RC Series Rackmount Installation Manual
iv
1
Installation and Operation
Use the following procedure when mounting an RC series
supply into a standard EIA 19" equipment rack .
1 . Ensure any internal configuration voltage selection and
fault detection settings are complete before mounting .
See Section 1 .3 of this manual for more information .
2 . Securely mount the included ears to the enclosure sides
using the eight included 6-32 countersunk screws (four
per ear) .
3 . Locate the rack-mounting holes in the ears of the en-
closure . (Figure 1)
4 . Slide the enclosure into an open 2U location in the rack
5 . Center the enclosure in the rack and secure with the
four 10-32 x 3/4" screws provided .
i
Use rails or other appropriate support for heavy en-
closures. Keep heavier components near the bottom of
the rack to reduce the risk of toppling of a top-heavy rack.
i
Ensure adequate spacing between the systems for
proper ventilation. If the internal temperature of the rack
is high, a ventilation fan for the rack should be considered.
1 .1 Mounting the Rackmount Supply into a Standard 19" Rack
The following pages cover the installation of the RC Series power supplies .
Section 1 – Installation & Operation
2
3
4
5
6
7
8
F
F
1
10 11 12 13 14 15 16
9
Figure 1 - The Enclosure Mounting Holes
Note: The RC Series is preconfigured for a 120VAC input. See
section 1.3.2 to set for a 230VAC input.
i