Lifebreath 94-EXCHANGER Скачать руководство пользователя страница 2

2

MODEL 94-EXCHANGER-MD - Includes 24 volt motorized damper

21.25"

(540 mm)

STALE AIR

TO OUTSIDE

FRESH AIR

FROM OUTSIDE

STALE AIR

FROM INSIDE

FRESH AIR

TO INSIDE

15"

(380 mm)

18.75"

(475

 mm)

*All Duct Connections 6" (150mm) 

FILTER

BALANCING

COLLARS

FILTER

ALUMINUM HEAT

EXCHANGE CORE

*NOTE: 

Front clearance 

 of 25 inches (635 mm)  
 is recommended 
 for ser vicing unit. 

DRAIN

SPOUT -1/2" O.D.

(DRAIN TUBING - 1/2" I.D.)

TAPE

TO DRAIN

TEE

CONNECTOR

DRAIN

SPOUT - 1/2" O.D.

21.25"

(540 mm)

STALE AIR

TO OUTSIDE

FRESH AIR

FROM OUTSIDE

STALE AIR

FROM INSIDE

FRESH AIR

TO INSIDE

15"

(380 mm)

18.75"

(475

 mm)

*All Duct Connections 6" (150mm) 

FILTER

BALANCING

COLLARS

FILTER

ALUMINUM HEAT

EXCHANGE CORE

*NOTE: 

Front clearance 

 of 25 inches (635 mm)  
 is recommended 
 for ser vicing unit. 

DRAIN

SPOUT -1/2" O.D.

(DRAIN TUBING - 1/2" I.D.)

TAPE

TO DRAIN

TEE

CONNECTOR

DRAIN

SPOUT - 1/2" O.D.

24 VOLT MOTORIZED DAMPER

1204

Engineering Data - HRV

Dimensions HRV

inches

 

(mm)

Dimensions HRV

inches

 

(mm)

WARRANTY:

Lifetime warranty on Aluminum Heat Exchange Core.
Five year warranty on all other parts.

MODEL 94-EXCHANGER - No damper. Optional kit (99-MD-KIT) can be added

Typical airflow is between 0 cfm and 130 cfm.

Typical airflow is between 60 cfm and 130 cfm.

Date: ___________________________________________

Tag: _____________________Qty:___________________

Project: _________________________________________

Engineer: _______________________________________

Contractor: ______________________________________

Supplier: ________________________________________

Quote#: _________________________________________

Submitted by: ____________________________________

Содержание 94-EXCHANGER

Страница 1: ...air that is being exhausted to condition the fresh air as it is being brought in These instructions are intended as a general guide and do not supersede local codes in any way Consult authorities who...

Страница 2: ...635 mm is recommended for servicing unit DRAIN SPOUT 1 2 O D DRAINTUBING 1 2 I D TAPE TO DRAIN TEE CONNECTOR DRAIN SPOUT 1 2 O D 24 VOLT MOTORIZED DAMPER 1204 Engineering Data HRV Dimensions HRV inche...

Страница 3: ...tor coupling with the damper shaft Align the damper in the fully closed position Using a 1 8 Allen key to tighten the set screw Dampers should now be in the fully closed position with no power Identif...

Страница 4: ...eather Hood Location and Installation Weatherhood kit includes two fixed cover hoods with a 1 4 6mm mesh screen Exhaust Weather Hood Requirements At least 6 2 m from the ventilation air intake At leas...

Страница 5: ...recommended min 36 1m recommended min 6 2m recommended min 18 460mm min 18 460mm min OUTSIDE CORNER INTAKE EXHAUST INSIDE CORNER Weatherhood arrangement requires a minimum of 6 2m separation and a min...

Страница 6: ...y be required to protect from condensate leakage The HRV and all condensate lines must be installed in a space where the temperature is maintained above the freezing point CAUTION Air Duct Design and...

Страница 7: ...line to be switched To confirm the proper polarity use a voltmeter or test lamp to ensure there is no power after the switch when the door is open Check between that point and ground on the cabinet A...

Страница 8: ...at highest operational speed 3 min recommended Insulated Duct DRAIN SPOUT TAPE TO DRAIN TEE CONNECTOR DRAIN SPOUT REMOTE DEHUMIDISTAT requires 2 wires anywhere humidity is a concern opens dampers to...

Страница 9: ...unt of straight duct The Pitot tube should be connected to a magnehelic gauge or digital manometer capable of reading from 0 to 0 25 in 0 62 Pa of water preferably to 3 digits of resolution The tube c...

Страница 10: ...rnace running at highest operational speed MAGNEHELIC MAGNEHELIC Placement of Pitot Tube HRV MAGNEHELIC Pitot Tube and Gauge Pitot Tube Air Flow Balancing Kit with magnehelic gauge Pitot tube hose and...

Страница 11: ...use dishwasher e install the clean filters f install clean core Note Core installation label on the outer end of the core To install the clean core a first mount the bottom flange of the core guide i...

Страница 12: ...12 Date Maintenance Performed Contractor Notes Maintenance Record Note It is important to maintain this product regularly to ensure optimal performance...

Страница 13: ...12 Date Entretien effectu Entrepreneur Notes Fiche d entretien Remarque pour un fonctionnement optimal il importe d entretenir ce produit r guli rement...

Страница 14: ...s servez jamais du lave vaisselle e Remettez les filtres propres en place f R introduisez le noyau nettoy Remarque L tiquette d installation du noyau doit tre son extr mit ext rieure Pour installer le...

Страница 15: ...ge des d bits d air avec tube de Pitot incluant un d bitm tre h lice un tuyau flexible et une mallette N B Ce sch ma n est offert qu des fins d illustration Les orifices de raccordement pour les canal...

Страница 16: ...ongueur de conduit droit Le tube de Pitot devrait tre connect un d bitm tre h lice ou un autre manom tre capable de faire une lecture de 0 0 25 pouce d eau 0 62 Pa de pr f rence avec une pr cision all...

Страница 17: ...t normalement quilibr alors que la fournaise fonctionne sa plus haute vitesse D SHUMIDISTAT DISTANCE qui exige deux fils s emploie partout o il y a beaucoup d humidit ouvre les registres pour assurer...

Страница 18: ...qui doit tre commut e Pour confirmer que la polarit est appropri e servez vous d un voltm tre ou d une lampe de v rification pour vous assurer que lorsque la porte est ouverte le courant lectrique est...

Страница 19: ...temp rature est maintenue au dessus du point de cong lation ATTENTION Conception et pose des conduites d air Quand l ensemble de canalisations est bien con u et cor rectement install on peut compter s...

Страница 20: ...d un appareil de traitement de l air fournaise efficacit moyenne ou lev e au moins 6 pieds 2 m tres des voies d acc s des canalisations de remplissage du mazout des compteurs de gaz des bacs ordures...

Страница 21: ...nseille d utiliser la pleine longueur des bandes entre le VRC et les solives de plancher Installation Toute erreur d installation de r glage de modification de r paration ou d entretien peut entra ner...

Страница 22: ...igner automatiquement le raccord du moteur et l axe du registre Alignez le registre en position compl tement ferm e Utilisez une cl Allen de 1 8 po pour serrer la vis de fixa tion Les registres devrai...

Страница 23: ...Le d bit d air habituel se situe entre 0 et 130 pieds cubes par minute Le d bit d air habituel se situe entre 80 et 130 pieds cubes par minute Date __________________________________________ tiquette...

Страница 24: ...u on expulse pour conditionner l air neuf qui arrive Ces instructions ne constituent qu un guide g n ral et ne remplacent aucunement les exigences des codes en vigueur Consultez les autorit s locales...

Отзывы: