Lowprofile CD7
Sleek and compact,
Lowprofile CD7
makes a dynamic
design statement
used individually
or in graceful
linear runs.
When suspended, the Lowprofile
CD7 appears to float in the
environment. The bold design
and full range of functions make
the Lowprofile CD7 ideal for
large open areas as well as
contained spaces. Its attractive
housing is made up of two
die cast end caps connected by
high quality aluminum extrusions.
Light shielding is by means of
a high performance semi-specular
parabolic louver or acrylic
prismatic lens.
Profiles
Architectural
Round
Square
Recessed
Cove
Accent
Custom
Lightolier Lighting Systems
Lightolier Lighting Systems are modular lighting systems that offer a wide selection of
geometric shapes, architectural profiles, scales and finishes.
These quality materials combined with a highly efficient reflector
system, make the Lowprofile CD7 ideal for settings requiring
generous overall illumination as well as those where a soft ambi-
ence is to be combined with controlled task lighting. The Lowprofile
is designed to provide both superior photometric performance in
either indirect/direct or direct light distributions. Whether stem
suspended, cable suspended or surface mounted, the Lowprofile
CD7 provides high performance in an attractive package.
Lighting Systems
Specifications
■
1
Housing:
Extruded aluminum. Die-cast end cap mechanically attached with no exposed fas-
teners. Concealed access holes in end plate for through wiring.
■
2
Lamping:
One, two or three T8 fluorescent lamps, as specified. Provided by others.
■
3
Reflector:
Accurate parabolic-shaped, die-formed semi-specular anodized aluminum reflector.
■
4
Shielding:
Louver or Lens as specified. Louver: parabolic-shaped, die formed semi-specular
anodized aluminum. Provides low brightness in lengthwise and crosswise views with
37 degree shielding lengthwise. Concealed latches operate from either side. Lens: extruded
100% acrylic clear prismatic lens.
Electrical
Specify 120 volt or 277 volt. 3 conductor, 12 gauge wire. Color-coded quick
connectors allow ease of connection for joiner modules. For special circuiting,
consult factory. Rapid start, HPF, class “P” thermally protected. PowerSpec
®
HDF
dimming ballast is available.
Mountings
Cable Suspension
(not shown) – 4 1/2" diameter flat canopy finished enamel white,
1/16" diameter stainless steel aircraft cable adjustable up to 36", adjustable cable
gripper.
Stem Mounting
(not shown) – 4 1/2" diameter flat canopy finished enamel white.
1/2" diameter stem. Chrome plate or white finish. Can be cut to length on job.
Self-aligning swivel provides adjustability up to 38 degrees. The stem assembly shall
meet or exceed the requirements set forth in the State of California Uniform Building
Code for suspended lighting fixtures installed in seismic zone four.
Surface and wall mounting
(not shown) – consult factory.
Finish
Powder coated baked white enamel. Custom colors available,
consult factory.
Options & Accessories
Fusing, two circuit switching, emergency batteries available – consult factory.
Labels
UL, ULc and IBEW.
Total
Ballast
Style Type
Mounting Length
Lamps
Color
& Voltage
Individual Fixtures
1. Order number of FIXTURES (fixture
comes with end caps, mountings
and power feeds).
Continuous Rows
1. Determine run length.
2. Order appropriate number of
FIXTURES to complete the run.
Fixtures can be bolted together and
through wired to complete long runs.
How to specify and order
CD7
WH
How to Specify
Style
Type
Lamps
CD7
1 = Direct Louver
1 = 1 lamp 4’
2 = Direct Lens
2 = 2 lamp 4’ or 1 lamp 8’
3 = Direct/Indirect Louver
3 = 3 lamp 4’ (T8 only)
4 = Direct/Indirect Lens
4 = 2 lamp 8’
6 = 3 lamp 8’ (T8 only)
Example: CD713
1
= Direct Louver
2
= Direct Lens
3
= Direct/Indirect
Louver
4
= Direct/Indirect
Lens
1
= Surface
2
= Cable
3
= Stem
4
= Wall
4
= 4 feet
8
= 8 feet
1
= 1 Lamp
per fixture
(4' fixture only)
2
= 2 Lamps
per fixture
(2 lamp cross
section per 4')
(1 lamp cross
section per 8')
3
= 3 Lamps
per fixture
(4' fixture only)
4
= 4 Lamps
per fixture
(2 lamp cross
section 8' only)
6
= 6 Lamps
per fixture
(3 lamp cross
section 8' only)
White
Blank
= T12 Magnetic
120v
2
= T12 Magnetic
277v
E1
= T12 Electronic
120v
E2
= T12 Electronic
277v
E81
= T8 Electronic
120v
E82
= T8 Electronic
277v
HD1
= T8 PowerSpec
HDF Dimming
120v
HD2
= T8 PowerSpec
HDF Dimming
277v
M71
= T8 Electronic
Dimming Ballast
120v
M72
= T8 Electronic
Dimming Ballast
277v
How to Order
Example: CD71283WHE1
2
1
4
3
3
1
/
4
"
9"
3 1/4"
9"
CD7 Direct Louver
Report No. LRL 699-4B
CD7-1
: 1 lamp T8
67.7% efficiency, 0%
∧
100%
∨
CD7-2
: 2 lamp T8
53.0% efficiency, 0%
∧
100%
∨
CD7-3
: 3 lamp T8
47.5% efficiency, 0%
∧
100%
∨
All performance data shown are for
2 lamp T8. For other lamping options
please refer to spec sheets.
Coefficients of Utilization
% Wall Reflectance
50
30
10
0
63
63
63
1
58
56
55
2
53
54
49
3
49
46
44
4
45
41
39
5
41
38
35
6
38
34
31
7
34
31
28
8
31
28
25
9
29
25
22
10
25
21
19
80%
Ceiling Reflectance
20%
Floor Reflectance
Room Cavity Ratio
Application Data
Fixture Spacing
Footcandles
Watt /Sq Ft
50’ x 70’ x 8.5’ Space
8’ x 8’ (64 sq ft /fixture)
35
1.0
8’ x 10’ (80 sq ft /fixture)
17
0.8
12’ x 16’ x 8.5’ Space
6’ x 8’ (48 sq ft /fixture)
34
1.2
8’ x 8’ x 8.5’ Space
8’ x 8’ (64 sq ft /fixture)
19
1.0
Reflectances: 80% Ceiling, 50% Wall, 20% Floor
Light Loss Factor = .75 (.88 BF x 8.5)
3 1/4"
9"
CD7 Direct Lens
Report No. LRL 282-5A
CD7-4
: 1 lamp T8
53.9% efficiency, 0%
∧
100%
∨
CD7-5
: 2 lamp T8
45.7% efficiency, 0%
∧
100%
∨
CD7-6
: 3 lamp T8
49.3% efficiency, 0%
∧
100%
∨
All performance data shown are for
2 lamp T8. For other lamping options
please refer to spec sheets.
Coefficients of Utilization
% Wall Reflectance
50
30
10
0
54
54
54
1
49
48
47
2
45
43
41
3
42
39
37
4
38
35
33
5
35
32
30
6
32
29
27
7
30
27
24
8
27
24
22
9
25
22
20
10
22
19
17
80%
Ceiling Reflectance
20%
Floor Reflectance
Room Cavity Ratio
Application Data
Fixture Spacing
Footcandles
Watt /Sq Ft
50’ x 70’ x 8.5’ Space
8’ x 8’ (64 sq ft /fixture)
38
1.0
8’ x 10’ (80 sq ft /fixture)
18
0.8
12’ x 16’ x 8.5’ Space
6’ x 8’ (48 sq ft /fixture)
36
1.2
8’ x 8’ x 8.5’ Space
8’ x 8’ (64 sq ft /fixture)
21
1.0
Reflectances: 80% Ceiling, 50% Wall, 20% Floor
Light Loss Factor = .75 (.88 BF x 8.5)
3 1/4"
9"
CD7 Direct/Indirect Louver
Report No. LRL 1282-5A
CD7-7
: 1 lamp T8
80.3% efficiency, 53.5%
∧
46.5%
∨
CD7-8
: 2 lamp T8
78.9% efficiency, 55.8%
∧
44.2%
∨
CD7-9
: 3 lamp T8
79.9% efficiency, 55.3%
∧
44.7%
∨
All performance data shown are for
2 lamp T8. For other lamping options please
refer to spec sheets.
Coefficients of Utilization
% Wall Reflectance
50
30
10
1
74
72
69
2
66
62
59
3
59
54
50
4
53
48
43
5
48
42
38
6
43
37
33
7
39
33
29
8
35
29
25
9
32
26
22
10
28
22
19
80%
Ceiling Reflectance
20%
Floor Reflectance
Room Cavity Ratio
Application Data
Ceiling
Susp.
Illum. Max.
Lum.
W/
Height
Dist.
(FC)
Lum.
Ratio Sq Ft
50' x 70' Space
10'
9' 18'
72
123
8.3
1.5
12'
10.5" 24"
60
92
7.4
1.3
12’ x 16’ Space
8'
9' 18"
71
119
6.9
2.0
8’ x 8’ x 5’ Cubicle R = 50%
12'
10.5'
24"
71
90
8.6
2.0
Reflectances: 80% Ceiling, 50% Wall, 20% Floor
Light Loss Factor = .75 (.88 BF x 8.5)
3 1/4"
9"
CD7 Direct/Indirect Lens
Report No. LRL 282-5B
CD7-10
: 1 lamp T8
84.1% efficiency, 57.8%
∧
42.2%
∨
CD7-11
: 2 lamp T8
78% efficiency, 54.6%
∧
45.4%
∨
CD7-12
: 3 lamp T8
83.6% efficiency, 54.6%
∧
45.4%
∨
All performance data shown are for
2 lamp T8. For other lamping options please
refer to spec sheets.
Coefficients of Utilization
% Wall Reflectance
50
30
10
0
83
83
83
1
73
71
68
2
66
62
58
3
59
54
50
4
53
48
43
5
48
42
38
6
43
38
34
7
39
34
30
8
36
30
26
9
33
27
24
10
29
24
20
80%
Ceiling Reflectance
20%
Floor Reflectance
Room Cavity Ratio
Application Data
Ceiling
Susp.
Illum. Max.
Lum.
W/
Height
Dist.
(FC)
Lum.
Ratio Sq Ft
50' x 70' Space
10'
9' 18'
71
123
8.4
1.5
12'
10.5" 24"
59
92
7.5
1.3
12’ x 16’ Space
8'
9' 18"
70
119
7.0
2.0
8’ x 8’ x 5’ Cubicle R = 50%
12'
10.5'
24"
70
90
8.7
2.0
Reflectances: 80% Ceiling, 50% Wall, 20% Floor
Light Loss Factor = .75 (.88 BF x 8.5)
Luminaire Row Spacing
Luminaire Row Spacing
400
800
1200
0
0˚
15˚
90˚
45˚
400
800
1200
0
0˚
15˚
90˚
45˚
400
400
800
800
0
0˚
15˚
45˚
150˚
90˚
120˚
400
400
800
800
0
0˚
15˚
90˚
180˚
150˚
120˚
45˚