background image

Pitot Tube Air Flow Balancing

It is necessary to have balanced air flows in an
HRV. The volume of air brought in from the outside
must equal the volume of air exhausted by the
unit. If the air flows are not properly balanced then:

• The HRV may not operate at its 

maximum efficiency

• A negative or positive air pressure 

may occur in the house

• The unit may not defrost properly

• Failure to balance the HRV may 

void warranty

Prior to balancing, ensure that:

1. All sealing of the ductwork system has been 

completed.

2. All of the HRV's components are in place 

and functioning properly.

3. Balancing dampers are fully open.

4. Unit is on high speed.

5. After taking readings of both the stale air to

the HRV duct and fresh air to the house duct,
the duct with the lower CFM ([L/s] velocity)
reading should be left alone, while the duct
with the higher reading should be dampered
back to match the lower reading.

6. Return unit to appropriate fan speed for 

normal operation.

Balancing Procedure

The following is a method of field balancing an
HRV using a Pitot tube, advantageous in 
situations when flow stations are not installed in

the ductwork. Procedure should be performed
with the HRV on high speed.

Choose the straightest section of duct between
the HRV and the weatherhoods. This will be
used for both the supply and return ducts.
Drill a small hole in the duct (about 3/16"), three
feet downstream of any elbows or bends, and
one foot upstream of any elbows or bends.
These are recommended distances but the 
actual installation may limit the amount 
of straight duct.

The Pitot tube should be connected to a 
magnehelic gauge or other manometer capable
of reading from 0 to 0.25 in. (0 - 62 Pa) of water,
preferably to 3 digits of resolution. The tube
coming out of the top of the Pitot is connected to
the high pressure side of the gauge. The tube
coming out of the side of the Pitot is connected
to the low pressure or reference side of 
the gauge.

Insert the Pitot tube into the duct, pointing the tip
into the airflow.

For general balancing it is sufficient to move the
Pitot tube around in the duct and take an 
average or typical reading. Repeat this 
procedure in the other (supply or return) duct. 
Determine which duct has the highest airflow
(highest reading on the gauge). Then damper
that airflow back to match the lower reading from
the duct. The flows should now be balanced.

Actual airflow can be determined from the gauge
reading. The value read on the gauge is called
velocity pressure. The Pitot tube comes with a
chart that will give the air flow velocity based on
the velocity pressure indicated by the gauge.
This velocity will be either feet per minute or
metres per second. To determine the actual 
airflow, the velocity is multiplied by the cross
sectional area of the duct being measured.

25

Содержание 40DHW

Страница 1: ...BE COMPLETED BY CONTRACTOR AFTER INSTALLATION OPERATION SIZING AND INSTALLATION MANUAL For Models 40DHW T Up Flow Model 60DHW T Up Flow Model 40DHWDF T Down Flow Model 60DHWDF T Down Flow Model 40DHWH...

Страница 2: ...on and Purpose 4 Combo System Basic Principle 5 Specifications 12 21 Installation 22 27 Plumbing 28 Electrical 29 30 Optional Dehumidistat 30 Start Up Procedure 31 Operation 32 Troubleshooting 33 34 S...

Страница 3: ...s to be concerned about Your domestic hot water heater boiler now provides the heat source for your furnace This Operating and Installation Guide will help you learn about your LIFEBREATH Clean Air Fu...

Страница 4: ...uses is reduced in temperature to minimize a scald hazard potential Combining two or more end uses such as space heating and the heating of domestic hot water in a single system has the potential to...

Страница 5: ...are normally open systems Combo System Basic Principles 5 WATER HEATER DOMESTIC HOT WATER SUPPLY AIR BLOWER HEATING COIL HRV ERV CORE CHECK VALVE RETURN AIR COLD WATER INLET ANTI SCALD VALVE WHEN REQU...

Страница 6: ...omestic Hot Water and Space Heating Operation When both return water from the space heating loop and new cold water replacing domestic water being used enters the water heater the mixed entering water...

Страница 7: ...istance to flow Gate valves have a greater susceptibility to chatter noise and malfunction with age Gate valves tend to be less expensive than the other type of valves The ball valve can be used as a...

Страница 8: ...ir and to remove air from the heating loop when commissioning a system The drain valve should be near the low point of the return piping system upstream of the shut off valve and is preferred to be ne...

Страница 9: ...r from the municipal supply The Anti Scald valve must be thermostatically controlled and approved to the ASSE standard No 1016 and 1017 for use as an anti scald device Note There are a number of press...

Страница 10: ...ater flow rate GPM Air Handler return air temperature Air Handler air flow rate CFM The hot water inlet temperature is typically 140 F 60 C If this temperature must be increased to achieve higher outp...

Страница 11: ...ater millimeters of water Note Although the water in the combo system is pressurized by the domestic water system the pump is required to create water flow in the heating loop The domestic water syste...

Страница 12: ...nded for regions where the temperature does not drop below 25 F 4 C Filters Washable air filters in exhaust and supply air streams of ventilation section 1 pleated in return plenum side Case Prepainte...

Страница 13: ...8 9 48 7 40 6 71 2 69 0 57 0 47 5 81 7 79 1 65 3 54 4 92 2 89 3 73 7 61 3 102 7 99 5 82 1 68 3 113 3 109 7 90 4 75 2 5 GPM 130 140 150 160 170 180 64 7 62 4 50 7 41 8 75 8 73 1 59 3 48 8 86 8 83 8 67...

Страница 14: ...160 170 180 48 0 44 1 41 7 38 7 56 2 51 7 48 8 45 5 64 5 59 3 56 0 51 9 72 8 66 9 63 2 58 6 81 2 74 6 70 4 65 3 89 6 82 3 77 6 72 0 5 GPM 130 140 150 160 170 180 50 5 46 1 43 5 40 0 59 1 54 0 50 9 46...

Страница 15: ...0 6 71 2 69 0 57 0 47 5 81 7 79 1 65 3 54 4 92 2 89 3 73 7 61 3 102 7 99 5 82 1 68 3 113 3 109 7 90 4 75 2 5 GPM 130 140 150 160 170 180 64 7 62 4 50 7 41 8 75 8 73 1 59 3 48 8 86 8 83 8 67 9 55 9 98...

Страница 16: ...9 67 8 61 9 58 3 53 7 76 5 69 8 65 8 60 5 85 3 77 8 73 3 67 4 94 1 85 8 80 8 74 3 890 790 740 660 40 7 38 0 36 5 33 8 47 7 44 5 42 7 39 6 54 8 51 0 49 0 45 5 61 9 57 6 55 3 51 3 CFM 5 WG 69 0 64 3 61...

Страница 17: ...2 2 89 3 73 7 61 3 102 7 99 5 82 1 68 3 113 3 109 7 90 4 75 2 5 GPM 130 140 150 160 170 180 64 7 62 4 50 7 41 8 75 8 73 1 59 3 48 8 86 8 83 8 67 9 55 9 98 0 94 5 76 6 63 0 109 2 105 3 85 3 70 1 120 4...

Страница 18: ...46 2 42 9 34 6 53 2 52 1 48 4 39 0 59 2 58 0 53 8 43 4 65 3 63 9 59 3 47 8 36 7 36 0 33 3 26 6 43 0 42 0 38 9 31 1 49 2 48 1 44 5 35 6 55 4 54 3 50 2 40 1 61 7 60 4 55 8 44 6 68 0 66 5 61 5 49 1 Spec...

Страница 19: ...25 F 4 C Filters Washable air filters in exhaust and supply air streams of ventilation section 1 pleated in return plenum side Case Prepainted galvanized steel for superior corrosion resistance Dimen...

Страница 20: ...F 4 C Filters Washable air filters in exhaust and supply air streams of ventilation section 1 pleated in return plenum side Case Prepainted galvanized steel for superior corrosion resistance Dimensio...

Страница 21: ...tional for energy efficient ventilation Enthalpic cores are recommended for regions where the temperature does not drop below 25 F 4 C Filters Washable air filters in exhaust and supply air streams of...

