This is a field option. You might not use this option with your Lightstat
TME
. You
may add this in the field to an existing Lightstat
TME
.
Mount the Remote Room Sensor on the wall 5’ to 7’ off the floor, in the area to be
controlled.
Use #18 gauge 2-conductor twisted pair cable between the Lightstat
TME
and the
Remote Room Sensor. Remote Room Sensors are unaffected by wire runs of up
to 500 feet.
Remote Room Sensor cables
do not
have polarity, either wire may be connected
to either terminal. Cables
do not
need to be shielded.
At the Lightstat
TME
end connect the 2-conductor cable to the two terminals
marked
Remote Room Sensor
.
Note:
The Lightstat
TME
must be powered Off and On in order to “read” a
change of switch settings.
When using a Remote Room Sensor make sure the
Remote Room Sensor
switch (#5) on the inside of the Lightstat
TME
is set to ON. The word
REMOTE
will appear in the display.