26
Questions... Call Tech Support at 800-292-2444
Symptom
Possible Cause
Solution
No Operation of
Heating or Cooling
Lightstat
TME
Power Off.
Press the System ON/OFF
button.
No Power to equipment or
Lightstat
TME.
Check switches, circuit
breakers, fuses, gas valve and
pilot.
Lightstat
TME
in Night
Setback.
See Light Adjustment on Page
19.
Lightstat
TME
at limit
temperature.
Check Display to verify the
Lightstat
TME
is set at its
Cooling Minimum or Heating
Maximum.
Display does not
come on during
Power-up
No power to the Lightstat
TME.
Verify 24 VAC is present at
terminal block by measuring
from R to C. If no voltage
present check breakers and
fuses.
Fan Blows Cold air in
Heating Season
Fan ON/AUTO is in the
wrong position.
Move Fan to Auto position by
pressing the FAN ON/AUTO
button.
Heat Fan Switch in wrong
position.
See setting the Heat Fan
switch on Page 15.
O/B switch set to wrong
position for Heat Pump.
See setting the O/B Switch on
Page 14.
Heating or Cooling
will not come ON
O/B switch set to wrong
position for Heat Pump.
See setting the O/B switch on
Page 14.
Time Delay holding Heating
or Cool Off.
Press the Check button to
cancel the time delays.
Green Setback Light
Stays ON or OFF
Improper Light Sensor
adjustment.
See Light Adjustment on Page
19.
Basic Troubleshooting