AF-3107 ARCHITECTURAL REMOTE STATION 

 Version 0.01   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

04/26/2011 

www.lightronics.com 
Lightronics Inc.   

 

 

 

 

509 Central Drive  Virginia Beach,  VA  23454   

 

 

 

   tel  757 486 3588 

 
 

INTRODUCTION 

 
The AF-3107 is a 6 scene, wall mount remote control 
unit intended for use with the Lightronics AR-1202 
Architectural dimmer.  The unit fits in a standard three 
gang wall switch box. 

 

All power and data connections are via a 4 wire 
communication bus between itself and the AR-1202 
dimmer. 

 

The unit provides manual fader control of 6 scenes.  A 
7th fader is provided as a master control for all six 
scenes.  Pushbutton switches are provided to activate a 
blackout and all full on selection.  LED indicators 
provide status feedback. 

 

Multiple units may be chained together to provide 
dimmer control from various locations.  The AF-3107 
may also be used with other Lightronics architectural 
remote stations. 
 

INSTALLATION 

 

CONNECTIONS 

 

 
 
 
 
 
The AF-3107 connects to the AR-1202 dimmer via a 
shielded 4 conductor cable arranged as 2 twisted pairs.  
A data grade, low capacitance cable (less than 25 pf 
per foot) is required to assure trouble free data 
transmission to and from the AF-3107.  One pair 
connects to the 

DATA  –

   

and 

DATA +

 signals.  The 

other pair carries the power 

(REMOTE V+)

 and 

COMMON

.  The cable shield should be connected to 

the 

COMMON

 

A connection diagram is provided at the end of this 
manual.

 

 

CONNECTING A SINGLE UNIT:  Connect the 4 
cable wires to the screw down terminals on the back of 
the unit.  Connect the cable shield to the 

REMOTE 

COMMON

 terminal.  The other end of the cable will 

connect to a terminal strip provided in the AR-1202 
dimmer unit.  See the AR-1202 owners manual for 
exact connection details. 

 

 
 
 

CONNECTING MULTIPLE UNITS: Follow the 
instructions above for a single unit for the first AF-
3107.  Connect the corresponding connector pins of the 
second unit to those of the first unit. 
 
MULTIPLE UNITS OF DIFERENT TYPES:  The AF-
3107 may be connected together with other Lightronics 
smart remotes.  These remotes all have the same 
connection scheme.  Connect the AF-3107 to the other 
remotes by connecting like signal names together 
(

REMOTE COMMON

 to 

REMOTE COMMON

 etc.).  

 

SCENE ASSIGNMENTS 

 
AF-3107s operate by fading scenes 51 thru 56 in the 
AR-1202.  The left hand end fader (#1) corresponds to 
scene 51.  If multiple AF-3107 units are used together 
then they will all operate scenes 51 - 56. 

 

It is possible to have an AF-3107 operate other scenes 
but the unit must be ordered with special programming. 
 

OPERATION

 

 
No setup or turn on procedure is needed.  When the 
AR-1202 unit is powered on, the AF-3107 will also be 
activated.  The AF-3107 will activate in the "all scenes 
off" State. 

 

The scenes activated by the AF-3107 must be created 
and stored in the AR-1202 prior to activation.   See the 
AR-1202 owners manual for detailed instructions for 
creating and storing scenes.  Scene numbers proceed 
from left to right at the AF-3107. 

 

The AF-3107 faders operate in a pile-on mode on a 
"greatest of" basis.  This means that the intensity of a 
dimmer channel will be at the intensity of the scene 
calling for the highest intensity level. 

 

The OFF button causes all six scenes to be blacked out 
(turned off). 

 

The ON button causes all six scenes to be fully 
activated (turned on). 
 
 
 
 
 
 

CAUTION 

Remove all power from the AR-1202 

before making connections 