background image

Job Information 

Type:

631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © 2009 Philips Group • C0609

Architectural Decorative

  4R35

Page 2 of 2 

Pendalux Traditional 35" Diameter Body 6-26/32/42 Triple Tube

ANGLE  MEAN CP  LUMENS

  495

497  

47

10 

490

15 

480  

136

20 

468

25 

450  

208

30 

430

35 

404  

253

40 

373

45 

340  

263

50 

304

55 

268  

240

60 

231

65 

190  

190

70 

154

75 

118  

126

80 

  85

85 

  56  

 68

90 

  44

CERTIFIED TEST REPORT NO. 4R35642A    

COMPUTED BY LSI PROGRAM **TEST-LITE**

LIGHTOLIER INDIRECT/DIRECT PENDANT FIXTURE                 

CAT. #4R35642SNU, 35” DIFFUSER              

6-42W T/E SYLVANIA LAMPS. LUMEN RATING = 3200 LMS.                

3-ADVANCE BALLAST #ICF-2S42-M2-LD, 120 VAC

TESTED ACCORDING TO IES PROCEDURES.  TEST DISTANCE EXCEEDS FIVE 

TIMES THE GREATEST LUMINOUS OPENING OF LUMINAIRE.

ANGLE  MEAN CP  LUMENS

  90 

44

  95 

235  

347

100 

757

105 

1311  

1339

110 

1681

115 

1932  

1913

120 

2163

125 

2341  

2083

130 

2442

135 

2546  

1973

140 

2654

145 

2727  

1707

150 

2764

155 

2785  

1290

160 

2818

165 

2679  

750

170 

2401

175 

2363  

231

180 

2540

C

ANDLEPOWER SUMMARY

DATE: MAR. 1, 2001
PREPARED FOR:
LIGHTOLIER, FALL RIVER, MA

ZONAL LUMENS AND PERCENTAGES

ZONE 

LUMENS % LAMP %LUMINAIRE

0-30 

424   

2.22 

3.23

0-40 

699   

3.64 

 

5.31

0-60 

1246   

6.48 

 

9.47

0-90 

1659   

8.64 

 

12.62

40-90 

1069   

5.01 

 

7.31

60-90 

414   

2.16 

 

3.15

90-180 

12631 

65.79 

 

95.98

0-180 

14269   

74.43 

 

100.00

**  EFFICIENCY = 74.4%  **

            COEFFICIENTS OF UTILIZATION ZONAL CAVITY METHOD

                   %EFFECTIVE FLOOR CAVITY REFLECTANCE = .20

 

80 

70 

50 

30 

10

 

50  30  10     50  30  10   50  30  10   50  30  10   50  30  10    0 

  1 

.58 .55 .53  .51 .49 .46  .37 .36 .35  .24 .24 .23  .13 .12 .12  .08

 

  2 

.51 .47 .43  .44 .41 .38  .32 .30 .28  .21 .20 .19  .11 .10 .10  .07

 

  3 

.45 .40 .36  .35 .35 .32  .29 .26 .24  .19 .17 .16  .10 .09 .09  .06

 

  4 

.39 .34 .31  .34 .30 .27  .25 .22 .20  .17 .15 .14  .09 .08 .07  .05

 

  5 

.34 .30 .26  .31 .26 .23  .22 .20 .17  .15 .13 .12  .08 .07 .06  .04

 

  6 

.31 .26 .22  .27 .23 .20  .20 .17 .15  .13 .12 .10  .07 .06 .06  .04

 

  7 

.28 .23 .19  .24 .20 .17  .18 .15 .13  .12 .10 .09  .06 .05 .05  .03

 

  8 

.25 .20 .17  .22 .18 .15  .16 .13 .11  .11 .09 .08  .06 .05 .04  .03

 

  9 

.22 .18 .14  .20 .16 .13  .15 .12 .10  .10 .08 .07  .05 .04 .04  .02

 

 10 

.20 .16 .13  .18 .14 .11  .13 .11 .09  .09 .07 .06  .05 .04 .03  .02

DETERMINED IN ACCORDANCE WITH CURRENT IES PUBLISHED PROCEDURES

Features

1.  Diffusing Reflector:

 White translucent acrylic, 3/16” thick.

2.  Inner Dirt Shield:

 White translucent acrylic, 1/8” thick.

3.  Chassis:

 Steel 20 gauge, semi-gloss white powder-coat finish.

4.  Suspension:

 Swivel (central) stem, 5/8” steel tube. Canopy, steel, 7” Dia. 

fastened internally, no exposed hardware. Permits installation on ceilings 
with slope of up to 45°. Complies with California Code.

5.  Rods:

 Reflector Bowl is suspended from a central point on three 3/16” steel 

rods.

6.  Lampholder:

 Multi-wattage, 4-pin, will accept either GX24q-3 or GX24q-4 

lamp base.

7.  Flange Trim:

 Steel 20 gauge, Plated or Painted finish.

Lamping (by others)

Compact Fluorescent:

 Triple Tube, 26, 32, or 42 Watts.

 

General Electric 

Osram/Sylvania 

Philips

 

26W Triple Tube 4-Pin 

(Amalgam) Compact 

Fluorescent Lamp

 

F26TBX/*/A/4P 

CF26DT/E/IN/* 

PL-T26W/*/4P

 

32W Triple Tube 4-Pin  

(Amalgam) Compact 

Fluorescent Lamp

 

F32TBX/*/A/4P 

CF32DT/E/IN/* 

PL-T32W/*/4P

  

42W Triple Tube 4-Pin 

(Amalgam) Compact 

Fluorescent Lamp

 

F42QBK/*/A/4P 

CF42DT/E/IN/* 

PL-T42W/*/4P

*Manufacturers’ color temperature designation.

Electrical

Ballast:

 Electronic, 2-Lamp HPF, Class P, Programmed Start. Universal Voltage 

120/277V, Multi-Wattage 26/32/42W.

6 Lamp 

26 Watt 

32Watt  

42Watt

Voltage

 

120V  277V 

120V  277V  120V  277V

Total Input Watts

 

168 

168 

210 

210 

279 

279

Max. Line Current

(amps)

 

2.22  0.96 

1.40 

2.80 

1.20 

1.60

Power Factor

 

>0.98  >0.98 

>0.98  >0.98  >0.99  >0.99

Ballast Factor

 

1.02  1.02 

0.96 

0.96  0.95  0.95

THD <10% Minimum Starting Temperature: -5˚F/-20˚C

Mounting 

Mounts directly to 4” outlet box, using crossbar hanger, supplied.

Labels

cULus  Suitable for Damp Locations.

Application Data

35 Inch Diameter

36’ x 36’ x 11’ Space

Luminaire 

Spacing: 12’ x 12’

 

 

Susp. Dist. 35”

2 Lamps 

26W 

32W 

42W

 

TTT 

TTT 

TTT

Illum. (FC) Maint. 

28 

37 

49

Lum.Ratio 

8/1 

8/1 

8/1

Watts/Sq. Ft. 

1.15 

1.42 

1.94

Reflectancies: 80% Ceiling, 50% Walls, 20% Floor.
Light Loss Factor = .75 (.88 BF x .85)
FC (footcandles) at 30” work plane.

Отзывы: