Control 

 

Cooling Control (U90 = C0)

 

 

Temperature control 

If 

Troom

 ≥ Set-point + U22, and Temp. Output has been de-energized for U10, then Temp. Output energized; 

If 

Troom

 ≤ Set-point, then Temp. Output de-energized. 

 

 

Heating Control (U90 = HE)

 

 

Temperature control 

If 

Troom

 ≤ Set-point - U22, then Temp. Output energized; 

If 

Troom 

≥ Set-point, then Temp. Output de-energized. 

 

 

Temp. Output Load Delay Protection (only for cooling control)

 

After power supplied, Temp. Output could be energized after U10; 

After Temp. Output de-energized, it could be energized again after U10. 

 

 

Buzzer Function 

Every key press, there will be a short beep. Every confirmation key press, there will be a long beep. Every error operation, there will 

be three short beeps. 

When there is failure, or external warning input: If U62 = 0, no buzzing warning. If U62 = 1, there will be continuous buzzing of 

warning.   

The waring will stop, if press

P

, or warning condition disappears. 

 

 

Over Temperature Warning 

When 

Troom

 ≥ SP + U54, or 

Troom

 ≤ SP – U55, display warning, and buzzing 

 

 

External Warning Input 

NO: normal open. If open, no warning; if closed, warning. 

NC: normal close. If closed, no warning; if open, warning. 

Locked: Warning keeps after the external warning disappeared. Press

P

  to stop warning. 

Unlocked: Warning stops after the external warning disappeared. 

Note

: When there is external warning, the output(s) will be de-energized. 

 

 

Sensor Fail 

R1 stop energized. 

 

 

Sensor Calibration 

The sensor can be calibrated by U20. 

 

 

Restore to Factory Default Settings 

Keep

P

and

depressed simultaneously for 5 sec, there will be a beep, and “UnL” displays. 

Press

twice, there will be a beep, all settings will be restored to factory default settings. 

 

Installation 

1st: Insert into drilling hole                                  2nd: Clamp 

 

 

 

 

 

 

 

 

 

 
 
 

Содержание ZL-6231A

Страница 1: ...lure Has failure Warning No warning Has warning R2 output R2 energized R2 de energized Egg turn times reached After reached stop egg turn Display Remark E01 Sensor failure short or open Hi Room temp is higher than the high limit Lo Room temp is lower than the low limit EE Memory error Err Password error i iA A E Ex xt te er rn na al l w wa ar rn ni in ng g U Un nL L Parameters Will restore to fact...

Страница 2: ...it_protection 2 U45 Timer repeat times 0 9999 If 0 Timer never stops Else R2 never on when U46 reaches U45 0 U46 Timer counter the value saved to permanent memory once every hour keeps even without power supply 0 9999 One period timer period 1 timer period 2 Clear to 0 before every hatching 0 U52 Over temp warning delay 0 180 min 0 U53 1st over temp warning delay after power supplied 0 180 hour 0 ...

Страница 3: ...ailure or external warning input If U62 0 no buzzing warning If U62 1 there will be continuous buzzing of warning The waring will stop if press P or warning condition disappears Over Temperature Warning When Troom SP U54 or Troom SP U55 display warning and buzzing External Warning Input NO normal open If open no warning if closed warning NC normal close If closed no warning if open warning Locked ...

Страница 4: ...dule as load or tungsten lamp or motor following the below requirements to avoid surging current damaging or shorten the life time of the controller outputs For ac dc module as load the rated current should be no more 1 10th of output specification under pure resistance For tungsten lamp as load the rated current should be no more 1 15th of output specification under pure resistance For motor the ...

Отзывы: