≥ SP, electrical heater is off 

Note: Heater will be on during defrosting. 

Water Ventilation Pump Control 

The pump will be on 60 seconds before the compressor is on, be off 60 seconds after the compressor is off. 
The pump will always be on during defrosting. 
If there is no water flowing for 10 seconds, stop compressor and heater, and keep warning. 
When the water flowing restores, restore the system control 

Avoid Freezing in Winter (in Offline Standby State) 

When T-outdoor 

≤ 2

, start anti-freezing pumping, the pump run 3 minutes for every 30 minutes. 

When T-outdoor 

≥ 3

, stop this anti-freezing protection pumping. 

Auto Defrost 

Start auto defrosting: When compressor has been running for U30, and if T-pipe 

≤ U31, start defrosting. 

Compressor and outdoor fan stop; 55 seconds later, valve acts; 5 seconds later, start compressor. 

Stop defrosting: When T-pip 

≥ U32, or the compressor has been running for U33, stop defrosting. 

Stop compressor; 55 seconds later, valve acts; 5 seconds later, start heating control. 

Defrost after turning the system online: When turn online, if the T-pipe 

≤ U31, defrost 1

st

Timer Defrost 

If pipe sensor fails

and the compressor has been running for U30, and 

If outdoor sensor is ok, and T-outdoor 

≤ U31, start defrosting. 

If outdoor sensor fails, start defrosting. 

Exhaustion Over Temperature Protection 

During compressor is on, if T-exhaustion 

≥ U50, stop compressor. 

When T-exhaustion 

≤ U50-10

, stop protection, and start heating control again.     

High/Low Pressure Warning and Protection 

When compressor running, if the high/low pressure is effective for 15 seconds, start pressure protection:   

Stop compressor, until the high/low pressure is not effective. 

If the pressure protection occurs 3 times within an hour, or once high/low pressure effectiveness keeps for 
one hour, the controller will be in machine protection mode:   

Never start heating again, until stop power supply and supply power again. 

When compressor has just started, the high/low pressure is not check for 3 minutes. 
Note: the high/low pressure mode is set in U51. 

Compressor Delay Protection 

After power supplied, the compressor can start after 3 minutes. 
After compressor stops, it can re-start 3 minutes later. 

Water Sensor Failure Warning 

When this sensor fails, system stops heating. 

 
 

Содержание ZL-R200A

Страница 1: ...mpressor 15A Heating 8A Others 3A Failure Code No Code Failure No Code Failure 1 E01 Water container sensor failure 5 E05 Water flow warning 2 E02 Pipe Coil sensor failure 6 E06 High low pressure input warning 3 E03 Exhaustion sensor failure 7 E07 Data saving failure 4 E04 Outdoor sensor failure 8 E08 Communication failure Display Indication Icon Display Not shown Icon Displaying Not shown Online ...

Страница 2: ...High low pressure warning mode 0 2 0 Disable 1 Closed when warning 2 Open when warning 0 9 U52 Water flowing switch mode 0 2 0 Disable 1 Effective when closed 2 Effective when open 0 10 U80 Auto restart function 0 1 0 Disable 1 Enable 0 11 U81 Keypad lock 0 1 0 Unlocked 1 Locked 0 12 U90 passwords 00 99 11 Working Mode Press to switch between AUTO and SAVE working mode AUTO mode always heating acc...

Страница 3: ...pressor and outdoor fan stop 55 seconds later valve acts 5 seconds later start compressor Stop defrosting When T pip U32 or the compressor has been running for U33 stop defrosting Stop compressor 55 seconds later valve acts 5 seconds later start heating control Defrost after turning the system online When turn online if the T pipe U31 defrost 1st Timer Defrost If pipe sensor fails and the compress...

Страница 4: ...tly otherwise system does not work correctly The real clock can only keep running correctly for 72 hours after power supply loses All sensors must be installed at correct position Do not plug in out panel bundle with power supplied Panel should be installed indoors instead of outdoors ...

Отзывы: