LifeSafety Power FlexPower Скачать руководство пользователя страница 3

FlexPower AC Power System Installation Manual

ii

iii

 

Symbol Definitions

The following symbols are used throughout this manual.

h  

This symbol is intended to alert the installer of shock haz-

ards within the enclosure. Service should only be per-

formed by qualified service personel.

 

i  

This symbol is intended to alert the installer of impor-

tant information intended to help the installer avoid 

personal injury or property damage.

Warnings

h   

Installation and service should be performed only by 

qualified service personel and should conform to all 

local codes.

h   

To reduce the risk of electric shock or fire, do not 

expose this equipment to rain or moisture.

i   

This equipment shall be installed in a manner which 

prevents unintentional operation by employees, 

cleaning personel, or others working in the premesis, 

by falling objects, customers, building vibration, or 

similar causes.

i   

This equipment is not intended for use within the pa-

tient care areas of a Health Care Facility.

h   

Replace fuses only with the same type and rating as indi-

cated in the specifications section of this manual.

i   

To prevent impaired operation, ensure that all wiring is 

routed and secured to prevent accidental open or short 

circuit conditions.

Regulatory Information

The equipment discussed within this manual has been  

tested to the following standards:

•  UL2044       
•  UL294
•  CSA C22.2 #107.1

Conventions Used Within this Manual

Positional information (eg. top, bottom, up, down, left, 

right, etc.) is referenced with the board or enclosure in the 

the orientation shown in the illustrations in this manual.

Notes and Warnings

Содержание FlexPower

Страница 1: ...LifeSafety Power Inc PH 888 577 2898 TechSupport LifeSafetyPower com P03 003 Rev A09 AC Power System Installation Manual FlexPower...

Страница 2: ...tandoffs and pluggable wires to add additional system capability or capacity when needed Reliability All power supplies within the FlexPower system are fully fault protected and feature conformal coat...

Страница 3: ...nts unintentional operation by employees cleaning personel or others working in the premesis by falling objects customers building vibration or similar causes i This equipment is not intended for use...

Страница 4: ...ation and Operation 1 1 1 Mounting 1 1 2 Connections and Setup 2 1 2 1 Transformer Secondary Wire Colors 3 1 3 Typical Installation Wire Routing 4 1 4 Power Up and Basic System Verification Checklist...

Страница 5: ...Leave the heads of the fasteners approximately out from the surface Minimum fastener size should be 10 or larger 5 Hang the enclosure on the two fasteners and mark the locations of the two bottom mou...

Страница 6: ...voltage buss input is selected for the out put Jumper numbers correspond with the zone number eg JP1 is the jumper for OUT1 Possible settings are as follows Position 2 Left 28VAC 18V for 16 5 18V FPA...

Страница 7: ...4 17A 28V 3 57A FPA150A 0V 24V 6 25A 28V 5 4A FPA300A 0V 24V 12 5A 28V 10 7A Brown Common Voltage Current Voltage Current FPA200A 0V 16 5V 6 06 18V 5 56A Black Common Voltage Current Voltage Current 0...

Страница 8: ...outs AC Input Power must enter the enclosure via one of the 3 4 single knockouts The installation and all wiring methods shall be in ac cordance with ANSI NFPA70 and all local codes For Canadian Insta...

Страница 9: ...PA power supply Q 3 Ensure all green Zone LEDs are lit Q 4 Verify zone output voltage with a meter a If the zone s jumper is set in position 1 the voltage should be approximately 24VAC b If the zone s...

Страница 10: ...jumpers and fuses are in place and intact Contact Life Safety Power Incorrect voltage out of zone Zone jumper set incorrectly Verify the proper setting of the zone jumper AC Input voltage incorrect V...

Страница 11: ...th A8P 2 5A zone max Fuse Ratings A8 ATM 3A ATM 3A ATM 3A ATM 3A ATM 3A ATM 3A A8P N A N A N A N A N A N A BTU Output BTU 68 102 204 410 612 137 3 2 Temperature Specifications All Models Ambient Tempe...

Страница 12: ...tability of each product for their particular application LifeSafety Power makes no warranties as to the accuracy or completeness of the information and disclaims any liability regarding its use LifeS...

Отзывы: