the compressor stops. 

For example:   

If set temperature is 18

℃,

U22

is 2

. When the temperature 

 20

, compressor starts. If 

the temperature

 16

℃,

compressor stops. The room temperature will be between 18±2

.

 

● Compressor emergent on 

Press and hold “▼” key for 5 seconds, the compressor will power on if the following meets: 

◆ 

The compressor has stopped for "U10";   

◆ 

The controller is not in defrosting or dripping water states; 

◆ 

Room 

temperature 

is 

between 

"Set 

temperature"+”U22” 

and 

“Set 

temperature”-”U22”. 

After  compressor  emergent  on,  when  room  temperature  goes  down  to  “Set 

temperature”-”U22”, it stops cooling. 

7.2 Compressor Delay Protection   

● After power supply, the compressor is able to start only after the time (U10) has passed. 

● After the compressor stops, it is able to restart again only after the time (U10) has passed. 

● After the compressor starts, it is able to stop only after the time (U11) has passed. 

7.3 Fan Control (Only for ZL-630A-R) 

7.3.1 Fan control mode: Controlled mode and free mode. 

7.3.2 Controlled mode

 

 In the state of cooling, when the evaporator temperature is less than (U40), or the cooling 

time is more than (U41), the fan will starts. 

 If set 0 for (U41), the fan will start immediately when come into the cooling state. 

 After cooling stops, the fan will stop after the time of (U41). 

 If set 0 for (U41), the fan will stop immediately when cooling stops. 

7.3.3 Free mode 

The fan will be always running, except during defrosting. In this mode, (U40), (U41) and 

(U42) parameters have no effect. 

7.4 Protection Running Mode When Room Temperature Sensor Fails

 

When the room temperature sensor fails, the system will automatically run into the protected 

running mode. In this mode, the compressor will run and stop with the period of 30 minutes. 

Compressor works for U12* 3 minutes, stops for 

30 - (U12* 3) 

minutes. 

For example: Set 

U12

  is 3

when the temperature sensor fails

compressor runs for 9 

minutes and then stops 21 minutes, move in circles. If U12=0, system stops when sensor fails 

7.5 Protection Running Mode When Defrost Temperature Sensor Fails 
(for ZL-620A-R, ZL-630A-R) 

●  When  the  defrost  sensor  fails,  the  controller  will  periodically  defrost  according  to  (U30) 

and (U31). The dripping water function will be cancelled. 

●  If  the  fan  is  in  the  "controlled  mode",  it  will  cancel  the  conditions  of  fan  temperature 

control; the fan will work according to (U41) and (U42) parameter. (For ZL-630A-R) 

7.6 Defrosting Function 

7.6.1 Automatic defrosting 

● 

When the compressor continuously running time reaches the time of defrost cycle (U30), 

the system starts to defrost. 

● 

When  one  of  the  conditions  (defrosting  end  time  (U31)  and  defrosting  end  temperature 

Содержание ZL-6 A-R Series

Страница 1: ...st control Based on both timer and temperatures Fan control Max high temperature or min low temperature exceed warning Sensor failure warning External warning input RS 485 3 Model List Model ZL 610A R ZL 620A R ZL 630A R Cool External Alarm Input High Efficient Intelligent Defrost RS 485 Cool External Alarm Input High Efficient Intelligent Defrost Fan Control RS 485 Function Cool External Alarm In...

Страница 2: ...ng during defrosting Temperature Setting Setting temperature Repairing Faulty No fault Warning Warning No warning Panel Digit Indication Four red digits display the measured temperature and warning code No Display Code Warning Information 1 E01 Room temperature sensor fault short circuit or open circuit 2 E02 Defrosting temperature sensor fault short circuit or open circuit 3 Hi Temperature exceed...

Страница 3: ...ameter code U10 Press or to select the parameter code Press S to show its value Press or to set the value Press S to return parameter code display status Exit the Mode Keep depressing P for 3 seconds the set parameters will be saved the mode exits If do not press any key for 30 seconds the mode will exit without saving all the set data 6 3 Parameter Code and Description Table ZL 610A R No Paramete...

Страница 4: ...assword 0000 9999 1111 22 End Finished setting ZL 620A R No Parameter code Function Range Note Factory setting 1 U10 Compressor power on delay time 1 100min 3 2 U11 Compressor MIN continuous work time 0 100min 3 3 U12 Compressor run frequency 0 8 0 Disable 5 4 U20 Room temperature sensor calibration 9 9 9 9 0 5 U21 Defrosting sensor calibration 9 9 9 9 0 6 U22 Temperature difference 0 1 10 0 The h...

Страница 5: ...n 0 20 U62 Buzzer warning 0 1 0 Warning off 1 Warning on 21 U97 Baud rate setting 0 3 0 2400bps 1 4800bps 2 9600bps 3 19200bps 3 22 U98 Device address 1 99 1 23 U99 Password 0000 9999 1111 24 End Finished setting ZL 630A R No Parameter code Function Range Note Factory setting 1 U10 Compressor power on delay time 1 100min 3 2 U11 Compressor MIN continuous work time 0 100min 3 3 U12 Compressor run f...

Страница 6: ... 60 0 Disable 0 20 U52 Over temperature warning delay time 1 180min 30 21 U53 First over temperature warning delay time after power supply 0 180 hour 0 Disable 2 22 U60 External input warning mode 0 4 0 Warning off 1 On Lock 2 On Unlock 3 Off Lock 4 Off Unlock 0 23 U61 External warning input delay 0 120min 0 24 U62 Buzzer warning 0 1 0 Warning off 1 Warning on 25 U97 Baud rate setting 0 3 0 2400bp...

Страница 7: ...state After cooling stops the fan will stop after the time of U41 If set 0 for U41 the fan will stop immediately when cooling stops 7 3 3 Free mode The fan will be always running except during defrosting In this mode U40 U41 and U42 parameters have no effect 7 4 Protection Running Mode When Room Temperature Sensor Fails When the room temperature sensor fails the system will automatically run into ...

Страница 8: ...n will be off if U62 0 or the buzzer continuous alarming if U62 1 After the system problem solved and disappears press P key to stop warning 7 8 High temperature and Low temperature Warning When the room temperature set temperature U50 and the time reaches to U52 or U53 or U34 high temperature warning starts When the test temperature set temperature U51 and the time reaches to U52 or U53 or U34 lo...

Страница 9: ...sly Try with effort to layout the sensors and switches line apart from inductive load lines and power supply lines The sensors and switches lines are not allowed go with the power supply lines and inductive load lines in a same pipeline and are not allowed to pass near the contactor breaker and the similar Reduce the length of sensors wiring as possible avoid forming a spiral shape near the power ...