Lightsafe_ERTSLEDPT_Instructions_Rev01
Automatic Self-Test Function
The luminaire has an integral automatic self-test function.
When the luminaire is connected to a 230v AC supply the luminaire will perform an automatic test, monthly and
annually. The first monthly test will be performed approximately between 16
th
to 30
th
day and the annual test will be
between 200
th
to 360
th
day from initial power on.
After the first annual test, the test routine will then be scheduled for every 30 days and every 360 day for the
monthly and annual tests. The luminaire will retain the testing schedule for approximately 7 days without a 230v AC
supply (the internal battery still has to be connected).
Automatic Daily Test
The luminaire checks daily if the lamps are connected, if connected these will be indicated by the two green LEDs on
the lid marked as ‘Lamp 1 OK’ and ‘Lamp 2 OK’, if there is an issue, the relevant lamp LED will be extinguished and
the “Status Indicator” will flash red twice every three seconds. Also as part of the daily check the fitting checks that
the battery is connected and that AC mains supply is present, if both are present then the Green Charge On LED on
the lid will be will be illuminated. If the battery is not connected or there is an issue with the battery the (Charge On)
LED will extinguish and the “Status Indicator” will flash Red once every three seconds. If there is no 230v AC supply
present all LED indicators on the lid will be extinguished and the luminaire will be in emergency mode.
Monthly /Annual Test
The luminaire performs an automatic 10 minutes duration self-test every month and an annual test for the full 3
hours duration. During the test all the LED indicators will be extinguished except for the (Status Indicator) which will
be flashing Red quickly to indicate the fitting is in test for the duration of the test, if the test has been completed and
satisfactorily then the (Charge On) and the two “Lamp Ok” LEDs will be a constant Green state.
If during the test there is an issue with the light output, then the (Charge On) LED will be off and the status indicator
will flash Red twice every three seconds.
If fitting does not complete the required emergency duration then the (status indicator) LED will flash Red three
times every three seconds.
Manual Test
The luminaire has an internal test button (on the PCB) which has two functions;
1.
When the button is pressed once, the schedule of self-test will be reset (i.e. from the 1
st
day installed).
2.
When the button is pressed for three seconds, the fitting will enter a self-test mode for 10 minutes with the
same LED indication as the monthly/annual test (see above).