AMx36 • SSI & BiSS C-mode
4.2 M8 cable specifications
Model
: LIKA HI-FLEX sensor cable type M8
Cross section
: 2 x 0.22 mm
2
+ 6 x 0.14 mm
2
(24/26 AWG)
Jacket
: Matt Polyurethane (TPU) halogen free, oil, hydrolysis,
abrasion resistant
Shield
: tinned copper braid, coverage > 85%
Outer diameter
: 5.3 ÷ 5.6 mm (0.209” ÷ 0.220”)
Min. bending radius
: outer diameter x 7.5
Work temperature
: dynamic -40°C +90°C (-40°F +194°F) / fixed -50°C
+90°C (-58°F +194°F)
Conductor resistance : <90
/Km (0.22 mm
2
), <148
/Km (0.14 mm
2
)
4.3 GND connection
Minimize noise by connecting the shield and/or the connector housing and/or
the frame to ground. Make sure that ground is not affected by noise. The
connection point to ground can be situated both on the device side and on
user’s side. The best solution to minimize the interference must be carried out by
the user.
4.4 Zero setting/Preset input
The output position information at a point in the shaft rotation can be set
either to 0 (SSI interface) or to a desired value called preset (BiSS C-mode
interface; the preset value has to be set next to the
30). The Zero setting/Preset input allows the operator to activate the zero
setting/preset function by using an input signal sent by a PLC or other
controller. If not used, connect the Zero setting/Preset input to 0Vdc. To activate
the zero setting/preset function, connect the Zero setting/Preset input to +Vdc
for 100 µs at least, then discVdc; normally voltage must be at 0Vdc;
Zero setting/Preset must be set after Counting direction. We suggest setting the
zero setting/preset function when the encoder shaft is not running.
WARNING
In the BiSS C-mode interface model, the Zero setting/Preset input is active only
when the
enabled (the bit 2 in the register 49 = 0, see on page 26); otherwise the
hardware function is disabled.
NOTE
In the BiSS C-mode interface model, the preset can be activated also by using
the
Save parameters and activate Preset
For detailed information please refer to the
register on page 25; the
MAN AMx36 SSI_BiSS E 1.1.odt
4 - Electrical connections
15 of 36