The programmed value will be deleted if the entered value is higher than the maximum
programming value.
Maximum programming value:
10000.
Minimum programming value:
1.
Press key
to access the next programming step
4�9�6� SECUNDARY NEUTRAL CURRENT (MODEL MCA PLUS II - ITF-IN)
The neutral current transformer secundary is programmed on this
screen.
Press key
for 3 seconds to edit the transformer secundary
value. The
prog
icon will be displayed on the bottom of the
screen.
Press key
to browse the two possible options for the current
transformer secondary (1A or 5A).
To validate the data, press
for 3 seconds and the
prog
icon will disappear from the display.
Press key
to access the next programming step
4�9�7� NUMBER OF QUADRANTS
The quadrant number on which the unit takes the measurement
is selected on this screen.
Press key
for 3 seconds to edit the number of quadrants. The
prog
icon will be displayed on the bottom of the screen.
Press key
to browse the two options:
2 or 4 quadrants.
To validate the data, press
for 3 seconds and the
prog
icon will disappear from the display.
Press key
to access the next programming step
4�9�8� MEASUREMENT CONVENTION
You can select the measurement convention of the device from
this screen.
To edit the measurement convention press key
for 3
seconds. The
prog
icon will be displayed on the bottom of the
screen.
The key
is used to browse the different options:
50
MCA PLUS II
Instruction Manual