Lightsafe_ERTSLEDPT_Instructions_Rev01 

Front Cover LED Indicator Status 

All LED indicators Off: 

No AC supply present  

Charge LED 

On (Green): 

AC mains supply and battery connected  

LED Off: 

test mode or battery/test fault  

Status Indicator  

Red Flash 

Once

 every 3 seconds: 

Issue with the battery during the daily test  

Red Flash very quickly: 

Luminaire in manual/monthly/annual test mode 

Red Flash 

Twice

 every 3 seconds: 

Fitting failed test - Issue with the light output during auto-test  

Red Flash 

Three

 every 3 seconds:     Fitting failed test – the battery duration was not achieved during auto-test  

Failed Test / Reset: 

After a failed test and the fault has been rectified, the internal test button will 

need to be pressed for 3 seconds to activate a self-test or remove the 230v AC 

supply to reset the fault and LED indicator status. 

 

 

Maintenance 

Repairs should only be carried out by suitably qualified person 
Regular cleaning of luminaires should be carried out at regular intervals not only to ensure good optical performance 
but also ensure that dirt does not accumulate to such an extent as to impair the electrical or thermal safety of the 
fitting, this should be done with a soft damp cloth, do not use any chemicals or abrasives. 
Servicing should only be carried out after the fitting has been made electrically safe and the battery disconnected. 

 
Light Source Maintenance:

 the light source of this luminaire is not replaceable; in case the light source need to be 

replaced (e.g. at the end of its life), the whole luminaire shall be replaced. 
 

Environment: 

Please DO NOT dispose of electrical items or packaging as unsorted waste, use the recycling facilities provided by 

your local authorities. 

 

TESTING

 

 

Ensure the luminaires are tested in accordance with 5266-8:2004 / BS EN 50172:2004 

Daily:

   

Ensure the green charge LED is illuminated  

Monthly:

   Check the LED Indicator Status, if Green then the unit has passed the monthly test.  If the LED is flashing 2 

or 3 times every 3 seconds then then luminaire has failed and will require an engineer to investigate, 

record the result in the log book                                                                     

Annually:

  Repeat the monthly inspection and record the result in the log book.   If the LED is flashing 2 or 3 times 

every 3 seconds then then luminaire has failed and will require an engineer to investigate. 

Defects:

  Any defects or failures should be noted and recorded in the log book and actioned by a competent person 

as soon as possible 

 

 