RC Series Rackmount Installation Manual

6

7

Installation and Operation

Field wiring connections are made on the rear panel after in-

stalling the enclosure into the rack . Field wiring connections 

are made to the removable terminal strips, which accept AWG 

12-22 wire . The back panel is also where the main AC power 

and optional ethernet connections are made .

1.4.1 Field Wiring

The RC Rackmount series has terminals for various inputs and 

outputs as follows:

Controlled Outputs

These terminals provide the distributed, controlled out-

puts to the load devices .  Depending on model, there will 

be either 8 or 16 output zones .  The output zone numbers 

will correspond with the the numbering of the zones on the 

front panel .  Polarity is indicated adjacent to each terminal .  

The output is configured by setting the front and rear panel 

jumpers and switches .

Control Inputs

These are the zone input terminal strips .  The terminals are 

labeled on the back panel near the terminal strip . 
• When using a dry contact input, the contact is connected 

across the A and B terminals .  When configured for a dry 

contact input, it is normal to measure a voltage across 

these two terminals .  This voltage is current limited and will 

not damage the activation contact .
• When using a voltage input, the voltage is connected to 

the B terminal .  The activation voltage must be common 

grounded with the system voltage .  The activation voltage 

must be between 12 and 24VDC nominal .  Do not connect 

anything to the A terminal of the input .
• When using an open collector (transistor) input, place a 

jumper across the A and B terminals and connect the open 

collector to the B terminal .  Note that the input source must 

be common grounded with the enclosure power source .

Distributed Outputs (optional)

If present, these terminals provide the non-controlled distrib-

uted outputs .  The output zone numbers will correspond with 

the numbering of the zones on the front panel .  Polarity is 

indicated adjacent to each terminal .

 

Battery (Bat+, Bat–)

This pair of terminals is for connection to a backup battery 

set, if required for the installation . Polarity is noted adjacent 

to the terminals . These terminals also charge the battery set .

NOTE:

 

Observe polarity or damage to the system will occur. 

Ensure the voltage of the battery set matches the voltage of 

the power supply.

NOTE:

 

It is the installer's responsibility to determine the 

proper battery size for the installation. See the Specifica-

tions section for battery standby current requirements.

DC1+, DC1–

The main DC output of the FPO power supply . The full cur-

rent of the FPO is available on these terminals at all times 

and is unaffected by the FAI input .

DC2+, DC2–

The DC2 output may optionally be controlled by the FAI in-

put . The full current of the FPO is available on these termi-

nals . The DC2 output may be set to power up when an FAI 

signal is received or to drop power when an FAI signal is 

received by changing the position of the DC2 fuse on the 

FPO before installing the RC RM into the rack .

AC Fault (ACF)

These terminals provide the AC Fault relay output from the 

FPO power supply . This relay signals when the internal FPO 

power supply detects a low or missing AC input voltage .

From the factory this output is set to provide a CLOSED 

connection when there is no fault . During a fault condition, 

the connection between these terminals will OPEN . To re-

verse this operation, see Section 1 .3 .5 of this manual .

System Fault (SF)

These terminals provide the System Fault relay output from 

the FPO power supply . This relay signals when any of the 

following conditions occur:

•  Missing Battery (If BAT DET jumper is ON)

•  Earth Ground Fault (If EARTH GND DET jumper is ON)

•  Battery voltage out of range

•  DC output voltage out of range

•  Ruptured fuse

•  Accessory Board Fault

•  Internal Fault
From the factory this output is set to provide a CLOSED 

connection when there is no fault . During a fault condition, 

the connection between these terminals will OPEN .To re-

verse this operation, see Section 1 .3 .5 of this manual .

FAI Input (V+, I+, I–, V–, L, L)

These terminals accept the optional FAI / Access Control in-

put for controlling the DC2 output . See 

Figure 4 - FAI Input 

Usage

 for more information . Connections are as follows:

•  L Terminals Latch Reset contact input . If a latching FAI 

Input is desired, a normally closed contact is placed 

across these terminals . When the FAI Input is activated, 

it will latch in the activated state until this contact is mo-

mentarily opened . If the latching feature is not desired, 

leave these terminals open .

•  V+ & V– Terminals These terminals are a low-current 

auxiliary voltage output to be used with a dry contact or 

open collector for activating the FAI Input .

•  I+ & I– Terminals These terminals are the input termi-

nals for the FAI Input . The FAI input is activated when a 

voltage between 9 and 30 volts is applied across these 
terminals in the correct polarity .

1 .4 Making the Wiring Connections

Содержание FLEXPOWER RC150 Series

Страница 1: ...LifeSafety Power Inc PH 888 577 2898 TechSupport LifeSafetyPower com RC Rackmount Installation Manual P03 050 Rev A03...

Страница 2: ...Mounting the Rackmount Supply into a Standard 19 Rack 1 1 2 RC Series Rackmount Power Supply Overview 2 1 3 Internal Pre Configuration 4 1 4 Making the Wiring Connections 6 Section 2 Configuration and...

Страница 3: ...ure that all wiring is routed and secured to prevent accidental open or short circuit conditions iThe system and any batteries if used should be tested at least once per year to ensure proper opera ti...

Страница 4: ...proved reliability a front removable chassis face plate for serviceability and is enclosed in a 16 gauge steel 2U Rack mount chassis The RC Series provides 12 and or 24 VDC power at 75W 150W and 250W...

Страница 5: ...enclosure in the rack and secure with the four 10 32 x 3 4 screws provided iUse rails or other appropriate support for heavy en closures Keep heavier components near the bottom of the rack to reduce...

Страница 6: ...0 A B 11 A B 12 A B 13 A B 14 A B 15 A B 16 A B CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 FLT 3 3 3 3 3 3 3 3 3 CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 FLT 3 3 3 3 3 3 3 3 3 CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 FLT 3 3 3 3...

Страница 7: ...I V L L These terminals accept the optional FAI input for controlling the DC2 outputs See Section 1 4 1 for more information 5 Bus Selection These jumpers select the output voltage for each output in...

Страница 8: ...rmation on setting the output voltage 1 3 4 Enabling or Disabling Battery Presence Detection The FPO power supply may be set to detect a missing bat tery set To enable battery presence detection place...

Страница 9: ...ETECT Earth GND 230VAC Jumper Battery DETECT Voltage SELECT B100 FPO NL Figure 3 Configuring the Internal Power Supplies AC Input cut jumper for 230VAC cut jumper for 230VAC AC ON AC Input AC ON FPO15...

Страница 10: ...termine the proper battery size for the installation See the Specifica tions section for battery standby current requirements DC1 DC1 The main DC output of the FPO power supply The full cur rent of th...

Страница 11: ...o larity FAI Deactivates when voltage is REMOVED or the polarity of the voltage is REVERSED Polarity shown in the ACTIVATED state FAI INPUT FAI INPUT L L L L V V I I I I V V FAI INPUT FAI INPUT L L L...

Страница 12: ...e Section 2 4 for more information To make the Ethernet connection connect one end of a stan dard RJ45 Ethernet cable to the connector on the back of the RC Series power supply See Figure 5 Connect th...

Страница 13: ...Selection Figure 7 These switches enable or disable FAI for the selected zone Switch 1 sets zone 1 switch 2 sets zone 2 and so on ON FAI Enabled When this switch is set to ON the zone s output will in...

Страница 14: ...ocal intranet via the ethernet port on the back of the enclosure See figure 10 See the included NetLink manual for more in formation ACF ACF DC2 DC2 BAT SF SF L L V I I V BAT DC1 DC1 MAIN OUTPUT 2 9 1...

Страница 15: ...11 Configuration and Usage PAGE INTENTIONALLY BLANK...

Страница 16: ...FullLoad NoBatt 88 120VAC60HzIn FullLoad NoBatt 88 120VAC60HzIn FullLoad NoBatt Battery Size Type 4 80AH Lead Acid or Gel Cell 4 80AH Lead Acid or Gel Cell 4 80AH Lead Acid or Gel Cell 4 80AH Lead Ac...

Страница 17: ...wer Inc or its affiliates 2015 LifeSafety Power Inc P03 050 Rev A03 02 16 RC Series Rackmount Power Supplies continued Specifications RC250 Series RC250B Series AC Input Voltage 120 230VAC 15 at 50 60...

Страница 18: ...wer or its distributors be liable for any incidental indirect or consequential damages arising from the sale resale use or misuse of the product Specifications are subject to change without notice In...

Отзывы: