background image

8

  

(24)

LIFTINGITALIA S.r.l.

Via Cadu�  del Lavoro, 16 -  43058 Bogolese, Sorbolo (PR) - Italy

Phone  +39 0521.695311  -  Fax  +39 0521.695313

www.li� ingitalia.com  -  info@li� ingitalia.com

3.  DESCRIZIONE PRODOTTO

3.1.  DESCRIZIONE GENERALE E TERMINOLOGIA

IM.TEC.077.IT_rev.2

   -  May 2019

EN

The electrical equipment of the domoFLEX lift is designed on the purpose to obtain the best possible integration between the elec

-

trical and mechanical parts. The main electrical components are as follows:

a. 

microprocessor card capable of communicating, through the serial 

interface card, directly with the buttons and signals in use;

b.  pre-wired compartment electric lines: made with double sheath 

cable and shunt boxes; quick installation system that does not 

require the laying of a conduit;

c.  car pre-wired electric lines

: composed of flexible flat cables alrea

-

dy connected to the edge of the machine; only the connection 

with the box in the pit is required.

PRODUCT DESCRIPTION

GENERAL DESCRIPTION AND TERMINOLOGY

INFORMATION

Содержание DomoFlex MM13

Страница 1: ... 43058 Bogolese Sorbolo PR Italy Phone 39 0521 695311 Fax 39 0521 695313 www li ingitalia com info li ingitalia com IM TEC 077 IT_rev 2 May 2019 EN sample image DomoFlex Screw driven lifting platform MM13 CONTROL CABINET INSTALLATION AND DIAGNOSTICS ...

Страница 2: ...olese Sorbolo PR Italy Phone 39 0521 695311 Fax 39 0521 695313 www li ingitalia com info li ingitalia com 20190525 IM TEC 077 IT_rev 2 May 2019 EN 2 General update 25 05 2019 1 General modifications for on board panel insertion 18 09 2017 Rev Description Data ...

Страница 3: ...NS OF THE INSTALLER 7 3 PRODUCT DESCRIPTION 8 3 1 GENERAL DESCRIPTION AND TERMINOLOGY 8 3 1 DESCRIZIONE GENERALE E TERMINOLOGIA 8 4 MM13 CONTROL CABINET PRINCIPAL COMPONENTS 9 4 1 SWITCHING POWER SUPPLY CBE5901 and CBE5902 9 4 2 ELECTROMOTIVE FORCE PANEL WITH MAINTENANCE AND EMERGENCY CONTROLS 9 4 3 ITF232 SERIAL INTERFACE CARD 10 4 4 ITF800 FLOOR AND CAR SERIAL CARD 10 5 FIRST RUN CONNECTION 11 6...

Страница 4: ...the corresponding safety measures can cause death or serious personal injury CAUTION The symbol indicates that failure to observe the relevant safety measures can cause minor or moderate personal injury or damage to the device NOTICE It is not a symbol of security It indicates that the failure to comply with relevant safety measures can result in property damage INFORMATION It is not a symbol of s...

Страница 5: ...ect drawing and in this manual any divergence from the prescribed procedure may affect the opera on and safety of the system and cause the immediate cancella on of the warranty Any modifica on or varia on made to the project and the to the assembly Instruc ons must be documented in detail and referred to LIFTING ITALIA S r l in order to allow the company an adequate assessment Under no circumstances...

Страница 6: ... deposited during the construc on of the sha Only nuts and bolts included in the supply must be used The bags containing the screws must be opened in correspondence with the respec ve opera ng phases indicated in this manual The instruc ons described in this manual refer to a reinforced sha to a fastening with mechanical expansion plugs of the stud type For the use of plugs in masonry other than t...

Страница 7: ...there is adequate ven la on for the smoke exhaust BEFORE STARTING THE INSTALLATION YOU NEED Arrange a material deposit area near the work area easily accessible and protected from the bad weather Prepare any li ing equipment to be used Check the presence of all materials using the list Check the state of all materials at the me of receipt on site and in case of damage or missing contact the suppli...

Страница 8: ...e elec trical and mechanical parts The main electrical components are as follows a microprocessorcardcapableofcommunicating throughtheserial interface card directly with the buttons and signals in use b pre wired compartment electric lines made with double sheath cable and shunt boxes quick installation system that does not require the laying of a conduit c carpre wiredelectriclines composedofflex...

Страница 9: ...CE NORMAL MODE switch allows to shift from normal mode to maintenance and vice versa every time you shift from maintenance to normal mode it is necessary to perform a reset by pressing both up and down buttons for more than 3 seconds Ascending button UP in maintenance and normal mode it commands the ascent when kept pressed Central button DOWN EMERGENCY red it forces a manual emergency manoeuvre W...

Страница 10: ...d if 1 second on and 1 second off d ST4 card connected if 1 second on and 1 second off It manages the floor and car buttons and signals connections on wiring diagram Diagnostic Led a DL1 correct operation if 1 sec on and 1 sec off fast flashing if jumper inserted interrupted or incorrect serial connections b DL2 if it flashes slowly the card is programmed the number of flashes between two long pau...

Страница 11: ...on panel b Connect a temporary 230Vac single phase power cable to the L N PE terminals present on the machine panel FIRST RUN CONNECTION INFORMATION To activate the movement of the machine press button 1 for an ascent and button 0 for a descent CAUTION The ascent command in maintenance mode has no electrical or mechanical limit so the machine will stop only when the button is released or when the ...

Страница 12: ... the exact floor level floor and car levels aligned 2 IS ascent sensor gradually move from the top the 150 mm magnet towards the sensor stopping just as the corresponding I13 LED on the card turns on 3 ID descent sensor gradually move from the bottom the 150 mm magnet to the sensor stopping just as the corresponding I11 LED on the card turns on MAGNETS LAYOUT STOP AND SLOW DOWN MAGNETS INFORMATION...

Страница 13: ...ew driven platform lift MM13 CONTROL CABINET INSTALLATION AND DIAGNOSTICS LEGEND IR Re phasing sensor ID Descent sensor stop and slowdown IS Ascent sensor stop and slowdown PB Lowest floor PI Intermediate floors PA Upper floor ZB Bypass zone Rall Slowdown distance Hereunder the recommended sensor location ...

Страница 14: ... del Lavoro 16 43058 Bogolese Sorbolo PR Italy Phone 39 0521 695311 Fax 39 0521 695313 www li ingitalia com info li ingitalia com Rall Rall Rall Rall Rall 150 PA PI PB IR IS ID ZB PA PI PB ZB ZB ZB ZB ZB IM TEC 077 IT_rev 2 May 2019 EN ...

Страница 15: ...sconnect al the battery terminals Disconnect all the users connecting the PE conductor by means of power supply clamps Measure the resistance values between the terminals indicated in the below table The table shows the test power V and the minimum resistance of the insulation between the circuits MΩ L1 L2 L3 LC L LV L 24 V 12 V PE 500 V 1 MΩ 500 V 1 MΩ 500 V 1 MΩ 250 V 0 5 MΩ 250 V 0 5 MΩ L1 L2 L...

Страница 16: ...gic signals on the card refer to the LEDs located in the respective terminals Each led is identified by a name to make reading easier I INPUT O OUTPUT are accompanied by a plate that has a short acronym to help identify the function CONTROL PROCEDURE ON FIRST START UP Bring the car to the bottom floor Close all doors and all safety devices so that the system is ready to be called system on Standby...

Страница 17: ...MAGNETIC SENSOR IS I14 NOT_USED I15 NOT_USED I16 NOT_USED I17 MAINS VOLTAGE FAILURE EM I18 BATTERY CHARGED BAT I20 FLOOR CALLS DISABLING XQ1 9 I21 PIT DOOR ACCESS UNLOCKED SQ_SPF I22 MANUAL DESCENT COMMAND SB_DN I23 MANUAL ASCENT COMMAND SB_UP I24 NORMAL MODE SWITCH SA_AUT I25 SCREW LIFTING AND BOTTOM SENSOR SQ_FON SQ_VIT I26 INVERTER FAULT INV FAULT I27 INVERTER SECURITY INV SEC I28 INVERTER BRAK...

Страница 18: ...R SAFETY DEVICES Description The car deactivates if one of its safety devices is triggered STANDBY only ON SQ_PER closed and SQ_BOR closed and SQ_MAD closed and SB_PEC closed and SQ_COL closed INCORRECT STATUS a check that perimeter safety device has not triggered SQ_PER terminal XQ12 b check that the edge safety device above the platform pushbutton panel has not triggered SQ_BOR terminal XQ9 c ch...

Страница 19: ...cription It activates if ID has a magnet in front STANDBY only ON ID closed with platform at stop level INCORRECT STATUS Check the position of the magnets with the car at the floor the ID sensor must have the ma gnet in front terminal XQ7 4 and XQ7 8 I12 Label CORRECTION MAGNETIC SENSOR Description It activates if IR has a magnet in front STANDBY only ON IR closed with platform at 0 stop level INC...

Страница 20: ...US a check that the door s that allow access to the pit are locked b check the wiring on terminal XF2 1 and XF2 3 I22 Label MANUAL DESCENT COMMAND Description Active if the manual descent button is pressed STANDBY only OFF The descent button is not pressed INCORRECT STATUS a check that the manual descent button is not pressed b check that terminal XQ1 20 is not powered I23 Label MANUAL ASCENT COMM...

Страница 21: ... that the bottom sensor is not crushed c check the wiring on terminals XF5 SQ_VIT and XQ17 SQ_FON Effect a reset procedure by holding UP and DOWN pressed for more than 3 seconds As soon as the Input status has been checked the Output status will be displayed as CORRECT STATUS of the following table Shoud they mismatch check the inputs once again and repeat the reset procedure Use the table below t...

Страница 22: ...oor opening command is given O5 Label PLATFORM DOOR CLOSURE Description It activates if the automatic platform door closure command is given It is triggered by the operator on the platform STANDBY only OFF IF LED is ON Door closure command is given O6 Label EMERGENCY BUTTON Description It activates if the EMERGENCY button on the FEM panel is pressed STANDBY only OFF IF LED is ON If the EMERGENCY b...

Страница 23: ...is given O10 Label FLOOR DOORS CLOSURE Description Active at each stop for a certain time can NOT be set STANDBY only OFF IF LED is ON Door closure command is given O16 Label BRAKE COMMAND Description Active during each run STANDBY only OFF IF LED is ON INCORRECT STATUS Check that the conditions are in place to be able to give the run command O17 Label ELECTRIC LOCK COMMAND Description Active if t...

Страница 24: ...r door closure contact 9 Car door open Check the car door closure contact 10 Brake command error Check that the inverter correctly gives the command to the brake motor 11 Inverter error Refer to the inverter manual 12 Access to the pit Check the bottom floor door contact DIAGNOSTICS BY MEANS OF BLINKING CODE INFORMATION Each single error is signaled by means of the related number of blinkings foll...

Отзывы: