13
U51
Low-temperature warning deviation
value to Min Temp
0~60
℃
0: Disable
0
14
U52
Over-temperature warning delay
time
1
~
180min
30
15
U53
First
over-temperature
warning
delay time after power supply
0~180 hour
0: Disable
2
16
U60
External input warning mode
0~4
0:Warning off
1:
On, Lock
2:On, Unlock
3:Off, Lock
4:Off, Unlock
0
17
U61
External warning input delay
0~120min
0
18
U62
Buzzer warning
0~1
0:Warning off
1:Warning on
19
U97
Baud rate setting
0 ~ 3
0: 2400bps
1: 4800bps
2: 9600bps
3: 19200bps
3
20
U98
Device address
1 ~ 99
----
1
21
U99
Password
0000~9999
1111
22
End
Finished setting
ZL-620A-R:
No
Parameter
code
Function
Range
Note
Factory
setting
1
U10
Compressor power on delay time
1
~
100min
3
2
U11
Compressor MIN continuous work
time
0
~
100min
3
3
U12
Compressor run frequency
0
~
8
0: Disable
5
4
U20
Room temperature sensor
calibration
-9.9
~
+9.9
0
5
U21
Defrosting sensor calibration
-9.9~+9.9
0
6
U22
Temperature difference
0.1
~
+10.0
℃
The hysteresis
of control
1.0
7
U30
Defrosting cycle
0~180 hour
0: Not defrost
12
8
U31
Defrosting
﹙
end
﹚
time
1
~
180min
30
9
U32
Defrosting end temperature
0.5
~
50
℃
15
10
U33
Dripping water time
0
~
180min
5
11
U34
Over temperature warning delay
time after defrost ends
0~180 hour
0: Disable
2
12
U35
Defrost when the device starts
0~1
0: Disable
0
Содержание ZL-6 A-R Series
Страница 10: ...Electrical wiring diagram ...