Lightsafe_EDL1PT_Instructions_Rev01
Automatic Self-Test Function
The luminaire has an integral automatic self-test function.
When the luminaire is connected to a 230v AC supply the luminaire will perform an automatic test,
monthly and annually. The first monthly test will be performed approximately between 16
th
to 30
th
day and the annual test will be between 200
th
to 360
th
day from initial power on.
After the first annual test, the test routine will then be scheduled for every 30 days and every 360 day
for the monthly and annual tests. The luminaire will retain the testing schedule for approximately 7
days without a 230v AC supply (the internal battery still has to be connected).
Please note there is no manual test button on this unit.
Automatic Daily Test
The luminaire checks daily if the battery is connected and that AC mains supply is present, if both are
present then the LED will be illuminated Green. If the battery is not connected or there is an issue
with the battery then the LED will change from Green to flash Red once every three seconds. If there
is no 230v AC supply present the LED will be lit at full brightness in emergency mode.
Monthly /Annual Test
The luminaire performs an automatic 10 minutes duration self-test every month and an annual test for
the full 3 hours duration. During the test the LED will be lit at full brightness (similar to emergency
mode), if the test is satisfactorily then the LED will return to a constant Green state.
If the fitting does not complete the required emergency duration then the LED will flash Red three
times every three seconds.