Location Selection

The HRV must be located in a heated space where it will
be possible to conveniently service the unit. Typically the
HRV would be located in the mechanical room or an area
close to the outside wall where the weather hoods will be
mounted. If a basement area is not convenient or does not
exist, a utility or laundry room may be used.

Attic installations are not normally recommended due to:

A) the complexity of work to install

B) freezing conditions in the attic

C) difficulty of access for service and cleaning

The HRV unit must be installed in a horizontal position as
shown in the illustration below. The unit should be sus-
pended using the provided hanging straps.  If necessary,
the unit may be installed on a platform: however, the cabi-
net should be isolated from the platform to prevent
vibration transmission. The unit must be level. Sufficient
clearance at the front of the access door is required for
servicing the air filters and core. A minimum of 25"
(635mm) clearance is recommended so the door can be
opened. Four PVC reinforced polyester hanging straps are
provided for hanging the HRV from the basement floor
joists.

Suspending the Unit

The hanging straps should be attached to the unit at the
top end corners (mounting screws are already located on
the HRV case). Securely fasten the other end of the straps
to the floor joists with wide head nails (not supplied), mak-
ing sure the UNIT IS LEVEL. The straps are designed to
reduce the possibility of noise, resonance or harmonics;
therefore using the full length of the strap between the
HRV and the floor joists is recommended.

Weather Hood Location and Installation

Weatherhood kit includes two fixed-cover hoods with a
1/4” (6mm) mesh screen.

Exhaust Weather Hood Requirements

•  At least 6' (2 m) from the ventilation air intake*

•  At least 18" (457mm) above ground or above the

depth of expected snow accumulation* 

Installation                                                  

Improper installation, adjustment, alteration, 
service or maintenance can cause property 
damage, personal injury or loss of life.  
Installation and service must be performed by a 
qualified installer or service agency.

WARNING

Electric shock hazard.  Can cause 
injury or death.  Before attempting to 
perform any service or maintenance, 
turn the electrical power to unit OFF 
at disconnect switch(es).  Unit may 
have multiple power supplies.

WARNING

Connecting Appliances to the HRV

The following appliances should not be connected to the
HRV:

• clothes dryer

• range top

• stovetop fan

• central vacuum system

NOTE:  Connecting any of these to the HRV will      

invalidate your warranty.

Clearances and Requirements                                                 

Before installation, careful consideration must 
be given to how this system will operate if 
connected to any other piece of mechanical 
equipment, i.e. a forced air furnace or air handler, 
operating at a higher static. After installation, the 
compatibility of the two pieces of equipment 
must be confirmed, by measuring the air flows of 
the ventilator, by using the balancing procedure 
found in this manual.

It is always important to assess how the operation 
of any HRV may interact with vented combustion 
equipment (i.e. Gas Furnaces, Oil Furnaces, 
Wood Stoves, etc.)

NEVER install a ventilator in a situation where its 
normal operation, lack of operation or partial 
failure may result in the backdrafting or improper 
functioning of vented combustion equipment!!!

WARNING

Lint, dust or grease will collect in the HRV 
damaging the unit. 

CAUTION

Содержание 94-EXCHANGER

Страница 1: ...air that is being exhausted to condition the fresh air as it is being brought in These instructions are intended as a general guide and do not supersede local codes in any way Consult authorities who...

Страница 2: ...635 mm is recommended for servicing unit DRAIN SPOUT 1 2 O D DRAINTUBING 1 2 I D TAPE TO DRAIN TEE CONNECTOR DRAIN SPOUT 1 2 O D 24 VOLT MOTORIZED DAMPER 1204 Engineering Data HRV Dimensions HRV inche...

Страница 3: ...tor coupling with the damper shaft Align the damper in the fully closed position Using a 1 8 Allen key to tighten the set screw Dampers should now be in the fully closed position with no power Identif...

Страница 4: ...eather Hood Location and Installation Weatherhood kit includes two fixed cover hoods with a 1 4 6mm mesh screen Exhaust Weather Hood Requirements At least 6 2 m from the ventilation air intake At leas...

Страница 5: ...recommended min 36 1m recommended min 6 2m recommended min 18 460mm min 18 460mm min OUTSIDE CORNER INTAKE EXHAUST INSIDE CORNER Weatherhood arrangement requires a minimum of 6 2m separation and a min...

Страница 6: ...y be required to protect from condensate leakage The HRV and all condensate lines must be installed in a space where the temperature is maintained above the freezing point CAUTION Air Duct Design and...

Страница 7: ...line to be switched To confirm the proper polarity use a voltmeter or test lamp to ensure there is no power after the switch when the door is open Check between that point and ground on the cabinet A...

Страница 8: ...at highest operational speed 3 min recommended Insulated Duct DRAIN SPOUT TAPE TO DRAIN TEE CONNECTOR DRAIN SPOUT REMOTE DEHUMIDISTAT requires 2 wires anywhere humidity is a concern opens dampers to...

Страница 9: ...unt of straight duct The Pitot tube should be connected to a magnehelic gauge or digital manometer capable of reading from 0 to 0 25 in 0 62 Pa of water preferably to 3 digits of resolution The tube c...

Страница 10: ...rnace running at highest operational speed MAGNEHELIC MAGNEHELIC Placement of Pitot Tube HRV MAGNEHELIC Pitot Tube and Gauge Pitot Tube Air Flow Balancing Kit with magnehelic gauge Pitot tube hose and...

Страница 11: ...use dishwasher e install the clean filters f install clean core Note Core installation label on the outer end of the core To install the clean core a first mount the bottom flange of the core guide i...

Страница 12: ...12 Date Maintenance Performed Contractor Notes Maintenance Record Note It is important to maintain this product regularly to ensure optimal performance...

Страница 13: ...12 Date Entretien effectu Entrepreneur Notes Fiche d entretien Remarque pour un fonctionnement optimal il importe d entretenir ce produit r guli rement...

Страница 14: ...s servez jamais du lave vaisselle e Remettez les filtres propres en place f R introduisez le noyau nettoy Remarque L tiquette d installation du noyau doit tre son extr mit ext rieure Pour installer le...

Страница 15: ...ge des d bits d air avec tube de Pitot incluant un d bitm tre h lice un tuyau flexible et une mallette N B Ce sch ma n est offert qu des fins d illustration Les orifices de raccordement pour les canal...

Страница 16: ...ongueur de conduit droit Le tube de Pitot devrait tre connect un d bitm tre h lice ou un autre manom tre capable de faire une lecture de 0 0 25 pouce d eau 0 62 Pa de pr f rence avec une pr cision all...

Страница 17: ...t normalement quilibr alors que la fournaise fonctionne sa plus haute vitesse D SHUMIDISTAT DISTANCE qui exige deux fils s emploie partout o il y a beaucoup d humidit ouvre les registres pour assurer...

Страница 18: ...qui doit tre commut e Pour confirmer que la polarit est appropri e servez vous d un voltm tre ou d une lampe de v rification pour vous assurer que lorsque la porte est ouverte le courant lectrique est...

Страница 19: ...temp rature est maintenue au dessus du point de cong lation ATTENTION Conception et pose des conduites d air Quand l ensemble de canalisations est bien con u et cor rectement install on peut compter s...

Страница 20: ...d un appareil de traitement de l air fournaise efficacit moyenne ou lev e au moins 6 pieds 2 m tres des voies d acc s des canalisations de remplissage du mazout des compteurs de gaz des bacs ordures...

Страница 21: ...nseille d utiliser la pleine longueur des bandes entre le VRC et les solives de plancher Installation Toute erreur d installation de r glage de modification de r paration ou d entretien peut entra ner...

Страница 22: ...igner automatiquement le raccord du moteur et l axe du registre Alignez le registre en position compl tement ferm e Utilisez une cl Allen de 1 8 po pour serrer la vis de fixa tion Les registres devrai...

Страница 23: ...Le d bit d air habituel se situe entre 0 et 130 pieds cubes par minute Le d bit d air habituel se situe entre 80 et 130 pieds cubes par minute Date __________________________________________ tiquette...

Страница 24: ...u on expulse pour conditionner l air neuf qui arrive Ces instructions ne constituent qu un guide g n ral et ne remplacent aucunement les exigences des codes en vigueur Consultez les autorit s locales...

Отзывы: