GYMLYTE
GM4B4SVI232
Page 2 of 2
SURFACE FLUORESCENT, 4' OR 8' LENGTH, 12-5/16" WIDE WITH STEEL WIRE DOOR
2 OR 3 LAMP T8 OR T12
Lightolier
a Genlyte Thomas Company
www.lightolier.com
Technical Information: (978) 657-7600 • Fax (978) 658-0595
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
© 2002 Genlyte Thomas Group LLC (Lightolier Division)
A0902
Section 6A/Folio P30-10
Job Information
Type:
OPTIONS & ACCESSORIES
SPECIAL LENSES:
Substitute KA for VI (standard.)
FUSING:
Internal fast-blow fusing.
SUFFIX:
GLR
.
Internal slow-blow fusing.
SUFFIX:
GMF
.
RADIO INTERFERENCE FILTER
120 or 277 volt, 50 or 60 Hz. One per fixture
is standard. SUFFIX:
RF
.
STEM AND CANOPY SETS:
Suspends fixture 6", 12", 18" or 24" from surface.
(Four per fixture is recommended.)
Catalog Number: ASC6 CSP
(6"),
ASC12
CSP
(12"),
ASC18 CSP
(18"),
ASC24 CSP
(24")
ELECTRICAL/WIRING OPTIONS
Consult factory.
SPECIFICATIONS
PERFORMANCE:
In an installation of 2 lamp 32W luminaires in a room cavity
ratio of 1, reflectance 80% ceiling, 50% wall, 20% floor, the C.U. shall not be
less than .63.
SPECIFICATIONS (continued)
MATERIALS: Chassis parts
are die formed 20 gauge cold rolled steel, weld-
ed for rigidity with all seams finished smooth.
FINISH: Chassis exterior
—white baked polyester powdercoat finish
Cavity
—white baked polyester powdercoat, minimum reflectance 84%.
LENS:
VI
(standard). Pattern 12, .125" nominal thickness, extruded virgin acrylic lens
(average weight per square foot is 6.8 ounces).
KA
(optional) Extruded acrylic,
square based male conical prism, .156" overall thickness (similar to pattern 19).
ELECTRICAL:
Thermally protected class “P” ballast C.B.M. approved, non PCB.
If K.O. is within 3" of ballast, use wire suitable for at least 90°.
LABELS:
I.B.E.W./UL and C-UL.
ORDERING INFORMATION
Explanation of Catalog Number. Example: GM4B4SVI232120SOGLR
Other dimming options. Consult factory.
GM
GYMLYTE
HEAVY DUTY
SURFACE
LUMINAIRE
FIXTURE
LENGTH:
4
=4' Length
8
=8' Length
B
BODY STYLE:
B
=Surface
4
FIXTURE
WIDTH:
4
=12-15/16"
S
CEILING
TYPE:
S
=Surface
LENS/
SHIELDING TYPE:
VI
=Pattern 12 lens .125"
polycarbonate
(standard)
KA
=Pattern 19 lens .156"
nominal Prismatic lens
LAMP
QUANTITY:
2
=2 Lamp
3
=3 Lamp
LAMP TYPE/
FIXTURE LENGTH:
32
=T8
34
=T12
(Nominal 48")
VOLTAGE:
120 or 277
BALLAST TYPE:
1 & 2 Lamp Mag. T12
LE
< 20THD <10THD
1 & 2 Lamp Elec. T8
SO*
H
I
*
3-2 Lamp Elec. T8 (8')
SO*
H
I
*
1-3 Lamp Elec. T8
O3*
H3*
2-3 Lamp Elec. T8 (8')
O6*
H6*
LOL T8 Dimming
PS
–
*
Instant Start Standard
OPTIONS:
Add appropriate
suffix to catalog
no, ie: (
GLR
)
PHOTOMETRY
MODEL NO. GM4B4SVI232120SO
coefficients of utilization — zonal cavity method
(effective floor cavity reflectance 0.20)
RF
20
20
20
RC
80
50
30
RW
70
50
30
50
30
10
50
30
10
1
66
63
61
60
58
57
57
56
55
2
61
57
53
53
51
48
51
49
47
3
56
51
46
48
45
42
46
44
41
4
52
45
41
43
39
36
42
39
36
5
48
41
36
39
35
32
38
34
31
6
44
37
32
35
31
28
34
30
28
7
41
33
28
32
27
24
31
27
24
8
38
30
25
29
24
21
28
24
21
9
35
27
22
26
22
19
25
21
18
10
32
24
20
23
19
17
23
19
16
room cavity ratio
LER = FL - 52
IW - 62
BF - 0.88
Comparative yearly lighting energy cost per 1000 lumens = $4.61