4�10�3�5� Power status�
All the Modbus map addresses are hexadecimal.
The
0x04 function
is implemented for this variable.
This variable indicates the quadrant in which the device is operating.
Table 24:Modbus memory map: Power status
Power status
Variable
Address
Default value
Power status
7D1
-
The variable format is shown in
Table 25:
Table 25:Variable format: Power status�
Bit 7 Bit 6 Bit 5 Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
0
0
0
1:
Capacitive
1:
Inductive
1:
Generated
1:
Consumed
4�10�3�6� The unit’s serial number�
All the Modbus map addresses are hexadecimal.
The
0x04 function
is implemented for this variable.
Table 26:Modbus memory map: Serial number�
The unit’s serial number
Variable
Address
Default value
Serial number
578 - 579
-
4�10�3�7�
Device configuration variables.
All the Modbus map addresses are hexadecimal.
The
0x04
and
0x10 functions
are implemented for this variable.
The device’s Modbus function does not check whether the variables recorded are within the
correct margins, they are only checked when they are read from the EEPROM. So if any
parameter is recorded with an incorrect value the device will be configured with its default
value.
The Modbus configuration will not take effect until the device is reset.
4�10�3�7�1�
Transformation ratios�
Table 27:Modbus memory map: Transformation ratios�
Transformation ratios
Configuration variable
(3) (4)
Address
Valid data margin
Default
value
Voltage primary
2710 - 2711
1 - 599999
1
Voltage secondary
2712
1 - 999
1
Current primary
2713
1 - 10000
5
Current secondary
2714
1:
.../1A
5:
../5 A
5
(3)
All variables must be programmed at the same time.
79
Instruction Manual
MCA PLUS II