Страница 22: ...filter heat recovery core and components As a rule this unit should be installed adjacent to the hot water heater If this is not possible or if the piping layout is complex the total head pressure on...

Страница 23: ...event heat loss All local codes must be followed in determining the amount of insulation needed The ventilation section consists of two 6 15 2cm round ports located on the side of the cabinet which ve...

Страница 24: ...collars provided to form a seal between the collars and the cabinet The collars can then be fastened into place with screws Note the exhaust outlet is always the port on the bottom and the supply inle...

Страница 25: ...the supply and return ducts Drill a small hole in the duct about 3 16 three feet downstream of any elbows or bends and one foot upstream of any elbows or bends These are recommended distances but the...

Страница 26: ...increased by taking an average of multiple readings as outlined in the literature supplied with the Pitot tube BUILT IN BALANCING DAMPERS BACK DRAFT DAMPER OUTSIDE HOOD INSULATED PIPE WITH VAPOUR BARR...

Страница 27: ...ny piping running through unconditioned space must be insulated to prevent heat loss and possible freezing of the line Stickers indicating direction of flow Supply to furnace and Return to water heate...

Страница 28: ...ducts the check valve is included with our manual kit for field installation between the air handler and hot water source The check valve should be installed in a vertical run of pipe with the flow of...

Страница 29: ...es phase and draws anywhere from 2 8 7 amps depending on fan speed The low voltage thermostat not provided connects to the R W terminals for heating and the R Y C terminals when calling for cooling Ca...

Страница 30: ...determine if this relay configuration is required 30 R G W Y C R G W Y Furnace T stat COM or Dehumidistat 24 Volt Relay NO Interface Relay NC TB 102 1099 Optional Dehumidistat An optional dehumidistat...

Страница 31: ...s instructions 3 Purge air from unit To do so open the supply shut off valve to the furnace Attach a garden hose to drain valve and drain water until you get a continuous flow Close the drain valve a...

Страница 32: ...lower will return to its preset speed or off Continuous low speed can be selected on the ventilation switch at the electrical box Ventilation The heat recovery ventilation HRV portion of the Clean Air...

Страница 33: ...ckage in the filter or some other obstruction 6 Make sure your water heater is sized large enough for heat load of house and for domestic hot water use 7 Air may still be in the water lines If so re p...

Страница 34: ...ts A rip in the vapor barrier or poorly sealed joints may cause condensation or ice to form on the ducting If this occurs replace the entire line Humidity levels are too low 1 If you have installed a...

Страница 35: ...ogical step by step method which should minimize the work and time involved in having the system meet the designed parameters The following conditions are assumed The air filter is in place All supply...

Страница 36: ...____________ Prov _____________ Postal Code ________________ Phone ____________ Fax ___________ Designer Signature _____________________________________________________________________________ Phone _...

Страница 37: ...ater Return Temperature ________ o F B 9 B 10 COOLING EQUIPMENT B 12 Cooling Output ________ Btu h ________ tons 80 125 of A 2 B 13 Manufacturers Flow Rate Ton ________ cfm ton B 14 Cooling Air Flow R...

Страница 38: ...or high volume applications If laundry is ensuite for a one bedroom dwelling increase tank size to 40 USG METHOD B domestic hot water usage for C 2 Activity Average Volume per usage USG X Times used...

Страница 39: ..._______ _________ x ________ ___________ ________________ _________ x ________ ___________ Measured Actual Length ___________ Total Effective Length ___________ TABLE D 1 EQUIVALENT LENGTHS FOR COPPER...

Страница 40: ...______ Phone ____________ Fax ___________ Designer Signature _____________________________________________________________________________ Phone _______________ Fax _______________ Date D ______ M ___...

Страница 41: ...resh Air Intake Air Flow _______________________________ Back Draft Damper installed in Stale Air to Outside Duct F 6 Required Supply Air Temperature ________ o F F 4 F 5 F 7 Returned Water Temperatur...

Страница 42: ...511 McCormick Blvd London Ontario N5W 4C8 Ph 519 457 1904 Fx 519 457 1676 Email nutech lifebreath com Website www lifebreath com...

Отзывы: