Lightsafe_ERTSLEDPT_Instructions_Rev01
ERTSLEDPT
3 hour Non Maintained LED Twinspot
c/w Automatic Self-Test Function
Please read these instructions before installation and retain for the user/maintenance engineer for future reference.
IMPORTANT NOTE:
The luminaire must be installed by a skilled electrician and to the most current electrical wiring and building
regulations
This product
MUST
be earthed
and
NOT
be subject to an electrical insulation test (500/1000v) which will not be
covered by the warranty
This product should not be modified in any way, if modified this will invalidate any warranties and Firesafe will not be
liable for any damages caused
The person carrying out the installation is to check and verify that the total load on the circuit, including the rating of
the cable, fuse and/or circuit breaker is not exceeded
It is the responsibility of the installer to consider any fire risks and breach in any fire protection barriers or partitions,
and take the appropriate precautions
Emergency lighting should be installed and maintained in accordance with BS5266 and BS EN50172.
INSTALLATION
1.
Ensure the mains supply is isolated
2.
Remove the 4 screws securing the lid
3.
If screws or bolts are used to secure the unit then consideration will need to be given as not to comprise the
IP rating of the fitting for the environment the luminaire is to be installed
4.
A permanent 230v AC supply is required to the live (L),
Earth and neutral (N) terminals on the PCB.
5.
Ensure a gland or grommet is used to maintain the IP rating of the luminaire and that ALL electrical
connections are made good with no loose strands
6.
Plug the battery lead into connector on the PCB
7.
Secure the lid with the 4 screws
8.
Restore the AC mains supply, ensure the LED indicators on the front of the lid, green charge LED, lamp 1 & 2
indicators are illuminated Green
9.
Allow 24 hour to charge the batteries and record the installation date in the log book
10.
After a 24 hour charge period test the luminaire for a full 3 hour duration by removing the 230v AC supply
and record the date of the commissioning on the battery pack inside the luminaire and also in the log book
11.
Subsequent testing should be carried out in accordance with the British/European standards and recorded in
the log book