SMRI2

along the whole measuring length.  Mechanical 
plays could compromise the proper counting;

the   surface   of   the   magnetic   ring   should   be 
cleaned periodically using a soft cloth to remove 
dust, chips, moisture etc.

9 - Troubleshooting

The   following   list   shows  some   typical   errors  that 
could occur during installation and operation of the 
magnetic measurement system.

Fault:

The system does not work (no pulse output).

Possible cause:

The   ring   or   the   sensor   has   been   mounted 
incorrectly.

A magnetic part has been inserted between the 
sensor   and   the   substrate.   Only   non-magnetic 
materials are allowed between the sensor and 
substrate.

The  sensor touches the substrate  because  the 
tolerance   gap   between   the   sensor   and   the 
substrate   is  not   met.  Check  the  sensor   active 
side if damaged.

The sensor has been damaged by short circuit, 
inversion of polarity or wrong connection.

Fault:

The measured values are inaccurate.

Possible cause:

The   mounting   tolerances   are   not   thoroughly 
met.

The connection cable runs near to high voltage 
cable or shield is not connected properly. See 
the section “6 - Electrical connections“.

The max. counting frequency of the receiving 
device is too low.

A section of the magnetic substrate has been 
damaged either mechanically or magnetically.

The measuring error is caused by torsion of the 
machine   structure.   Check   parallelism   and 
symmetry of machine movement.

MAN SMRI2 I_E 1.3.odt

14

www.lika.it

www.lika.biz

Содержание SMRI2

Страница 1: ...ali non utilizzare in ambienti esplosivi o infiammabili il mancato rispetto delle norme di sicurezza o delle avvertenze specificate in questo manuale considerato una violazione delle norme di sicurezz...

Страница 2: ...il codice di ordinazione e il numero di serie quando si contatti Lika Electronic per l acquisto di un ricambio o nella necessit di assistenza tecnica Per ogni informazione sulle caratteristiche tecni...

Страница 3: ...llo magnetico con il lato dell etichetta Reference come in Figura 2 Figura 2 Montaggio del sensore Nel caso di anelli con superficie magnetica di larghezza 10 mm allineare il sensore e l anello sullo...

Страница 4: ...2 8 pin Connettore M12 8 pin maschio lato contatti Codifica A 6 2 Caratteristiche del cavo M8 Modello cavo LIKA HI FLEX M8 Conduttori 6 x 0 14 mm2 2 x 0 22 mm2 Schermo Schermo a treccia in rame Diamet...

Страница 5: ...2 100 numero poli 182 Perci 32 182 5 824 fronti giro Da questo si ricavano i PPR encoder PPR encoder fronti giro 5 824 1 456 PPR 4 4 NOTA La direzione di conteggio standard il canale A precede il cana...

Страница 6: ...to ripetutamente a contatto con la superficie magnetica provocandone il guasto ispezionare la superficie attiva del sensore E stato provocato un cortocircuito sulle uscite oppure un inversione di pola...

Страница 7: ...SMRI2 MAN SMRI2 I_E 1 3 odt 7 www lika it www lika biz Pagina lasciata bianca intenzionalmente...

Страница 8: ...rence 1 3 Revisione istruzioni di montaggio revisione generale Lika Electronic Via S Lorenzo 25 36010 Carr VI Italy Tel 39 0445 806600 Fax 39 0445 806699 Italy eMail info lika it www lika it World eMa...

Страница 9: ...s personal and or the environment damage high current voltage and moving mechanical parts can cause serious or fatal injury warning Do not use in explosive or flammable areas failure to comply with th...

Страница 10: ...hen reaching Lika Electronic for purchasing spare parts or needing assistance For any information on the technical characteristics of the product refer to the technical datasheet Warning devices havin...

Страница 11: ...he sensor When the sensor is installed on magnetic rings having a 10 mm 0 4 wide magnetic surface line up both the sensor and the ring on the central axis as previously stated if the Reference track i...

Страница 12: ...ding 6 2 M8 cable specifications Type LIKA HI FLEX M8 Wires 6 x 0 14 mm2 2 x 0 22 mm2 Shield Tinned copper braid External 5 3 5 6 mm Impedance 148 Km 6 90 Km 2 Min bend radius x 7 5 The total length o...

Страница 13: ...er PPR result from the following calculation Encoder PPR edges rev 5 824 1 456 PPR 4 4 NOTE The standard counting direction the channel A leads the channel B is to be intended with ring rotating as in...

Страница 14: ...r and substrate The sensor touches the substrate because the tolerance gap between the sensor and the substrate is not met Check the sensor active side if damaged The sensor has been damaged by short...

Страница 15: ...SMRI2 MAN SMRI2 I_E 1 3 odt 15 www lika it www lika biz This page intentionally left blank...

Страница 16: ...ion 1 3 Mounting instructions updated general review Lika Electronic Via S Lorenzo 25 36010 Carr VI Italy Tel 39 0445 806600 Fax 39 0445 806699 Italy eMail info lika it www lika it World eMail info li...

Отзывы: