ERTSLEDPT

 

3 hour Non Maintained LED Twinspot 

c/w Automatic Self-Test Function

 

 

 

 

 

 

 

 

Please read these instructions before installation and retain for the user/maintenance engineer for future reference.  

  

IMPORTANT NOTE:

  

The luminaire must be installed by a skilled electrician and to the most current electrical wiring and building 

regulations  

This product 

MUST

 be earthed 

 and 

NOT

 be subject to an electrical insulation test (500/1000v) which will not be 

covered by the warranty 

This product should not be modified in any way, if modified this will invalidate any warranties and Firesafe will not be 

liable for any damages caused 

The person carrying out the installation is to check and verify that the total load on the circuit, including the rating of 

the cable, fuse and/or circuit breaker is not exceeded 

It is the responsibility of the installer to consider any fire risks and breach in any fire protection barriers or partitions, 

and take the appropriate precautions 

Emergency lighting should be installed and maintained in accordance with BS5266 and BS EN50172. 

                                                     

 

INSTALLATION

 

1.

 

Ensure the mains supply is isolated 

2.

 

Remove the 4 screws securing the lid  

3.

 

If screws or bolts are used to secure the unit then consideration will need to be given as not to comprise the 
IP rating of the fitting for the environment the luminaire is to be installed  

4.

 

A permanent 230v AC supply is required to the live (L), 

 Earth and neutral (N) terminals on the PCB.   

5.

 

Ensure  a  gland  or  grommet  is  used  to  maintain  the  IP  rating  of  the  luminaire  and  that  ALL  electrical 
connections are made good with no loose strands 

6.

 

Plug the battery lead into connector on the PCB  

7.

 

Secure the lid with the 4 screws 

8.

 

Restore the AC mains supply, ensure the LED indicators on the front of the lid, green charge LED, lamp 1 & 2 
indicators are illuminated Green 

9.

 

Allow 24 hour to charge the batteries and record the installation date in the log book 

10.

 

After a 24 hour charge period test the luminaire for a full 3 hour duration by removing the 230v AC supply 

and record the date of the commissioning on the battery pack inside the luminaire and also in the log book 

11.

 

Subsequent testing should be carried out in accordance with the British/European standards and recorded in 

the log book 

 

 