Code
Remark
Real time detection
Delay
Duration Reset
Action
E01 Temperature sensor failure
Yes
0 sec
6 sec
Auto
Alarming,
temperature output de-energized,
the other control not affected
E02 Humidity sensor failure
Yes
0 sec
6 sec
Auto
Alarming,
humidity output de-energized,
the other control not affected
tHi High temperature
Yes
0 sec
5 sec
Auto Alarming
tLo Low temperature
Yes
0 sec
5 sec
Auto Alarming
HHi High humidity
Yes
0 sec
5 sec
Auto Alarming
HLo Low humidity
Yes
0 sec
5 sec
Auto Alarming
dr
Door open
Yes
0 sec
1 sec
Auto
Related alarming,
temperature output de-energized,
ventilation de-energized,
humidity control output de-energized,
lamp on for U34 (when U30 = 0)
iCE Touched IC fault
Yes
0 sec
5 sec
Auto
Auto Restart Function
After power supply stops, and comes back, the controller will run under the same settings and status.
Incubation Day Counter
When controlling, the
incubation day counter
will keep counting.
If the counter value reaches U18, controller keeps controlling as normal, and the counter value will be flashing.
If the counter value reaches 99, stop counting. Keeping
depressed for 3 seconds will reset the
accumulated times
of egg turning
and
incubation day counter.
Restore to Factory Default Settings
When the controller is online, keep
and
depressed simultaneously for 3 seconds. The display shows
“UnL”.
Then press
twice, the controller will restore the parameters to factory default settings.
Fahrenheit/Celsius display
Keep
and
depressed simultaneously for 3 seconds to switch between Fahrenheit / Celsius display.
Manually Checking the Outputs One by One
Keep
depressed for 3 seconds, LCD displays
“CCC”. Then press
twice to enter into manual checking mode.
Now all outputs are de-energized. Press
and
to energize R1/R2/R3/R4/R5/R6/R7/SSR in turn.
Attention
1. Please read this instruction carefully. Electrical wiring must be manipulated by certified electrician. Wrong wiring may
damage the device and system seriously.
2. Avoid humid environment, or with corrosive gases, or strong electric-magnetic field. The device is possible abnormal in
such condition.
3. This product has been strictly tested before shipping. The company warranty is one year, the responsibility is limited to
the sale of the product itself. Damage caused by improper usage is not covered by the warranty.
Wiring Diagram