IF62 - IF63
6 – Operation and LEDs' function
6.1 IF62 transmitter's settings and LEDs
IF62 transmitter modules are local Masters. This means that they generate the
clock signals to be provided to the encoder/sensor. After connecting the wires,
the DIL switches located in the front side of the unit must be set in order to
adjust the clock features. To remove the protection front panel, gently press
down the latch at the top using a screwdriver.
6.1.1 SW1 DIL switch
SW1 DIL switch
Clock frequency for the encoder / sensor
ON
1 MHz
OFF
500 kHz
On behalf of a fast data update, the higher frequency has to be selected,
provided that the encoder/sensor allows it.
6.1.2 SW2 DIL switch
SW2 DIL switch
Width between the clock pulse sequences
ON
40 µs
OFF
20 µs
MAN IF62_IF63 I_E 1.2.odt
6 – Operation and LEDs' function
25 / 28