Document No.D210-00-401-IS 

Issue 1        02-08-16                         Sheet 1 of 6

 

                                                                                              

  

INSTRUCTION MANUAL (ATEX / IECEx) 

BExBGL2D LED BEACON

 

For use in Flammable Gas and Dust Atmospheres

 

 

 

 

 

 

 

1)  Warnings 

 DO NOT OPEN WHEN AN EXPLOSIVE 

ATMOSPHERE IS PRESENT 

 DO NOT OPEN WHEN ENERGIZED 

 POTENTIAL ELECTROSTATIC CHARGING 

HAZARD 

 COVER BOLTS CLASS A4-80 

 USE HEAT RESISTING CABLES AND CABLE 

GLANDS (RATED 110°C) AT AMB. 
TEMPERATURES OVER 40°C 

 

2)  Rating & Marking Information 

 

All units have a rating label, which carries the following 
important information:- 

 

Model No.:

  

BExBGL2D 

 

Input Voltage:

     DC Units    24V 

              AC Units    115V or 230V 

 

BExBGL2 Codes:  

Ex d IIC T6 Gb Ta. -50 to +60°C  
Ex d IIC T5 Gb Ta. -50 to +70°C 
Ex tb IIIC T60°C Db Ta. -50 to +40°C 
Ex tb IIIC T75°C Db Ta. -50 to +55°C 
Ex tb IIIC T90°C Db Ta. -50 to +70°C 

 

Certificate No.

     KEMA 00ATEX2006X 

 

 

IECEx KEM 10.0002X  

 

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

The units can be installed in locations with the following 
conditions: 

 

Area Classification Gas: 

Zone 1 

Explosive gas air mixture likely to occur in 
normal operation. 

Zone 2 

Explosive gas atmosphere not likely to 
occur in normal operation but may be 
present for short periods. 

 

Gas Groupings: 

Group IIA 

Propane 

Group IIB 

Ethylene 

Group IIC 

Hydrogen and Acetylene 

 

Temperature Classification: 

T1 

450ºC  

T2 

300ºC 

T3 

200ºC 

T4 

135ºC 

T5 

100ºC  

T6 

85ºC  (up to 65

°

C ambient) 

 

Area Classification Dust: 

Zone 21 

Explosive dust air mixture likely to occur in 
normal operation. 

Zone 22 

Explosive dust air mixture not likely to 
occur in normal operation, and if it does, it 
will only exist for a short time. 

 

Dust Groupings: 

Group IIIA 

Combustible Dusts 

Group IIIB 

Non-Conductive Dust 

Group IIIC 

Conductive Dust 

 

Maximum Surface Temperature for Dust Applications: 

90ºC 

 

IP Rating:

  

IP66/67 to EN/IEC60529 and IP6X to 
EN/IEC60079-0, EN/IEC60079-31 

 

Equipment Category:

 

2G / 2D 

 

Equipment Protection Level:

 

Gb / Db 

 

Ambient Temperature Range:

 

-50°C to +70°C Gas Groups IIA, IIB and IIC 
-50°C to +70°C Dust Groups IIIA, IIIB and IIIC 

0518 

II  2G 
II  2D 

Epsilon x 
Equipment Group and 
Category: 

CE Marking 
Notified Body No. 

BExBGL2D 