manualshive.com logo in svg
background image

                     

 

 

 

 

 

 

Page 

of 

AF-2104 ARCHITECTURAL REMOTE STATION 

 Version 0.01   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

04/25/2011 

www.lightronics.com 
Lightronics Inc.   

 

 

 

 

509 Central Drive  Virginia Beach,  VA  23454   

 

 

 

   tel  757 486 3588 

 
 

INTRODUCTION 

 
The AF-2104 is a 4 scene, wall mount remote control 
unit intended for use with the Lightronics AR-1202 
Architectural dimmer.  The unit fits in a standard 
double gang wall switch box. 

 

All power and data connections are via a 4 wire 
communication bus between itself and the AR-1202 
dimmer. 

 

In addition to manual fader control of 4 scenes, 
pushbutton switches are provided to activate a blackout 
and full on selection.  LED indicators provide status 
feedback. 

 

Multiple units may be chained together to provide 
dimmer control from various locations.  The AF-2104 
may also be used with other Lightronics architectural 
remote stations. 
 

INSTALLATION 

 

CONNECTIONS 

 

The AF-2104 connects to the AR-1202 dimmer via a 
shielded 4 conductor cable arranged as 2 twisted pairs.  
A data grade, low capacitance cable (less than 25 pf 
per foot) is required to assure trouble free data 
transmission to and from the AF-2104.  One pair 
connects to the 

DATA  –  

and 

DATA +

 signals.  The 

other pair carries the power 

(REMOTE V+)

 and 

COMMON

.  The cable shield should be connected to 

the 

COMMON

 

A connection diagram is provided at the end of this 
manual.

 

 

CONNECTING A SINGLE UNIT:  Connect the 4 
cable wires to the screw down terminals on the back of 
the unit.  Connect the cable shield to the 

REMOTE 

COMMON

 pin.  The other end of the cable will 

connect to a terminal strip provided in the AR-1202 
dimmer unit.  See the AR-1202 owners manual for 
exact connection details. 

 

CONNECTING MULTIPLE UNITS: Follow the 
instructions above for a single unit for the first AF-
2104.  Connect the corresponding connector pins of the 
second unit to those of the first unit. 
 
 

 
 
MULTIPLE UNITS OF DIFERENT TYPES:  The AF-
2104 may be connected together with other Lightronics 
smart remotes.  These remotes all have the same 
connection scheme.  Connect the AF-2104 to the other 
remotes by connecting like signal names together 
(REMOTE COMMON to REMOTE COMMON etc.).  

 

SCENE ASSIGNMENTS 

 
AF-2104s operate by fading scenes 51 thru 54 in the 
AR-1202.  The left hand end fader (#1) corresponds to 
scene 51.  If multiple AF-2104 units are used together 
then they will all operate scenes 51 - 54. 
 
It is possible to have an AF-2104 operate other scenes 
but the unit must be ordered with special programming. 

 

OPERATION

 

 

No setup or turn on procedure is needed.  When the 
AR-1202 unit is powered on, the AF-2104 will also be 
activated.  It will activate in the "All Scenes OFF" 
condition. 
 
The scenes activated by the AF-2104 must be created 
and stored in the AR-1202 prior to activation.   See the 
AR-1202 owners manual for detailed instructions for 
creating and storing scenes.  Scene numbers proceed 
from left to right at the AF-2104. 
 
The AF-2104 faders operate in a pile-on mode on a 
"greatest of" basis.  This means that the intensity of a 
dimmer channel will be at the intensity of the scene 
calling for the highest intensity level. 
 
The OFF button causes all four scenes to be blacked 
out (turned off). 

 

MAINTENANCE AND REPAIR 

 

TROUBLESHOOTING 

 
Check the cable and its connections. 

 

If the unit is being used with an AR-1202 system - 
ensure that one (and only one) of the AR-1202 
dimmer(s) in the system is set to UNIT ADDRESS 00. 
 
 
 