background image

11

FRAME ASSEMBLY

1. Take one end piece (locking tabs) and one side
piece (slots).  Stand both pieces vertically on the floor
or roof. See Figure 1.

2. Raise slightly the corner of the end piece (locking
tabs) and mate with side piece (slots), ensuring that
lower locking tab with leading edge is through slot
opening. See Figure 2.

3.Push down on top edge of end piece. Ensure that all
3 of the locking tabs are feeding into each correspond-
ing slot.  Once both pieces are flush, the process is
complete. See Figure 3.

4. Drive one spike provided into wood nailer strips at
each corner. See Figure 3.

FRAME APPLICATION AND LOCATION

This roof mounting frame provides necessary support
when the unit is installed.  The frame can be installed
directly on deck having adequate structural strength or
on roof supports under deck.

SECURING THE FRAME

To ensure proper mating with unit, it is critical that
mounting frame be squared to the roof, as follows:

1. With frame situated level in desired location on roof
trusses, tack weld one corner of frame.

2. Measure frame diagonally from one corner to the
opposite corner. Repeat with the remaining two cor-
ners.  These dimensions must be equal for the frame
to be square.

3. It is extremely important to sight frame from all cor-
ners to ensure that the frame is not twisted across top
side.  Shim frame under any low sides.

4. After frame has been squared, straightened and
shimmed, weld or attach frame securely to roof.

MAX. SLOPE TOLERANCE: 

1/16" per linear

foot in any direction.

Note specification of duct location on bottom of
HRV when positioning cross members (duct cavity).

side piece

slot for tab 

wood nailer strip 

side piece 

slot for tab

locking tab

spike

wood nailer strips

tabs through slots

end piece

wood nailer strip 

end piece

locking tab       

Roof Curb Assembly

Figure 1

Figure 2

Figure 3

Roof Curb Assembly Instructions

Содержание 2500EFD

Страница 1: ...nstallation the compatibility of the two pieces of equipment must be confirmed by measuring the airflow s of the Heat Recovery Ventilator HRV Energy Recovery Ventilator ERV by using the balancing proc...

Страница 2: ...will help in cooling the incoming fresh air with the stale air that is being exhausted Table of Contents Introduction 2 Select Correct HRV 3 Specifications Model 2500IFD 4 Specifications Model 2500EF...

Страница 3: ...required 45 x 20 900 cfm 450 L s Bank Customers 25 Staff 9 Total 34 ASHRAE requirement 20 cfm 10 L s per person Ventilation required 34 x 20 680 cfm 320 L s Bar or Tavern Seats 50 Employees 7 Total 5...

Страница 4: ...n each air stream DUCT CONNECTIONS Four 24 X 16 610mm X 406mm CABINET 20 gauge powder coated galvanized steel G60 for superior corrosion resistance 16 gauge galvanized frame insulated with1 5 fibregla...

Страница 5: ...ar aluminum sensible heat recovery core Plate to plate type Slides out of either side of cabinet for service MOTORS Two single shaft PSC 3 speed 208 230V 5 1 amps 1 ph 1 hp BLOWERS Two direct drive ce...

Страница 6: ...ANK TIMER Mechanical timer to activate high speed 99 116 DEHUMIDISTAT VENTILATION CONTROL DVC Turns unit on off via slider switch and high low via built in dehumidistat 99 130 DEHUMIDISTAT Activates h...

Страница 7: ...used to control the unit see pg 9 Installation Tips 1 Whichever method is chosen to operate the 2500 keep in mind that Air to Air exchangers in general are not booster fans and are normally sized to v...

Страница 8: ...humidity level exceeds selected setting PART NO 99 130 CRANK TIMER Provides high speed ventilation as required Crank Timer 60 minute PART NO 99 101 ON OFF HIGH LOW COMMON I I I I I I I I I I I I I I I...

Страница 9: ...e where the surrounding air temperature does not fall below freezing point The exhaust air temperature must be above 60 F 16 C for proper defrost operation If the air temperature is too low the defros...

Страница 10: ...n and slope of drain lines Vibration isolators May be anchored to floor leaving space for drain connections 2500IFD Saddle mount not provided Hang unit with threaded rods and U channel members 2 X 4 u...

Страница 11: ...RAME To ensure proper mating with unit it is critical that mounting frame be squared to the roof as follows 1 With frame situated level in desired location on roof trusses tack weld one corner of fram...

Страница 12: ...elsewhere and provided by the contractor The 2500EFD has built in screens to prevent foreign objects from entering into the ductwork through the out side hoods NOTE It is extremely important to desig...

Страница 13: ...grilles should be located high on the wall If contaminants are heavier than air a lower placement of the grilles will be required Information on a contaminants specific gravity and toxicity should be...

Страница 14: ...wnstream of any elbows or bends and one foot upstream of any elbows or bends These are recommended distances but the actual installation may limit the amount of straight duct The Pitot tube should be...

Страница 15: ...d the HRV Electrical Connections System is 208 230V 1 phase 60 Hz This unit meets all local codes and requirements It is STRONGLY recommended that an electrical disconnect be installed prior to the HR...

Страница 16: ...UNIT Check design static pressure of air handler to ensure it is compatible with HRV B A ROOFTOP HEAT COOL UNIT SUPPLY DUCTWORK CEILING RETURN AIR PLENUM ROOF DECK STALE AIR EXHAUST HRV FRESH AIR SUP...

Страница 17: ...LOW TIMER ON OFF ON OFF 24V F1 XFRM1 240V 240 VAC 15 AMPS COMMON 24 VAC 24 VAC TI 109 07 97 5 AMP COMMON HIGH LOW HIGH LOW SNAP DISK C3 HIGH BLACK HIGH YELLOW COM BLUE MID RED LOW EXHAUST MOTOR EXHAU...

Страница 18: ...5A 5A ON OFF HIGH LOW SNAP DISK TM1 1 R2 1 R1 1 R3 1 R4 1 R3 1 R3 1 R3 1 Blk High Red Low Blk High Red Low Yel Com Yel Com Yel Com Yel Com XFMRI SM SM EM EM Exhaust Motor SM Supply Motor EM R2 R3 R1 R...

Страница 19: ...d London Ontario N5W 4C8 519 457 1904 or fax 519 457 1676 to find the name of your nearest dealer in order to repair the product The labour required to install any replacement part s shall be dealt wi...

Страница 20: ......

Отзывы: